Professional Documents
Culture Documents
Street Light Pole Voltage Drop Calculation - UNLOCK (1.1.17)
Street Light Pole Voltage Drop Calculation - UNLOCK (1.1.17)
Street Light Pole Cable Route System Detail Voltage Distribution at each Pole
System System Phase for Select Phase
Pole (From) Pole (To) P.F
Voltage (P-P) Voltage (L-N) Pole for Luminar
A B 415 230 1Ph R 0.75
B C 415 230 1Ph Y 0.75
C D 415 230 1Ph B 0.75
D E 415 230 1Ph Y 0.75
E F 415 230 1Ph Y 0.75
F G 415 230 1Ph B 0.75
G H 415 230 1Ph R 0.75
H I 415 230 1Ph Y 0.75
I J 415 230 1Ph B 0.75
J K 415 230 1Ph R 0.75
K L 415 230 1Ph Y 0.75
L M 415 230 1Ph B 0.75
M N 415 230 1Ph R 0.75
N O 415 230 1Ph Y 0.75
O P 415 230 1Ph B 0.75
P Q 415 230 3Ph - 0.75
Q
Voltage Drop Calculator Jignesh.Parmar www.electri
:Summary: :Voltage Drop Detail:
0.8 Km Cable Voltage Drop Permissible Actual Status
8 Watt Voltage Drop in R Phase 6.0% 3.81% O.K
16 Nos Voltage Drop in Y Phase 6.0% 5.27% O.K
32 Nos Voltage Drop in B Phase 6.0% 5.38% O.K
Cable Detail
Voltage
Rsistance Reactance Drop
(/Km) (/Km)
2.29 0.097 0.11%
2.29 0.097 0.22%
2.29 0.097 0.34%
2.29 0.097 0.45%
2.29 0.097 0.56%
2.29 0.097 0.67%
2.29 0.097 0.79%
2.29 0.097 0.90%
2.29 0.097 1.01%
2.29 0.097 1.12%
2.29 0.097 1.23%
2.29 0.097 1.35%
2.29 0.097 1.46%
2.29 0.097 1.57%
2.29 0.097 1.68%
2.29 0.097 1.00%