Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Units

vii) Maximum steam side temperature 100C


imbalance in the LHS & RHS at boiler
outlet (from the average)
viii) Minimum load with separator running dry 30-40 % TMCR (As per
manufacturers proven
practice)
ix) Header pressure unbalance (steam side) 6%
x) Air ingress from furnace bottom Hopper As per manufacturer's
predictions

6.4.13 Safety and relief valves

Boiler Safety valves and relief valves shall have minimum discharge
capacities as under:
Valve Minimum discharging capacities
i) Spring loaded safety valves at:
a) Separator & superheater Combined capacity 100% BMCR
b) Reheater system Combined capacity 105% of
reheater flow at BMCR
ii) Electromatic relief valves at:
a) Superheater outlet 10% BMCR
b) Reheater outlet 15% BMCR

6.4.14 Steam purity parameters


Steam purity parameters at outlet of the steam generator shall meet
requirement of turbine manufacturer and shall generally not be inferior to
those indicated below:
i) Sodium : < 3 ppb
ii) Chloride : < 3 ppb
iii) Iron : < 10 ppb
iv) Silica : < 10 ppb
v) Cation conductivity : < 0.2 S/cm

6.5 Specifications of Equipment and Systems


The specified requirements shall be complied for the most stringent conditions
resulting either from the range of coals (design/ worst/ best) or from the range
of operating conditions specified (like 100% BMCR or HP Heaters out of
operation etc.), or from both occurring simultaneously, unless specifically
mentioned otherwise.

6.5.1 Steam generator enclosure


i) Steam Generator enclosure shall form air/gas tight envelope from
secondary air and primary air inlet points to chimney inlet.

29