Report No:

Generator Inspection Report


Page | 1 OF 1

Genset Brand & Model : Perkins 250 KVA Client: Alba Generator
Maximum LOAD : 200 KW \ HZ Machine Code: AP 132 Work order NO: 2
Date of Inspection: 26-8-2017 Fuel type: Diesel Run hours: 7776.9 Hrs.

Engine serial number : WGHF 7204 N 10212 Y Ambient temp : 40 C Sound proof Yes

Oil Water Battery


Duration Exhaust Temp. C load Blowby Boost Exhaust
Press Temp. Volt. P.f A1 A2 A3 Hz V KW inch H20
Min % pressure colour
bar C V

10 4.1 63 380 28 0.98 101 101 100 50 398 69 35 OK OK OK

10 4.14 74 460 28 0.98 200 200 200 50 398 138 69 OK OK OK

ENGINE INSTRUMENTS Available Check ALTERNATOR CONTROLS Available Check

High Coolant Temperature Emergency Stop


Oil /Low Oil Pressure O/U Voltage Fault
Water /Low water Level O/U Frequency Fault
High Oil Temperature Reverse Power
Exhaust Temp. 3 Start attempts
Fuel Level Overload 110%
Audible Alarm Over speed
Compression Test Records
Cylinder NO: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Pressure (Bar) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

VIBRATION RECORDS (VELOCITY MM/S

POINT X Y Z
1
2
3
4
5
6
7
8
Evaluation:
1-Generator tested till 69% from its full load
2-All Parameters reading in the accepted range at 69% from its full load

Result:

Accepted

Inspected By WorkShop DEP Reviewed By Witnessed By

Name: Wagih Abd El Aziz Name:Wagih Abd El Aziz Name: Aly Kamal

Signature: Wagih Abd El Aziz Signature: Wagih Abd El Aziz Mechanical Dep.

Date : 26/08/2014 Date : 26/08/2014 Date : 26/08/2014

Page 1 of 1