Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Units

9.2.7 Oil burners

Description HFO firing system LDO firing system

i) Type of burner Steam atomized Air atomized

ii) Burner cooling Steam or air Air


medium
iii) Burner tip Resistant to corrosion Resistant to corrosion
material due to fuel oils due to oil containing
containing sodium, sodium, vanadium,
vanadium, sulphur, sulphur, chloride etc.
chloride etc.
iv) Minimum life of 8000 hours 8000 hours
burner tips, before
needing any
maintenance/
replacements
v) Hardness of Minimum vickers Minimum vickers
atomizer (the hardness number of 400 hardness number of 400
hardness to be
retained even at
4000C)
vi) Type of oil High energy arc igniters High energy arc igniters
igniters

vii) Oil burner turn 4:1 4:1


down ratio

9.2.8 The design of fuel oil system shall ensure that compliance with the following
operational requirements:

i) Facilities for auto start of standby HFO/ LDO pressuring pumps in event
of tripping of any running pump or low fuel oil pressure.

ii) Facility for auto start and shutdown of drain oil pumps in conjunction
with level in the drain oil tanks.

iii) Facility for automatic as well as manual start/ignition of oil burners (in
association with BMS).

iv) Maximum turn down ratio, for the oil burners (without needing burner
tip changes).

v) Automatic purge interlock to facilitate restarting of oil firing system


after trip /prior shut down of oil firing.

77