Hydraulic Profile - Rev. 1.1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Parameter Unit Value

Scenario Summer Winter


0.1 Flowrates
m3/d 5000 5000
Influent flowrate
3 208,3 208,3
m /h
Mechanical pre-treatments - 1,60 1,60
Peak factor
Biological treatments - 1,10 1,10
3 250 250
m /d
Internal wastewater line 3
m /h 10,4 10,4
Ratio - 5,00 5,00
RAS (Return Activated Sludge) 3 27500 27500
m /d
Flowrate
m3/h 1145,8 1145,8
Ratio - 3,38 4,83
IMLR (Internal Mixed-Liquor Recycle) 3
m /d 18604 26577
Aerobic to anoxic stage Flowrate
3 775,2 1107,4
m /h
Ratio - 2,00 1,70
IMLR (Internal Mixed-Liquor Recycle) 3
m /d 11000 9350
Anoxic to anaerobic stage Flowrate
3 458,3 389,6
m /h
3 104
Membrane filtration tank drainage flowrate m /d
m3/h 104,0
3 -
Membrane soaking tank drainage flowrate m /d
3 41,6
m /h
Sludge dewatering drainage flowrate m3/d 123
3 21,5
m /h
0.2 Elevation data
Reference m 34,300
0.3 WWTP layout
Coarse screening - 1
Inlet pumping - 1
Grit removal - 2
Fine screening - 2
Number of lanes Biological treatments - 2
Membrane filtration - 2
Permeate holding - 1
Membrane soaking - 1
Sludge dewatering - 1
Parameter Unit Value
Scenario Summer Winter
1.1 Inlet piping
Number of parallel pipes - 1
Design flowrate 3 333,3 333,3
m /h
Slope - 0,50%
Strickler coefficient 1/3 110
m /s
Filling degree - 50% 50%
Wetted angle rad 3,14 3,14
F coefficient - 0,16 0,16
Calculated mm 381,2 381,2
Minimum internal diameter
Chosen mm 470,8
Material - PVC
Pipe Pressure - PN 8
Diameter mm OD 500
Effective F coefficient value - 0,09 0,09
Effective filling degree value - 37% 37%
Effective wetted angle value rad 2,61 2,61
Effective average flow value m/s 1,61 1,61
Elevation of the bottom of the pipe Final section m 26,800
Elevation of the free surface Final section m 26,940 26,940
1.2 Coarse screening
Design flowrate m3/h 333,3 333,3
Width of channel m 0,50
Length of channel m 6,00
Slope of channel - 0,50%
Strickler coefficient of channel m1/3/s 75
Water depth of channel m 0,163 0,163
Water depth in front of the screen m 0,215 0,215
Flow velocity in front of the screen m/sec 0,86 0,86
Distance between bars mm 15
Width of bars mm 10
Screen inclination 75
Shape coefficient of bars - 2,42
Distance of the upstream screening section from the inlet m 2,00
Head losses trough the screen m 0,051 0,051
Critical water level m 0,120 0,120
Initial section m 26,500
Elevation of the bottom of the channel Screening section m 26,490
Final section m 26,470
Initial section m 26,663 26,663
Upstream screening section m 26,705 26,705
Elevation of the free surface
Downstream screening section m 26,653 26,653
Final section m 26,590 26,590
1.3 Inlet pumping pit
Design flowrate m3/h 343,8 343,8
Maximum water level m 0,500 0,500
Minimum water level m 0,900 0,900
Elevation of the bottom of the pit m 25,500
1.4 Piping from grit removal to fine screening
Number of parallel pipes - 1
Design flowrate m3/h 171,9 171,9
Design average speed m/s 0,60
Calculated mm 318,3 318,3
Minimum internal diameter
Minimum internal diameter
Chosen mm 309,7
Material - SS AISI 304
Pipe Pressure - -
Diameter mm DN 300
Effective average flow m/s 0,63 0,63
Length m 10,00
Major head losses
Roughness coefficient - 140
(Hazen-Williams formula)
Hydraulic slope m/m 0,001 0,001
Inlet - 1
Outlet - 1
Elbow 90 - 5
Elbow 45 - 1
Minor head losses Expansion - 0
Contraction - 0
Tee - 0
Butterfly valve - 0
Gate valve - 0
Total head losses m 0,076 0,076
1.5 Fine screening
Design flowrate m3/h 171,9 171,9
Drum diameter m 1,00
Drum length m 2,00
Filling degree - 60%
Wetted angle rad 3,54
Active drum surface m2 3,54
Discharge coefficient - 0,70
Head losses trough the screen m 0,000 0,000
1.6 Piping from to fine screening anaerobic stage
Number of parallel pipes - 1
Design flowrate 3 171,9 171,9
m /h
Design average speed m/s 0,60
Calculated mm 318,3 318,3
Minimum internal diameter
Chosen mm 309,7
Material - SS AISI 304
Pipe Pressure - -
Diameter mm DN 300
Effective average flow m/s 0,63 0,63
Length m 8,00
Major head losses
Roughness coefficient - 140
(Hazen-Williams formula)
Hydraulic slope m/m 0,001 0,001
Inlet - 1
Outlet - 1
Elbow 90 - 1
Elbow 45 - 2
Minor head losses Expansion - 0
Contraction - 0
Tee - 0
Butterfly valve - 0
Gate valve - 0
Total head losses m 0,052 0,052
1.7 Pre-treatments bypass piping
Number of parallel pipes - 1
Design flowrate 3 333,3 333,3
m /h
Slope - 0,10%
Strickler coefficient 1/3 110
m /s
Filling degree - 70% 70%
Wetted angle rad 3,96 3,96
F coefficient - 0,26 0,26
Calculated mm 424,9 424,9
Minimum internal diameter
Chosen mm 470,8
Material - PVC
Pipe Pressure - PN 8
Diameter mm OD 500
Effective F coefficient value - 0,20 0,20
Effective filling degree value - 58% 58%
Effective wetted angle value rad 3,45 3,45
Effective average flow value m/s 0,89 0,89
Length of the pipe m 55,00
Initial section m 26,400
Elevation of the bottom of the pipe
Final section m 26,345
Initial section m 26,645 26,645
Elevation of the free surface
Final section m 26,590 26,590
Parameter Unit Value
Scenario Summer Winter
2.1 Distribution channel
Design influent flowrate m3/h 171,9 171,9
Design bypassed flowrate 3 57,3 57,3
m /h
Design effluent flowrate m3/h 114,6 114,6
Width of channel m 0,60
Length of channel m 7,00
Slope of channel - 0,05%
Strickler coefficient of channel 1/3 75
m /s
Initial section m 37,185
Elevation of the bottom of the channel Downstream the overflow discharge m 37,183 37,183
Final section m 37,181
Initial section m 37,322 37,322
Water level inside the channel Downstream the overflow discharge m 37,331 37,331
Final section m 37,329 37,329
2.2 Excess influent flowrate overflow
Overflow heigth m 0,120 0,120
Downstream water level m 0,148 0,148
Downstream specific energy m 0,154 0,154
Critical flowrate 3 223,3 223,3
m /h
Check - Ok Ok
Upstream water level - 0,137 0,137
Flow coefficient - 0,40
Overflow length m 2,64 2,64
2.3 Discharge from distribution channel to anaerobic stage
Width of discharge m 1,00
Water level at the discharge section m 0,047 0,047
Minimum water free fall m 0,200 0,200
2.4 Anaerobic stage
Elevation of the bottom of the tank m 31,080
Water level inside the tank m 37,082 37,082
2.5 Connection from anaerobic to anoxic stage
Design flowrate 3 343,8 309,4
m /h
Width of connection m 1,00
Height of connection m 1,00
Area of connection m2 1,00
Flow coefficient - 0,616
Head losses trough the connection m 0,001 0,001
2.6 Anoxic stage
Elevation of the bottom of the tank m 31,080
Water level inside the tank m 37,081 37,081
2.7 Connection from anoxic to aerobic stage
Design flowrate m3/h 502,2 668,3
Width of connection m 2,00
Height of connection m 1,00
Area of connection m2 2,00
Flow coefficient - 0,616
Head losses trough the connection m 0,001 0,001
2.8 Aerobic stage
Elevation of the bottom of the tank m 31,080
Design water depth m 6,00 6,00
Water level inside the tank m 37,080 37,080
2.9 Discharge from anoxic stage to membrane loading pumping pit
Design flowrate 3 687,5 687,5
m /h
Width of discharge m 2,00
Water level at the discharge section m 0,098 0,098
2.10 Membrane loading pumping pit
Minimum water free fall m 0,200 0,200
Water level inside the tank m 36,782 36,782
2.11 Membrane filtration stage
Elevation of the bottom of the tank m 34,028
Design water depth m 3,20 3,20
Water level inside the tank m 37,228 37,228
2.7 RAS piping
Number of parallel pipes - 3
Design flowrate 3 191,0 191,0
m /h
Design average speed m/s 1,20
Calculated mm 237,2 237,2
Minimum internal diameter
Chosen mm 260,4
Material - SS AISI 304
Pipe Pressure - -
Diameter mm DN 250
Effective average flow m/s 1,00 1,00
Length m 8,00
Major head losses
Roughness coefficient - 140
(Hazen-Williams formula)
Hydraulic slope m/m 0,004 0,004
Inlet - 1
Outlet - 1
Elbow 90 - 3
Elbow 45 - 0
Minor head losses Expansion - 0
Contraction - 0
Tee - 0
Butterfly valve - 0
Gate valve - 0
Total head losses m 0,148 0,148
2.8 Permeate holding tank discharge
Number of parallel pipes - 1
Design flowrate 3 229,2 229,2
m /h
Design average speed m/s 1,20
Calculated mm 259,9 259,9
Minimum internal diameter
Chosen mm 260,4
Material - SS AISI 304
Pipe Pressure - -
Diameter mm DN 250
Effective average flow m/s 1,20 1,20
Length m 75,00
Major head losses
Roughness coefficient - 140
(Hazen-Williams formula)
Hydraulic slope m/m 0,005 0,005
Inlet - 1
Outlet - 1
Elbow 90 - 3
Elbow 45 - 0
Minor head losses Expansion - 0
Contraction - 0
Tee - 0
Butterfly valve - 0
Minor head losses

Gate valve - 0
Total head losses m 0,542 0,542
2.9 Secondary treatments bypass piping
Number of parallel pipes - 1
Design flowrate 3 114,6 114,6
m /h
Design average speed m/s 1,20
Calculated mm 183,8 183,8
Minimum internal diameter
Chosen mm 260,4
Material - SS AISI 304
Pipe Pressure - -
Diameter mm DN 250
Effective average flow m/s 0,60 0,60
Length m 80,00
Major head losses
Roughness coefficient - 140
(Hazen-Williams formula)
Hydraulic slope m/m 0,001 0,001
Inlet - 1
Outlet - 1
Elbow 90 - 3
Elbow 45 - 0
Minor head losses Expansion - 0
Contraction - 0
Tee - 0
Butterfly valve - 0
Gate valve - 0
Total head losses m 0,152 0,152
2.10 Membrane filtration drain piping
Number of parallel pipes - 1
Design flowrate m3/h 104,0
Design average speed m/s 1,20
Calculated mm 175,1
Minimum internal diameter
Chosen mm 159,3
Material - SS AISI 304
Pipe Pressure - -
Diameter mm DN 150
Effective average flow m/s 1,45
Length m 70,00
Major head losses
Roughness coefficient - 140
(Hazen-Williams formula)
Hydraulic slope m/m 0,012
Inlet - 1
Outlet - 1
Elbow 90 - 4
Elbow 45 - 0
Minor head losses Expansion - 0
Contraction - 0
Tee - 0
Butterfly valve - 0
Gate valve - 1
Total head losses m 1,181
Parameter Unit Value
Scenario Summer Winter
3.1 Membrane soaking drain piping
Number of parallel pipes - 1
Design flowrate 3 41,6
m /h
Design average speed m/s 1,20
Calculated mm 110,7
Minimum internal diameter
Chosen mm 107,1
Material - SS AISI 304
Pipe Pressure - -
Diameter mm DN 100
Effective average flow m/s 1,28
Length m 70,00
Major head losses
Roughness coefficient - 140
(Hazen-Williams formula)
Hydraulic slope m/m 0,016
Inlet - 1
Outlet - 1
Elbow 90 - 3
Elbow 45 - 0
Minor head losses Expansion - 0
Contraction - 0
Tee - 0
Butterfly valve - 0
Gate valve - 0
Total head losses m 1,309
3.2 Sludge dewatering drain piping
Number of parallel pipes - 1
Design flowrate m3/h 21,5
Design average speed m/s 1,20
Calculated mm 79,6
Minimum internal diameter
Chosen mm 107,1
Material - SS AISI 304
Pipe Pressure - -
Diameter mm DN 100
Effective average flow m/s 0,66
Length m 15,00
Major head losses
Roughness coefficient - 140
(Hazen-Williams formula)
Hydraulic slope m/m 0,005
Inlet - 1
Outlet - 1
Elbow 90 - 2
Elbow 45 - 0
Minor head losses Expansion - 0
Contraction - 0
Tee - 0
Butterfly valve - 0
Gate valve - 0
Total head losses m 0,117

You might also like