Professional Documents
Culture Documents
R0 - Internal Electrical-Boq With Cost
R0 - Internal Electrical-Boq With Cost
R0 - Internal Electrical-Boq With Cost
SECTION A :
3.0 Ladder Type and Perforated Cable tray 1,639,600 281,100 1,920,700
SECTIONB:
4.0 Power circuit wiring for Small Power 514,000 118,450 632,450
SECTION C :
SECTION D :
SECTION A: LT PANELS
1
Supply, receiving, unloading, shifting to indoor Electrical rooms, inspection,
handling, assembly, installing in correct aligned position, making proper
connections, testing and commissioning of the following LT Panels including
alignment leveling, grouting with anchor fasteners, GI nuts and bolts and
making of all incoming and outgoing feeders with approved aluminum
engraved name plates complete as required by Project Managers/Consultant.
All materials and workmanship shall conform to latest Indian standards /
Consultants technical specifications /tender drawings and shall comply with
statutory requirements.
1.1 LT SWITCH BOARDS (As per enclosed technical specifications Ref No.-
100 & SLD Ref No.- WW - ELEC-100)
3 phase, 4wire, floor mounting free standing / Wall mounted, cubicle type, LT
switchboards.
a. 16A TP + NL,10kA, C Curve MCB in IP-52 Powder coated MS enclosure. Nos. 8 1350 146 10800 1168 11968
b. 25A TP + NL, 10kA, C Curve MCB in IP-52 Powder coated MS enclosure. Nos. 6 1569 146 9414 876 10290
c. 20A TP + NL, 10kA, C Curve MCB in IP-52 Powder coated MS enclosure. Nos. 1 1450 146 1450 146 1596
d. 32A TP + NL, 10kA, C Curve MCB in IP-52 Powder coated MS enclosure. Nos. 2 1569 146
e. 40A TP + NL, 10kA, C Curve MCB in IP-52 Powder coated MS enclosure. Nos. 11 1800 160 19800 1760 21560
f. 63A TP + NL, 10kA, D Curve MCB in IP-52 Powder coated MS enclosure. Nos. 6 2880 219 17280 1314 18594
g. 125A, 415V, 3P+2NL, TM based, adjustable O/L and Fixed SC, 25kA MCCB
Nos. R0 12000 219
in IP-52 Powder coated MS enclosure.
h. 63A TP + 2NL, TM based, adjustable O/L and Fixed SC, 16kA, MCCB in IP-
Nos. R0 3000 219
52 Powder coated MS enclosure.
I 400A isolator in IP-52 Powder coated MS enclosure with indication( UPS input
Nos. 1 24000 219 24000 219 24219
side).
a. 3.5C x 185 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Mtrs. 80 850 85 68000 6800 74800
Cable. (A2XFY)
b. 3.5C x 150 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Mtrs. R0 725 75
Cable. (A2XFY)
c. 3.5C x 120 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Mtrs. R0 600 60
Cable. (A2XFY)
d.
3.5C x 95 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Mtrs. 80 460 60 36800 4800 41600
Cable. (A2XFY)
e.
3.5C x 70 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Mtrs. 420 460 60 193200 25200 218400
Cable. (A2XFY)
2.1.3
4C, 3C & 1C XLPE insulated, Cu conductor, PVC Outer sheathing Cables
b. 3.5C x 185 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Set 4 2200 300 8800 1200 10000
Cable. (A2XFY)
c. 3.5C x 150 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Set R0 1750 250
Cable. (A2XFY)
d. 3.5C x 120 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Set R0 1200 225
Cable. (A2XFY)
e 3.5C x 95 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Set 4 850 210 3400 840 4240
Cable. (A2XFY)
f 3.5C x 70 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Set 10 700 200 7000 2000 9000
Cable. (A2XFY)
2.2.3
4C, 3C & 1C XLPE insulated, Cu conductor, PVC Outer sheathing Cables
d. 4C x 4 Sq.mm Cu.conductor, PVC insulated, armoured & PVC Set 20 120 30 2400 600 3000
sheathed cable (YRY).
e. 3C x 4 Sq.mm Cu.conductor, PVC insulated, armoured & PVC Set 115 30
sheathed cable (YRY).
f.
1C x 50 Sq.mm PVC insulated Flexible Copper Cable (YY). Set 30 740 70 22200 2100 24300
Supply and installation of Race ways of following sizes made of 1.6 mm thick
pre galvanized sheet steel (Perforated wherever specified) with 1.2 mm thick
screwed / Push to fit type cover. The race ways shall be similar to Profab
make UT range & shall be suitable for installation in floor screed / above false
ceiling / open ceiling areas. The joining accessories shall be of same material
supplied along with race ways. Approval shall be obtained from consultants on
product sample before procurement.
5.3 CONDUITS .
a. 32Mmm dia conduit ( Ceiling ) Mtrs 1660 40 25 40 41500 41540
b. 32Mmm dia conduit ( Floor ) Mtrs 590 30 20 30 11800 11830
1 DISTRIBUTION BOARDS
Surface mounting double door type MCB DBs conforming to the specification
and fabricated out of CRCA sheet with powder coated to RAL 7032 lockable
hinged glazed front door, cable gland plate, conduit knockouts. The DBs shall
comprise of 63A Neutral terminal block for incomer, insulated fork type phase
bus bars, independent neutral terminal bar for each phase where required,
common insulated earth terminal bar and complete with interconnecting wiring.
The IP class shall be 31 or better. The rate shall include costs of MCB /
RCCB / RCBO.
3 Nos. of din rail mounting type SPD, 1.5kV, 15kA, DP Surge protection device
for each phase incomer.
1.2
Raw Power Distribution Board: (As per enclosed technical specification)
4 Tier/Row 40 Module MCB DB as above Nos. 5 13000 1100 65000 5500 70500
Frame with wire ways shall be made out of 16SWG CRCA sheet steel and
powder coating colour shall match the colour of MCB DB's. 200mm x 200mm
wire ways / Raceway with 2mm thick screwed / press to fit cover for making
Frame for MCB DB's. Complete required including installation accessories.
b. Floor POPUP box for fixing the power and data points ( 2nos 6/16A UPS
socket controlled by individual 16A switches and 1no. Data outlet ). Legrand Nos. 36 8000 250 288000 9000 297000
Make.
Supply, installation, testing and commissioning Power wiring from Raw power
& UPS power DBs to power sockets with 660V FRLS insulated multi strand
copper wires in conduits / Raceways including termination in sockets/ MCBs.
iv) Insulation sleeves for flexible wires as required in the workstation partitions.
6.1 GI Conduits:
a. 25mm dia GI conduit Mtrs. R0
6.2 MS Conduit:
a. 25mm dia MS conduit Mtrs. R0
a 1 tier / row 14 module MCB DB with 1 pole 14 module insulated fork bus bar,
Neutral, earth terminal block with supports (1-Phase SP outgoing Circuits).For Nos. 5 5500 500 27500 2500 30000
Emergency Lighting.
b 2 tier / row 28 module MCB DB with 1 pole 28 module insulated fork bus bar,
Neutral, earth terminal block with supports (1-Phase DP outgoing Circuits) for Nos. R0 7000 600
Main Emergency lighting DB.
a 3 Run of 1.5 Sq.mm copper FRLS wires in already laid conduits with ferrules
and pin type lugs for both the ends. Mtrs. R0
b 2 Run of 2.5 Sq.mm+ 1Run of 1.5sq.mm copper FRLS wires in already laid
Mtrs. 26250 70 10 1837500 262500 2100000
conduits with ferrules and pin type lugs for both the ends.
5 POINT WIRING
Supply and installation of Point Wiring for light points with 660V grade multi
strand flexible copper wires 3 run 2.5 sq. mm, 25mm dia 2mm thick FRLS
PVC conduits, PVC reinforced flexible conduits with end couplers and conduit
accessories and decorative modular type switches in zinc passivated switch
box, switches and front cover etc., complete in all respect.
k. One exhaust fan point controlled by one 6A switch and one socket near the
Set R0
exhaust fan.
l. One Wall mounted fan point controlled by one 6A switch and one socket near
Set R0
the exhaust fan.
6.2 MS Conduit:
a. 25mm dia MS conduit Mtrs. 100 70 15 7000 1500 8500
a
3-Phase input & 3 Phase output 10kVA Line interactive type inverter with 90
Minutes Battery Backup and Protections for Incoming and outgoing Circuits.
The batteries shall be placed in cabinet. The batteries shall be
VRLA+AGM+GEL type SMF batteries. Technical specifications approval shall
be obtained from Consultants along with offer submittals. The battery shall be
provided in 2mm thick MS powder coated rack. The inverter /batteries shall Nos. 1 300000 1000 300000 1000 301000
comply to relevant standards/codes. The inverter design Output PF shall not
be less than 0.95PF. Inverter efficiency shall be 93% or more. The complete
equipment shall be supplied as per enclosed SLD. Make of batteries shall be
Global Yuhasa (Rocket)/ Panasonic / Exide. Minimum 2 years warranty from
date of commissioning of batteries & Inverters
2 GI EARTHING CONDUCTOR
Supply, laying and termination of the following sizes of earth flats and wires
laid underground at 600mm deep / on Cable trays/ drawn through pipe sleeves
along with column/ walls for safety earthing As per enclosed technical
specifications. All joints in the runs of the conductor shall be welded. All weld
joints shall be protected with bitumin paint. The equipment tape connections
shall be bolted using galvanized hardware.
j.
25x6mm GI 300mm Long Bus bar with FRP Supporting insulator with suitable
Nos. 1 900 150 900 150 1050
size of Brass coated Bolts and Nuts and suitable size of Grip Bolts
a 40 x 6mm electrolytic grade copper strip in PVC sleeves. Mtrs. 1600 150
b. 25 x 6mm electrolytic grade copper strip in PVC sleeves. Mtrs. 800 100
c. 25 x 3mm electrolytic grade copper strip in PVC sleeves. - Up to shaft. Mtrs. 400 650 100 260000 40000 300000
d. 7 / 16 SWG GI Wire including terminations Mtrs. 12 5
e
40x6mm GI. 600mm Long Bus bar with FRP Supporting insulator with
Nos. R0 950 150
suitable size of Brass coated Bolts and Nuts and suitable size of Grip Bolts
f
25x6mm Copper 300mm Long Bus bar with FRP Supporting insulator with
Nos. 2 650 150 1300 300 1600
suitable size of Brass coated Bolts and Nuts and suitable size of Grip Bolts
2 MISCELLANEOUS ITEMS
2.1 MS Fabrication work carried out of M.S angle, plates and flats for fixing
of cable tray/pipe sleeves, DBs, etc., duly painted complete with
necessary hardware.
a 12mm dia Anchor fasteners Nos. 20 5
b 10mm dia Anchor fasteners Nos. 147 15 5 2200 733 2933
c 8mm dia Anchor fasteners Nos. 1400 12 5 16800 7000 23800
d Galvanized M8 rod Hi-tech supports Mtrs. 1120 30 8 33600 8960 42560
e Galvanized M10 rod Hi-tech supports Mtrs. 117 50 8 5867 939 6805
f Galvanized M12 rod Hi-tech supports Mtrs. 70 8
g ISMC channels / angles supporting structure for raceways, cable trays &
suspended lighting etc.The cost shall be including cutting, welding, painting Kgs R0 180 25
and necessary items to complete the work. .
h 5mm Thick, 25mm W G.I slotted channel supports for ceiling raceways. The
cost including making of 'L' or 'C' type supports for ceiling suspended trays
Mtrs. 200 80 30 16000 6000 22000
installations .The cost shall be including cutting, welding, painting, installation
and necessary items to complete the work.
i 2mm Thick, 40mm W G.I slotted channel for ceiling raceways. The cost
including making of 'L' or 'C' type supports for raceway installation .The cost
Mtrs. 200 65 45 13000 9000 22000
shall be including cutting, welding, painting installation, and necessary items to
complete the work.
e
10mm thick, SYNTEX make Hot pressed SMC moulded Chequered Plates.
Sq. M R0
Plate to be cut to size as required and installed after removing all sharp edges.
g
Fire barriers at wall / Floor crossing with Intuemescent sealant for sealing
small & medium size penetrations with 2 hour fire rated sealant as per the site
condition - Only HILTI / 3M make intuemescent sealant shall be used. Sq. M 4 65000 1500 260000 6000 266000
The same shall be installed by authorized agency & the installation shall have
the manufacturers Certificate.
GENERAL CONDITIONS
Clients reserves to supply any listed items, the contractor shall install the
A
same at quoted installation price.
Clients reserves to change specification and makes of materials prior to
B
procurement by contractor.
All the execution shop drawings shall be prepared by vendor and approval
C shall be taken from Consultants/Architects/Clients before execution.
The quantities indicated cover the probable quantities of work involved. The quantities are indicated for the guidance of the bidder.
The order arising out of this enquiry will be an unit rate contract & not a lump sum one. The Owner, however, does not in any way
B guarantee that the actual work involved would correspond to the quantities indicated in the tender.
C No change in unit rate will be allowed for any change in quantity, or for any other reason whatsoever.
D The rates quoted for the "Supply" items shall be include all taxes, packing, forwarding, freight, insurance & unloading charges.
The installation charges shall be inclusive of the cost of shifting materials to the installation spot, unpacking, installation on
E foundations as specified elsewhere, supply of hardware, consumables and any minor civil works involved.
The installation rate of all LT switchboards shall include the cost of fixing bolts & nuts, painting of cable sizes, fixing of nameplates,
F danger boards, testing & commissioning.
The rate for installation of earthing grid conductors shall include the cost of welding/ riveting & brazing of the joints, protecting the
G same against corrosion at joints, drilling holes for equipment terminations, cost of lugs for earthing wires and supply of hardware.
H All testing charges for the Equipment shall be included n the installation rate of the respective equipment.
The installation rate for cables shall include shifting of cable drums, unwinding & laying as per engineering standards all labor
supervision, routine testing, supply of consumables and installation materials such as identification tags, clamps etc. However,
the cost shall exclude steel supports, installation of trays and cable termination as also the excavation, backfilling, supply of
I protective covers, sand, bricks etc. which be quoted separately under the appropriate item.
The cost of excavation, supply of sand, bricks, back filling and supply of cable markers etc shall not be included in the cost of cable laying and
J same shall be covered under appropriate headings in the BOQ
The supply rate quoted for cable termination shall include heavy duty single compression brass cable gland, crimping type heavy
duty tinned copper lugs & earth tag for gland earthing. The installation rate shall include all consumables and Labor for preparation
K of cable, glanding & crimping.
The supply price of power wiring shall include the cost of FRLS grade wires, crimping type lugs for termination, Conduit, all conduit
L accessories such as bends, junction boxes, draw boxes etc., as per the specification.
The installation rates for concealed conduits shall include the cost of chasing the walls to appropriate depth to provide 20mm cover.
Installing the conduits with clamps in the wall recess and rough plastering the surface using cement mortar of specified mix to bring
M the wall surface to the original level. The final finishing shell however be carried out by other agencies.
The installation price of wiring shall include the cost of all necessary consumable required for fixing drawing, the wires and
N terminating the same with ferrules, sleeves etc.
The installation rate of cable trays shall exclude tray supports but shall include necessary clamp/ hardware required for fixing it
O on tray supports.
The installation rate for recess mounted luminaire shall include all the above and the cost of the GI suspension chain and alignment
P of luminaries.
The cost of steel frame work & supporting structure, required for the Switchboards / bus duct/ cable tray etc., shall be quoted under
Q the heatd Supply and Installation' of supporting steel.
The point wiring rate for luminaires shall include supply of all materials starting from passivated metal switchbox, junction boxes,
switch plate, switches, conduits & accessories, wires, tags, earthing the switchbox, earthing of luminaires etc. and no extra claim will
be allowed under any circumstances. The cost of suspension conduits, flexible PVC conduits, wires as required shall be included.
The point wiring rates of *ceiling fans shall include the supply of fan hook boxes in the case of recessed wiring and hooks in the case
R of surface wiring.
Page 10
preamble
The installation price of industrial power socket outlets shall include all necessary hardware & consumables required for mounting
S it on the surface of the wall/ column or concealing the same in walls.
Installation rate for pipe sleeves/ conduits shall cover necessary chasing in the floor/ walls etc., excavation if any and backfilling
T and rough plastering if required.
U The installation cost of surface mounted luminaires shall include the following
I Assembling the luminaire and checking the same.
ii Supply & installation of anchor fastners as required for the supports.
iii Installation of luminaire using appropriate hardware.
iv Wiring connection and installation of lamps.
V Testing & commissioning.
Any item not specifically mentioned in this specification & BOQ but considered essential for satisfactory operation of the system
shall be included by the tenderer in his offer. NO EXTRA AMOUNT WHATSOEVER WILL BE PAID FOR ANY CONTINGENT
V SUPPLY OR INSTALLATION WORK.
Page 11