Professional Documents
Culture Documents
4 Essential Features of Transformer On-Load Tap Changer OLTC
4 Essential Features of Transformer On-Load Tap Changer OLTC
4 Essential Features of Transformer On-Load Tap Changer OLTC
(OLTC)
electrical-engineering-portal.com /4-essential-features-of-transformer-on-load-tap-changer-oltc
Google+ 2015-1-28
1. Because the currents are lower, the tap changer contacts, leads, etc., can be smaller.
2. As the HV winding is wound outside the LV winding, it is easier to get the tapping connections out to the tap
changer.
Figure 1 below shows the connections for an on-load tap changer that operates on the HV winding of the
transformer.
1. Selector Switches
1/5
These switches select the physical tap position on the transformer winding and, because of their construction,
cannot and must not make or break the load current.
2. Reactors
Therefore, during
each tap change,
there is an interval
where two voltage
taps are spanned.
Reactors
(inductors) are
used in the circuit
to increase the
impedance of the
selector circuit and
limit the amount of
current circulating
due to this voltage
difference. Under
normal load
conditions, equal
load current flows
in both halves of
the reactor
windings and the
fluxes balance out
Figure 1 On-Load Tap Changer
giving no resultant
flux in the core.
With no flux, there is no inductance and, therefore, no voltagedrop due to inductance. There will be however, a
very small voltage drop due to resistance.
During the tap change, the selector switches are selected to different taps (see Figure 2) and a circulating current
will flow in the reactor circuit. This circulating current will create a flux and the resulting inductive reactance will limit
the flow of circulating current.
3. Vacuum Switch
This device performs the duty of a circuit breaker that makes and breaks current during the tap
changing sequence.
2/5
4. Bypass Switch
This switch operates during the tap changing sequence but, at no time, does it make or break load current ,
though it does make before break each connection.
An example of the tap changing sequence is detailed in Figure 2 (diagrams 1 through 10). Table 1 describes the
sequence of operations for the tap changer of Figure 2 to change from tap 1 to tap 2. Changing to any other tap
position is done similarly with the selector switch always moving sequentially (i.e., it is impossible to go from tap 1 to
tap 3 directly, the order must be tap 1, tap 2, then tap 3).
The operating mechanism for the on-load tap changer is motor driven. Manual operation is used in the event of
motor failure.
The sequence of operation is mechanically linked, orinterlocked, to ensure that all contacts always operate in their
correct order. Any failure of the operating mechanism can result in severe damage to the transformers and tap
changers.
1 Present position tap changer selected to tap 1, bypass switch in, A + B, home position.
3 Vacuum switch opens, removing load current from upper circuit arm freeing one half of selector switch for
move.
5 Vacuum switch closes both selector switches onload, circulating current is limited by reactors.
6 Bypass switch selects upper arm circuit arm. No arcing occurs as vacuum switch is closed and in parallel.
7 Vacuum switch opens, removing load current from lower circuit arm, freeing lower selector switch for move.
10 With vacuum switch closed and selector switch on a single tap, the bypass switch can now return to its
home position. Both reactor circuits stay normally in parallel. The tap change is now complete.
The previous example describes one type of on-load tap changer. There are several other types inuse however,
which may differ significantly from the type described.
Differences are usually in how the selection of taps is made and the degree of mechanization. However, most
importantly, all on-load tap changers allow voltage changes to take place without interrupting the power
circuit.
Reference: Science and Reactor Fundamentals Electrical CNSC Technical Training Group