d) Supporting arrangement
All horizontal heat transfer surfaces shall be supported by steam or
water cooled hanger tubes designed for a minimum of 2 times the
calculated load so as not to cause any dislocation/ damage to the tube
banks/sections. The stress in the hanger tubes under such condition
also shall not exceed the maximum permissible limits as per IBR.
Erosion allowance of one (1) mm shall be provided over and above
the calculated thickness of hanger tubes.
e) Arrangement of headers
Headers shall be located out side the gas path and shall be fully
drainable. Wherever, locating the headers in the gas path becomes
unavoidable these shall be suitably protected with erosion shields/
protectors. Further, the nipples and studs of the header shall also be
provided with wear resistance stainless steel shields of minimum 2.5
mm or higher thickness. The arrangement of headers shall be such
that it does not cause the high localised flue gas velocity on tubes
down stream side of the header.
f) Attemperators
39