Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Units

b) Access openings alongwith air/ gas tight hinged doors shall be


provided for approach to above maintenance spaces without any
hindrance from hanger tubes.
1. All access door shall be of 450mm x 450mm size (minimum).
2. Access doors 800 mm above the nominal floor level shall have
access platform.
3. Hanger tubes of horizontal banks shall have access opening for
crossing over.

c) Stainless steel erosion shields shall be provided for all bends of


outermost tube/ coil of all SH/ RH sections and hanger tubes in
areas where flue gas temperature is below FEGT. For the pendant
tube sections, the erosion shield shall be provided on the leading
tubes and wherever else considered necessary as per the proven
design.

d) Suitable arrangement for internal inspection of attemperators/


headers shall be provided.

vi) Headers and pipes, if made using X-20 Cr MO V 121 to DIN 17175
material, shall have provisions to ensure that no site welding of this
material with similar or dissimilar material is needed.

6.5.7 Economisers

i) Economizer design shall conform to the following criteria/requirements


under all condition of operation and for the complete range of specified
fuels.

a) Economizer type Non-steaming type with parallel cross


flow or counter flow arrangement.
b) Approach temperature 17C (minimum).
within control range
c) Maximum average flue 10 m/sec (maximum localized velocity
gas velocity through the across the cross-section not to exceed 12
economizer tube banks, m/sec).
with 25% excess air at
economizer outlet. For high GCV low ash (say 10% and
below) coals:
12 m/sec (maximum localized velocity
across the cross-section not to exceed 14
m/sec).
d) Economizer tube i) Erosion allowance of 1mm (minimum)
thickness shall be provided in addition to
thickness calculated as per IBR
formulae.