Settings Editor (Group 1) (Aux Transformer) PDF
Settings Editor (Group 1) (Aux Transformer) PDF
rsf2 Page 1 of 3
SYSTEM CONFIG
System Frequency (50..60) 50Hz
Setting Dependencies (Disabled..Enabled) Enabled
Favourite Meters Timer (Off..60) 60min
Backlight timer (Off..60) 5min
Curr Set Display (xNom..Secondary) xNom
E/F Curr Set Display (xNom..Secondary) xNom
Select Grp Mode (Edge triggered..Level triggered) Edge triggered
Clock Sync. From BI (Disabled..Minutes) Minutes
Operating Mode (Out Of Service..Local Or Remote) Local Or Remote
Setting Password (Password) NONE
Control Password (Password) NONE
Trip Alert (Disabled..Enabled) Enabled
Relay Identifier (16 Character String) ARGUS-C7SR11
CT/VT CONFIG
Phase Current Input (1..5) 5A
Phase CT Ratio (1:0.2..5000:7) 100:5
Earth Current Input (1..5) 5A
Earth CT Ratio (1:0.2..5000:7) 100:5
FUNCTION CONFIG
Gn Phase Overcurrent (Enabled..Disabled) Enabled
Gn Cold Load (Enabled..Disabled) Disabled
Gn Derived E/F (Enabled..Disabled) Enabled
Gn Measured E/F (Enabled..Disabled) Disabled
Gn Restricted E/F (Enabled..Disabled) Disabled
Gn NPS Overcurrent (Enabled..Disabled) Disabled
Gn Under Current (Enabled..Disabled) Disabled
Gn Thermal (Enabled..Disabled) Disabled
Gn CB Fail (Enabled..Disabled) Disabled
Gn CT Supervision (Enabled..Disabled) Disabled
Gn Broken Conductor (Enabled..Disabled) Disabled
Gn Trip Cct Supervision (Enabled..Disabled) Disabled
Gn Close Cct Supervis'n (Enabled..Disabled) Disabled
Gn Inrush Detector (Enabled..Disabled) Disabled
Gn CB Counters (Enabled..Disabled) Disabled
Gn I^2t CB Wear (Enabled..Disabled) Disabled
Gn Demand (Enabled..Disabled) Disabled
CURRENT PROT'N
PHASE OVERCURRENT
Gn 51/50 Measurement (RMS..Fundamental) RMS
51-1
Gn 51-1 Element (Disabled..Enabled) Disabled
51-2
Gn 51-2 Element (Disabled..Enabled) Disabled
50-1
Gn 50-1 Element (Disabled..Enabled) Enabled
Gn 50-1 Setting (0.05..50) 0.63xIn
Gn 50-1 Delay (0..14400) 1s
50-2
Gn 50-2 Element (Disabled..Enabled) Enabled
Gn 50-2 Setting (0.05..50) 3.5xIn
Gn 50-2 Delay (0..14400) 0.3s
DERIVED E/F
51N-1
Gn 51N-1 Element (Disabled..Enabled) Disabled
51N-2
Gn 51N-2 Element (Disabled..Enabled) Disabled
50N-1
Gn 50N-1 Element (Disabled..Enabled) Enabled
Gn 50N-1 Setting (0.05..50) 0.06xIn
Gn 50N-1 Delay (0..14400) 1s
50N-2
Gn 50N-2 Element (Disabled..Enabled) Enabled
Gn 50N-2 Setting (0.05..50) 0.17xIn
Gn 50N-2 Delay (0..14400) 0.3s
CONTROL & LOGIC
CIRCUIT BREAKER
Gn Close CB Delay (0..60000) 10000ms
Gn Close CB Pulse (0..20) 2s
Settings Editor Aux Transformer.rsf2 Page 2 of 3