Model H
Typical applications
l Lubricating oil temperature control
l Jacket water high temperature (HT)
l Secondary water low temperature (LT)
l Heat recovery
l Water saving applications
l Boiler inlet temperature control
l Co-generation, cooling towers
l Temperature mixing or diverting
l Engine and compressor cooling system
H Valve
Accreditations available
l PED* Suitable for Group 1 & 2 liquids
(Ensure materials are compatible)
l ATEX* 11 2 G X
l * Complies with all relevant EU directives
* Contact AMOT
Datasheet_H_Thermostatic_Control_Valve_0812_Rev4 www.amot.com
Thermostatic Control Valves - Model H
Contents
Overview ............................................................... 3
Applications ........................................................... 4
Specification .......................................................... 9
Dimensions ........................................................... 10
Weights ................................................................ 10
Datasheet_H_Thermostatic_Control_Valve_0812_Rev4 page 2
Thermostatic Control Valves - Model H
Overview
AMOT model H thermostatic valves are available very economical temperature limiting valves to
in a wide selection of sizes and settings to prevent scalding in home, motel or hotel hot
fill a multitude of fluid temperature control water supply systems. Radiant heating systems
requirements. These valves may be mounted can use these valves in limiting water temperature
in any position and use the proven expanding to prevent surface cracking and over-heating of
wax principle to actuate the 3-way temperature plastic piping. Other applications include electronic
element assemblies. The model H valves may be and battery cooling circuits, pump temperature
used for diverting or mixing service. They make relief valves etc.
Element materials
l Bronze, brass and stainless steel
l Nickel plated/Stainless steel
Leakholes
In some applications, it is necessary to have leak Selection Guide (Datasheet_Temp_Control_Valve_
holes drilled in the element to ensure a small flow Guide) to determine the hole size required for
between ports A and C. Leak holes are available in specific applications.
sizes ranging from 6.3mm to 19mm (1/4 to 3/4).
Please refer to the Temperature Control Valve
Temperature settings
A wide selection of element materials, seals, and For mixing and oil circuits the temperature may be
temperatures are available. Follow the equipment one to two degrees higher due to flow, viscosity
manufacturers guidelines for heating/cooling and other system parameters.
systems.
Elements and seals are available in a variety of
Temperature settings are available from 13C to materials. These materials are suitable for most
116C (55F to 240F). Refer to the Temperature applications. Please refer to the Temperature
& Element Characteristics table on page 6 for Control Valve Selection Guide (Datasheet_Temp_
specific temperature settings. In general the Control_Valve_Guide) for material compability
temperature quoted is the nominal operating information.
temperature in diverting mode on water systems.
Datasheet_H_Thermostatic_Control_Valve_0512_Rev3 page 3
Thermostatic Control Valves - Model H
Applications
Diverting Applications
Pump
Mixing Applications
Pump
Pump
B
Port
A
blocked
C
Datasheet_H_Thermostatic_Control_Valve_0812_Rev4 page 4
Thermostatic Control Valves - Model H
Valve characteristics
H Valve Flow Chart
Pressure drop - Metric Units AMOT thermostatic valves are designed to
produce minimal pressure drop. The normal
ISO VG100 ISO VG46 Water
recommendation in sizing the valves is to
select a pressure drop between 0.14 to
0.65 0.5 Bar (2 and 7 PSI).
0.60
0.55
0.50
Pressurre Drop (Bar)
0.45
0.40
0.35
0.30
0.25
0.20
0.15
0.10
0.05
-
-
Valve 25 50 75 100 125 150 175 200
4 H 25 50 75 Flow 100
(m3/hr) 125 150 175 200
5 H 43 85 128 171 214 256 299 342
6 H 46 93 139 185 231 278 324 370
10
8
Pressurre Drop (PSI)
-
Valve
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800
4 H 150 200 250 300 Flow400
350 (GPM)450 500 550 600 650 700 750 800
5 H 256 342 427 512 598 683 769 854 939 1025 1110 1196 1281 1366
6 H 277 370 462 554 647 739 832 924 1016 1109 1201 1294 1386 1478
Datasheet_H_Thermostatic_Control_Valve_0512_Rev3 page 5
Thermostatic Control Valves - Model H
Valve characteristics
Flow coefficient Kv is the flow coefficient in metric units. It is defined as the flow rate in
cubic meters per hour (m/h) of water at a temperature of 16 Celsius
Flow coefficients with a pressure drop across the valve of 1 bar. The basic formula to find
(calculated)
a valves Kv is shown below:
Size Kv Cv 2 Q = Flow in m3/hr
4H 200 232 Q DP
DP = SG Q = Kv DP = Pressure drop (Bar)
5H 400 464 Kv SG SG = Specific gravity of fluid (Water = 1.0)
6H 400 464 Kv = Valve flow coefficient
Datasheet_H_Thermostatic_Control_Valve_0812_Rev4 page 6
Thermostatic Control Valves - Model H
How to order
Use the tables below to select the unique specification of your H Valve.
Datasheet_H_Thermostatic_Control_Valve_0512_Rev3 page 7
Thermostatic Control Valves - Model H
Recommended spares
Model HO Model HM
Ref Part no. Qty Description When properly applied and installed, AMOT
no. thermostatic valves should operate for years with
minimal maintenance. An inspection at two or
2 9760X 1 or 2 Element assembly
three year intervals is adequate to detect and
(temp)
make provision for normal wear. The frequency of
2 9760P 1 or 2 Element assembly, element replacement will depend on the operating
(temp) plated conditions and the type of fluid being controlled.
2 9844 1 or 2 Element assembly, Because of the diaphragm and plug construction
(temp) manual override of the wax actuated element, calibration will be
3 11009L001 1 or 2 O-ring, element, Buna N maintained over thousands of cycles.
(Std) Whenever elements are replaced, the O-ring
seals should also be replaced. For convenience,
3 11009L002 1 or 2 O-ring, element Viton
elements and O-ring seals may be ordered
8 11007L001 1 or 2 O-ring, housing, Buna N together in the service kits listed below. The parts
8 11007L002 1 or 2 O-ring, housing, Viton may also be ordered individually by their part
13 11148 1 or 2 O-ring, stem seal, number.
Buna N
13 11148L001 1 or 2 O-ring, stem seal,
Viton
Datasheet_H_Thermostatic_Control_Valve_0812_Rev4 page 8
Thermostatic Control Valves - Model H
Specification
Flow rate 56 to 280m3/hr (245 to 1232 US gpm)
Recommended pressure 0.14 to 0.5 bar (2 to 7 PSI)
drop
Body materials Steel (BS: 3100 A1, WCB) For high strength/pressure ratings
Stainless steel
Seal materials Nitrile
Viton
Mounting position Any orientation
Ports Below nominal temperature Ports A and B connected
Above nominal temperature Ports A and C connected
Port connections ANSI flanges
Maximum working
pressures ANSI 150 lb 16 bar (230 psi)
ANSI 300 lb 45 bar (655 psi) 4 valve only
Valve size 100mm, 125mm and 150mm (4, 5 and 6)
(nominal bore)
Control temperatures 13C to 116C 55F to 240F
See element characteristics table
Accreditations* PED Suitable for Group 1 & 2 liquids.
(Ensure materials are compatible.)
ATEX 11 2 G X
Complies with all relevant EU
directives
* Contact AMOT
Datasheet_H_Thermostatic_Control_Valve_0512_Rev3 page 9
Thermostatic Control Valves - Model H
Valve dimensions
Model HO and HM
A = Inlet port
B = Bypass port
C = Cooler port
Datasheet_H_Thermostatic_Control_Valve_0812_Rev4 page 10
Americas Europe, Middle East and Africa
AMOT Shanghai
Rm 4102 - 4104 United Plaza AMOT Russia
1468 Nanjing Road West #34 Shabolovka Street
Shanghai 200040 Building 2
China Moscow 115419
Russia
Tel +86 (0) 21 6279 7700
Fax +86 (0) 21 5237 8560 Tel +7 495 617 12 93
Email shanghai@amot.com Fax +7 495 913 97 65
Email russia@amot.com
AMOT Singapore
10 Eunos Road 8 #12-06
Singapore Post Centre
Singapore 408600
Tel +65 6408 6265
Fax +65 6293 3307
Email singapore@amot.com
www.amot.com