Series 44 Intrinsically Safe

Stainless Steel Media Isolated Pressure Sensor


Series
44
4
Features
Class 1 Div 1, Groups C&D Intrinsically Safe.
High Strength Stainless Steel Construction.
No silicone oil, no internal o-rings, no welds.
Wide operating temperature range.
Ranges up to 10,000 PSI.
Rugged design survives harsh environments.
Compatible with wide range of gases and liquids.
Suitable for high shock and vibration applications.

Specifications
Performance @ 25C (77F)
Accuracy1 <0.25% BFSL
Stability (1 year) 0.25%FS, typ Electrical Data
Proof Pressure 2X Rated Pressure Excitation 5VDC 10-28 VDC
Output 0.5-4.5V Ratiometric 1-5 V & 4-20mA
Burst Pressure 5X or 20,000 PSI,
whichever is less Input Impedance N/A N/A

Wetted Material 17-4PH S.S. (NACE compatible) Output Impedance 100 Ohms nom. 100 Ohms, nom. -
(for other material consult factory) Current Consumption <10mA <10mA & 25mA max
Pressure Cycles > 100 Million Bandwith (-3dB) DC to 1kHz DC to 1kHz & 250Hz
1 Output Noise <2mV RMS <2mV RMS
Accuracy includes: Non-linearity, Hysteresis and Non-repeatability
Reverse polarity YES YES

Physical Description Zero Offset <1% of FS <1% &1.5% of FS


Span Tolerance <2% of FS <2% of FS
Case 304 Stainless Steel
Output Load 10k Ohms, min. 10k Ohms, min.
Pressure Fittings 1/8" MNPT, 1/4" MNPT
(for others consult factory) Agency Approvals UL/CUL 1604 for all models
Electrical Connection 2 feet cable std.
(for other lengths consult factory) Pressure Ranges*+
Gage Proof Burst Pressure
Environmental Data psig psig psig Range Code
Temperature 0-25 50 250 00025
Operating -40 to 85C (-40 to 185 F) 0-50 100 250 00050
0-100 200 500 00100
Storage -55 to 125C (-65 to 250 F)
0-200 400 1,000 00200
Thermal Limits
0-500 1,000 2,500 00500
Compensated Range 0 to 55C (30 to 130 F)
0-1,000 2,000 5,000 01000
TC Zero <1.5% of FS (2.0% for 316 L)
0-2,500 5,000 12,500 02500
TC Span <1.5% of FS (2.0% for 316 L)
0-5,000 10,000 20,000 05000
Other 0-7,500 15,000 20,000 07500
Shock 100G, 11msec, 1/2 sine 0-10,000 20,000 20,000 10000
Vibration 20G Peak, 20 to 2000 HZ * Typical Ranges. All ranges between 0-25psi and 0-10,000psi
Rating: IP-66 are available. Please consult factory.
+ Vacuum calibration available. Please consult factory.

EMI/RFI Protection Yes Specifications are subject to change without notice.


7
Series
44
4
Ordering Information
Construct a product code using the chart below. (Consult factory for other options)

44-A-00500-B-3-L-0-000

Series Process Pressure Pressure Outputs Electrical Wetted Options


Type Connection Range Unit Interface Material

44 X= Special XXXXX= X= Special X= Special X= Special X= Special XXX= Special


Intrinsically A= 1/4 MNPT Special B= BAR 1= 10mV/V A= 2Ft. Cable 0= 17-4 PH 000= No Options
Safe B= 1/8 MNPT K= kg/cm2 2= 0.5-4.5V B= 4Ft. Cable 1= 316 L A10= 0.10 Accuracy
F= 7/16-20 UNF Insert P= PSI ratiometric C= 6Ft. Cable 2= Inconel A25= 0.25 Accuracy
Male Pressure 3= 1-5V/DC D= 10Ft. Cable C01 Calibration 1-9
E= 1/2 MNPT Range from 4= 4-20mA 2 wire E= Mini DIN 43650 C10 Calibration 10-49
J= 1/4 FNPT Chart 6= 1-6V F= Packard Metripack C50 Calibration 50-up
H= 1/8 FNPT
C= 1/4 BSPP Male Vacuum=V0000
D= 1/8 BSPP Male -14.7psig/-1.01bar

Dimensional Information
Class I, Div. 1, Groups C, D The transducers listed below are designed for installation in a Class I, Division 1, Groups C and D,
Hazardous Location Nonhazardous Location Division 1 hazardous location when connected to Associated Apparatus as described in note 1.
Entity Parameters
Hazardous Location
Vmax = 28Vdc
Red 3 excitation + Imax = 175mA Imax is the total current available from the Associated
Black 4 Intrinsic Safety 2 excitation - C1 = 0.44uf Apparatus under any condition.
/PA
Barrier PA/ L1 = 0
44X0 mV
output Green 3 signal + Notes:
White Intrinsic Safety
4 2 signal - 1. Associated Apparatus shall provide intrinsically safe connections which meet the following parameters.
Barrier PA/
/PA
Voc or Vt Vmax Ca C1 + Cleads
Isc or It Imax La L1 + Lleads
Figure 1: Wiring diagram for Ground Bus
4-wire, mV output 2. Control Room aparatus shall not generate in excess of 250V (Umax).
I. S. ground
conductor 3. Installation should be in accordance with Article 504 in the National Electrical Code, ANSI/NFPA 70.

Hazardous Location Nonhazardous Location

Table 1
Red
44X0 3 supply voltage Output Pin 3 Pin 2 Pin 1
Black 4 Intrinsic Safety 2
4-20 mA 1-5V +V Supply -V Supply Output
Barrier PA/
output /PA
analog
RL 4-20mA +V Supply -V Supply N/C
input

supply
common
Ground Bus
Figure 2: Wiring diagram for
2-wire, 4-20mA output I. S. ground
conductor

Hazardous Location Nonhazardous Location

Red
44X0 3 supply voltage
White Intrinsic Safety
Voltage 4 2 signal
Black Barrier
output /PA PA/ common

Ground Bus
Figure 3: Wiring diagram for common
3-wire, Voltage output I. S. ground
conductor