Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

External Alarm Solution

Djezzy 2G/3G Project

Huawei OTA Project


October 2014

HUAWEI TECHNOLOGIES CO., LTD.


1. BTS External Alarms Solution

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 2
BBU and Boards(UPEA & UEIU)
BBU

UEIU

UPEU

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 3
Pin definition
Board Indicator Port Type
BBU Side EXT-ALM0 0 RJ45
Color of core-cable
PIN Port UIEU
EXT-ALM1 1 RJ45
<>Orange & White 1
<> Orange 2 EXT-ALM0 2 RJ45
UPEU
<>Green & White 3 EXT-ALM1 3 RJ45
<> Green 6 RJ45
<>Blue & White 5 Connector Pin on the
RJ45
<> Blue 4 BBU Alarm Port
Connector
Wire Color Wire Type Pin on the DDF Description
in BBU
<>Brown & White 7 X1.1 White and orange X2.1 Boolean input 4+
Twisted pair
<> Brown 8 X1.2 Orange X2.2 Boolean input 4- (GND)
X1.3 White and green X2.3 Boolean input 5+
Twisted pair
EXT-ALM1 X1.6 Green X2.6 Boolean input 5- (GND)
X1.5 White and blue X2.5 Boolean input 6+
Twisted pair
X1.4 Blue X2.4 Boolean input 6- (GND)
X1.7 White and brown X2.7 Boolean input 7+
Twisted pair
X1.8 Brown X2.8 Boolean input 7- (GND)
X1.1 White and orange X2.1 Boolean input 0+
Twisted pair
X1.2 Orange X2.2 Boolean input 0+ (GND)
X1.3 White and green X2.3 Boolean input 1+
Twisted pair
X1.6 Green X2.6 Boolean input 1- (GND)
EXT-ALM0
X1.5 White and blue X2.5 Boolean input 2+
Twisted pair
X1.4 Blue X2.4 Boolean input 2- (GND)
X1.7 White and brown X2.7 Boolean input 3+
Twisted pair
X1.8 Brown X2.8 Boolean input 3- (GND)

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 4
Existing external alarm on live network

Alarm Name
High temperature (35)
Very high temperature (40)
Air Cond. Alarm
Fire alarm
Smoke Alarm
Door Open
GE working
Battery status(battery deep discharge)
Commercial power down(Main power down)
Rectifier fault
Overvoltage protection

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 5
External alarm on Huawei power system

Alarm Name
Commercial power down (Main power down)
DC output overvoltage/under voltage alarm
Rectifier fault alarm
Door status alarm (PS)
TCU fault alarm (HAU/fan/TEC fault)

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 6
Alarm Configuration
Indoor Indoor Outdoor Outdoor
Custom DDF ( Reuse (Swap (Reuse (Swap
Alarm ID Alarm Name Category BBU Pin-arrangement port arg. Power) Power) Power) Power)
65033 High temperature (35) Major UEIU White and orange/Orange 0 8
65034 Very high temperature (40) Critical UEIU White and green/Green 1 9
65035 Air Cond. Alarm Major UEIU White and Blue/Blue 2 UEIU 7
65036 Fire alarm Critical UEIU White and brown/Brown 3 EXT-ALM0 5
65037 Smoke Alarm Minor UEIU White and orange/Orange 4 12
65038 Door Open Minor UEIU White and green/Green 5 3
65039 GE working Critical UEIU White and Blue/Blue 6 16
Battery status(battery deep UEIU EXT-
65040 discharge) Critical UEIU White and brown/Brown 7 ALM1 11
Commercial power
65041 down(Main power down) Critical UPEU White and orange/Orange 0 1
65042 Rectifier fault Critical UPEU White and green/Green 1 UPEU 2
65043 Overvoltage protection Major UPEU White and Blue/Blue 2 EXT-ALM0 4

Commercial power down


65049 (Main power down) Critical UPEU White and orange/Orange 0 1
DC output under voltage
65050 alarm Critical UPEU White and Blue/Blue 1 11(4)
White and green/Green UPEU
65051 Rectifier fault alarm Critical UPEU 2 EXT-ALM0 2
65055 Door status alarm (PS) Minor UPEU White and Blue/Blue 6 14
TCU fault alarm port UPEU
65056 (HAU/fan/TEC fault) Critical UPEU White and brown/Brown 7 EXT-ALM1 15

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 77
Page
Scenario 1 :Indoor Reuse Power system
UEIU : UPEU :

0 - High temperature (35) (DDF port 8) 0 - Commercial power down(Main power down)
1 - Very high temperature (40) (DDF port 9) (DDF port 1)

0 to 3 2 - Air Cond. Alarm (DDF port 7) 0 to 3 1 - Rectifier fault (DDF port 2)


3 - Fire alarm (DDF port 5) 2 - Overvoltage protection (DDF port 4)
3-
4 - Smoke Alarm (DDF port 12) 4-
5 - Door Open (DDF port 3) 5-

4 to 7 6 - GE working (DDF port 16) 4 to 7 6-


7 - Battery status(battery deep discharge) (DDF port 11) 7-

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 8
Scenario 2 : Outdoor Reuse Power system
UEIU : UPEU :

0 - Commercial power down(Main power down)


1 - Rectifier fault

0 to 3 2 - Overvoltage protection
3-

6 - GE working
7 - Battery status(battery deep discharge)
4 to 7

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 9
Scenario 3 : Indoor SWAP Power system 1

UEIU :

0 - High temperature (35) (DDF port 8)


1 - Very high temperature (40) (DDF port 9)

0 to 3 2 - Air Cond. Alarm (DDF port 7)


3 - Fire Alarm (DDF port 5)

4 - Smoke Alarm (DDF port 12)


5 - Door Open (DDF port 3)
4 to 7 6 - GE working (DDF port 16)
7 -Battery status(battery deep discharge) (DDF port 11)

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 10
Scenario 3 : Indoor SWAP Power system 2

UPEU :

0 - Commercial power down (Main power down)


(DDF port 1)
BTS3900
1 - Rectifier fault alarm (DDF port 2)

0 to 3 2 DC input under voltage alarm


(DDF port 4)

DDF

External alarm cable

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 11
Scenario 4 : Outdoor SWAP Power system 1

UEIU :

6 - GE working

4 to 7

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 12
Scenario 4 : Outdoor SWAP Power system 2

USLP
UPEU
BTS3900A

0 - Commercial power down (Main power down)

1 - Rectifier fault alarm

2 - DC output undervoltage alarm


External alarm cable 0 to 3

6 - Door status alarm (PS)

7 - TCU fault alarm (HAU/fan/TEC fault)


4 to 7

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 13
Scenario reference : Outdoor Connection from USLP to UEP/IU
ALM1 ALM0
BBU

ALM1 ALM0
OUT1
OUT0
Board 1
USLP2

OUT0 OUT1
Board 0
BBU Alarm Pin on the RJ45
Port/USLP2 Connector in Wire Color Wire Type USLP2 port
To Custom DDF/PS Port USLP2

X1.1 White and orange IN0.1


Twisted pair
USLP2 Side X1.2 Orange IN0.2
Color of core-cable
X1.3 White and green IN1.1
PIN Port EXT- Twisted pair
X1.6 Green IN1.2
<>Orange & White 1 ALM1/OUT1 X1.5 White and blue IN0.4
Twisted pair
<> Orange 2 X1.4 Blue IN0.3
X1.7 White and brown IN1.3
Twisted pair
<>Green & White 3 X1.8 Brown IN1.4
X1.1 White and orange IN2.1
<> Green 6 RJ45 X1.2 Orange
Twisted pair
IN2.2
<>Blue & White 5 Connector X1.3 White and green IN3.1
Twisted pair
EXT- X1.6 Green IN3.2
<> Blue 4 ALM0/OUT0 X1.5 White and blue IN2.4
Twisted pair
<>Brown & White 7 X1.4 Blue IN2.3
X1.7 White and brown IN3.3
Twisted pair
<> Brown 8 X1.8 Brown IN3.4

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 14
Scenario reference : Outdoor Connection from Twisted cable to USLP

Outdoor Outdoor USLP2


Custom DDF (Reuse (Swap USLP2 USLP2 OUT to
Alarm ID Alarm Name Category BBU Pin-arrangement port arg. Power) Power) IN Board UEP/IU
65033 High temperature (35) Major UEIU White and orange/Orange 0 8 IN2.1/IN2.2
65034 Very high temperature (40) Critical UEIU White and green/Green 1 9 IN3.1/IN3.2
OUT0
65035 Air Cond. Alarm Major UEIU White and Blue/Blue 2 UEIU 7 N2.4/IN2.3
65036 Fire alarm Critical UEIU White and brown/Brown 3 EXT-ALM0 5 IN3.3/IN3.4
65037 Smoke Alarm Minor UEIU White and orange/Orange 4 12 IN0.1/IN0.2 Board 1
65038 Door Open Minor UEIU White and green/Green 5 3 IN1.1/IN1.2
65039 GE working Critical UEIU White and Blue/Blue 6 16 IN0.4/IN0.3 OUT1
Battery status(battery deep UEIU EXT-
65040 discharge) Critical UEIU White and brown/Brown 7 ALM1 11 IN1.3/IN1.4
Commercial power IN2.1/IN2.2
65041 down(Main power down) Critical UPEU White and orange/Orange 0 1 OUT0
65042 Rectifier fault Critical UPEU White and green/Green 1 UPEU 2 IN3.1/IN3.2
65043 Overvoltage protection Major UPEU White and Blue/Blue 2 EXT-ALM0 4 N2.4/IN2.3

Commercial power down IN2.1/IN2.2 Board 0


65049 (Main power down) Critical UPEU White and orange/Orange 0 1
65051 Rectifier fault alarm Critical UPEU White and green/Green 1 2 IN3.1/IN3.2 OUT0
DC output under voltage UPEU N2.4/IN2.3
65050 alarm Critical UPEU White and Blue/Blue 2 EXT-ALM0 11(4)
65055 Door status alarm (PS) Minor UPEU White and Blue/Blue 6 14 IN0.4/IN0.3
TCU fault alarm port UPEU OUT1
65056 (HAU/fan/TEC fault) Critical UPEU White and brown/Brown 7 EXT-ALM1 15 IN1.3/IN1.4

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 15
Board 1: USLP 2 OUT 0 UEIU EXT-ALM0

Board 1: USLP 2 OUT 1 UEIU EXT-ALM1

Board 1

Board 0

Board 0: USLP 2 OUT 1 UPEU EXT-ALM1

Board 0: USLP 2 OUT 0 UPEU EXT-ALM0

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 16
SLPU2 need grounding cable

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 17
Page 17
Scenario 1 : Outdoor Reuse Power system

Board 1

Board 0

GE working Rectifier fault alarm


Battery
status(battery Overvoltage
deep discharge) Main power Protection

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 18
Page 18
Scenario 2 : Outdoor Swap Power system

Board 1

Board 0

GE working Rectifier fault alarm


TCU fault alarm
port (HAU/fan/ DC input
Door status alarm TEC fault) Main power under voltage
(Battery Rack) Alarm

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 19
Page 19
Board 1

Board 0

Scenario 2 : Outdoor
Swap Power system

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 20
Page 20
Rectifier fault Door status
Main power DC output overvoltage alarm TCU fault
alarm (Battery
under voltage alarm (BDD) alarm
Rack)

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 21
Page 21
BTS External Alarm Configure Script
Scenario 1,2 :

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 22
BTS External Alarm Configure Script
Scenario 3,4 :

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 23
Alarm Name Definition Script
Define all external alarms for BTS, once per BSC:

SET ENVALMPARA:AID=65033, ANM="High temperature (35)", ALVL=Major, ASS=env;


SET ENVALMPARA:AID=65034, ANM="Very high temperature (40)", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65035, ANM="Air Cond. Alarm", ALVL=Major, ASS=env;
SET ENVALMPARA:AID=65036, ANM="Fire alarm", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65037, ANM="Smoke Alarm", ALVL=Minor, ASS=env;
SET ENVALMPARA:AID=65038, ANM="Door Open", ALVL=Minor, ASS=env;
SET ENVALMPARA:AID=65039, ANM="GE working", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65040, ANM="Battery status(battery deep discharge)", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65041, ANM="Commercial power down(Main power down)", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65042, ANM="Rectifier fault", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65043, ANM="Overvoltage protection", ALVL=Major, ASS=env;

SET ENVALMPARA:AID=65049, ANM="Commercial power down (Main power down) ", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65050, ANM="DC output overvoltage/under voltage alarm", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65051, ANM="Rectifier fault alarm ", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65052, ANM="AC/DC surge protection alarm", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65053, ANM="Load/battery fuse and circuit failure alarm", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65054, ANM="Battery over-temperature and under-temperature alarm", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65055, ANM="Door status alarm (PS)", ALVL=Minor, ASS=env;
SET ENVALMPARA:AID=65056, ANM="TCU fault alarm port (HAU/fan/TEC fault)", ALVL=Critical, ASS=env;

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 24
2. BSC External Alarms Solution

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 25
Environment Alarm of BSC

BSC6900

J2
EMUA 5 to 8 1 to 4

(1) Six ports for Boolean signal output (2) Port for water sensors

(3) Port for door status sensors (4) Port for smoke sensors

(5) Port for humidity/temperature sensors (6) Port for infrared sensors

(7) Four ports for analog signal sensors (8) RS-232 port

(9) Active/standby power port (10) Two RS-485 ports


Power (12) Thirty-two ports for Boolean signal
(11) Grounding screw sensors

OTA request

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 26
BSC System Alarms

(2) Port for water sensors (3) Port for door status sensors
(5) Port for humidity/temperature
(4) Port for smoke sensors
sensors

Alarm ID Alarm Name Severity Alarm Type


20043 Water Damage Critical Fault
20045 Ambient Temperature Abnormal Major Fault
20046 Ambient Humidity Abnormal Major Fault
20047 Smoke Critical Fault
20048 Theft Proof Critical Fault

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 27
BSC Custom External Alarms

Alarm Alarm Alarm


Alarm ID Alarm Name Cabinet Subrack Port
Severity Type Voltage
65334 Air Cond Alarm Major Fault 0 0 1 High
65335 HEAT_VENT Major Fault 0 0 2 High
65336 High Temp 35 Major Alarm 0 0 3 High
65337 High Temp 40 Critical Alarm 0 0 4 High
65338 Main Power Down Critical Alarm 0 0 5 High
65339 Rectifier Fault Major Alarm 0 0 6 High
65340 Battery discharge Fault Critical Alarm 0 0 7 High
65341 GE Fault Critical Alarm 0 0 8 High
65342 Door Open Minor Alarm 0 0 9 High

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 28
DIP in EMUA type B
humidity/temperature

ON-ON

SW_THE

ON-ON-OFF-OFF

SW_ADDR water/smoke/optical/gate
OFF-ON-ON-ON

SW_BKE
HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 29
BSC External Alarm Configure Script
BSC External Alarm Name Definition
SET ENVALMPARA:AID=65334, ANM="Air Cond Alarm", ALVL=Major, ASS=env;
SET ENVALMPARA:AID=65335, ANM="HEAT_VENT", ALVL=Critical, ASS=power;
SET ENVALMPARA:AID=65336, ANM= High temperature (35)", ALVL=Major, ASS=env;
SET ENVALMPARA:AID=65337, ANM ="Very high temperature (40)", ALVL=Critical, ASS=env;
SET ENVALMPARA:AID=65338, ANM="Main Power Down", ALVL=Critical, ASS=power;
SET ENVALMPARA:AID=65339, ANM="Rectifier Fault", ALVL=Major, ASS=power;
SET ENVALMPARA:AID=65340, ANM="Battery discharge Fault", ALVL=Critical, ASS=power;
SET ENVALMPARA:AID=65341, ANM="GE Fault", ALVL=Critical, ASS=power;
SET ENVALMPARA:AID=65342, ANM="Door Open", ALVL=Minor, ASS=env;

BSC external alarm activation Script


SET ALMPORT:SRN=0, PN=1, PT=BOOL, SW=OPEN, AID=65334, AVOL=HIGH;
SET ALMPORT:SRN=0, PN=2, PT=BOOL, SW=OPEN, AID=65335, AVOL=HIGH;
SET ALMPORT:SRN=0, PN=3, PT=BOOL, SW=OPEN, AID=65336, AVOL=HIGH;
SET ALMPORT:SRN=0, PN=4, PT=BOOL, SW=OPEN, AID=65337, AVOL=HIGH;
SET ALMPORT:SRN=0, PN=5, PT=BOOL, SW=OPEN, AID=65338, AVOL=HIGH;
SET ALMPORT:SRN=0, PN=6, PT=BOOL, SW=OPEN, AID=65339, AVOL=HIGH;
SET ALMPORT:SRN=0, PN=7, PT=BOOL, SW=OPEN, AID=65340, AVOL=HIGH;
SET ALMPORT:SRN=0, PN=8, PT=BOOL, SW=OPEN, AID=65341, AVOL=HIGH;
SET ALMPORT:SRN=0, PN=9, PT=BOOL, SW=OPEN, AID=65342, AVOL=HIGH;

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 30
Comments

The remaining alarm can be used for the special cases as: Power Down for a Transmission
site.

For 3G overlay sites: Huawei PS alarms will be connected to the existing 2G BTS.

The status (open or closed) can be changed according to each alarm.

More special alarms can be created according to each actual BSC alarms (exp: alarm power
for site Trans, or others);

Special modifications can be done on the created alarms

For 3G only sites (in the future), the external alarms will be connected to the 3G NodeB.

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 31
Pave the way to Broadband Life
Together!
Thank you

HISILICONTECHNOLOGIES
HUAWEI SEMICONDUCTOR
CO., LTD. Page 32

You might also like