Cable Imp

You might also like

Download as txt, pdf, or txt
Download as txt, pdf, or txt
You are on page 1of 1

BaseRdc(Ohm/kft or Ohm/km) = 0.

3946
TcAdj = 1.25025
RdcT_Adj(Ohm/kft or Ohm/km) = 0.493349
Rs(uOhm/ft) = 13.2913
Yshield/sheath_Circ = 0, Yshield/sheath_Eddy = 0.0171352
MF = 1, Ycs = 0.000487992, Ycp = 0.000233414, YsShield = 0, YsSheath = 0,
YsShield/Sheath = 0.0171352,Ys (Shield + Sheath + Shield/Sheath) = 0.0171352,
YsArmor = 0, Yconduit = 0
Rac/Rdc(1.01786) = [1 + MF(1) * (Ycs(0.000487992) + Ycp(0.000233414) + Yshield(0) +
Ysheath(0)) + Yconduit(0)] * (1 + Yarmor(0))
RacT_Adj(Ohm/kft or Ohm/km) = 0.502158
RL'(Ohm/kft or Ohm/km) = 0.502158
Delta(m) = 356.956
Case1: 3 x 1/C unshielded/unsheathed and unarmoured cable with no Main or Aux N or
PE wires as per cases 1a & 1b of IEC 60909-2 Table 7 (TT system)
X1 Factor = 1