Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

GENERAL INFORMATION

Project Identification: For Lease


Average maintained illuminance for design: 750 lux

Luminaire Data: Lamp data:


Manufacturer: Cree Type and colour: LED 4000K
Catalogue Number: Led Count: 12
HBY-EHO-DM-24-E-UL-WH-1000-40K Total lumens: 36,628

SELECTION OF COEFFEICIENT OF UTILIZATION

Step 1: Fill in sketch L


= 0.25 hCC = 1m

Step 2: Determine Cavity Ratios = 0.25


L=
hRC = 4.2m
= 0.70
Room Cavity Ratio, RCR = 1.86
W=
Ceiling Cavity Ratio, CCR = 0.44 Work-plane
= 0.13 = 0.69 hFC = 0.8m
Floor Cavity Ratio, FCR = 0.54

Step 3: Obtain Effective Ceiling Cavity Reflectance CC = 0.25


Step 4: Obtain Effective Floor Cavity Reflectance FC = 0.69
Step 5: Obtain Coefficient of Utilization from Manufacturers Data CU =
104.12

Selection of Light Loss Factor


Room surface dirt depreciation = 0.98 Lamp burnouts factor = 1
Lamp lumen depreciation = 1 Luminaire dirt depreciation = 0.97
Total LLF = 0.951

(Illuminance )( Area )
No. luminares=
( Lumens)(CU )( LLF)

(750)(618.82)
No. luminares= =13luminaires
(36,628)(1.04)(0.951)

(Lumens)(No . luminares)(CU )(LLF )


Illuminance=
( Area)

(36, 628)(13)(1.04)(0.951)
Illuminance= =761.04 lux
(618.82)