Professional Documents
Culture Documents
09 System Earthing
09 System Earthing
By
T.R.Sathyanarayana Rao
Agenda
Ungrounded & Solidly Grounded Systems
Show Hazards
Review Systems
Discuss causes of Hazards
Solidly Grounded
Resistance Grounded
Ungrounded Systems
Popular in 3-wire LV systems up to 1950s
Industrial and water treatment facilities
Negligible fault current and no tripping on first
ground fault
Difficult to locate ground faults
5-6 times transient voltage escalation on
intermittent, sputtering arcing ground faults due
to DC voltage buildup across the stray
capacitance to ground
Capacitive Charging Current
C A N
C A N
120 60
82
N
G G
B
Full Ground Fault on Phase B
B
B
50% Ground Fault on Phase B
No Ground Fault
System Charging Current 3IC0
A
347V
B
C
N Bolted
Ground Fault
69 5A to equipment
G frame
System Capacitance
Unable to discharge leading to transient over-voltages
C
Ground Faults
Ground fault current distribution (minimal current)
480V Delta Source
3 Load
A B
C
440V
Xc
c
c
Xb Xc
a
Total Capacitive Current
Ic
c
c
Ib Ic
a If
I f = (I c c c
a + I b + Ic )
Ica = 0A (short-circuited)
V l-l V l-l
c c
Ib = Ic =
c c Ground A
Xb Xc
Bolted Ground Faults
Highly Inductive Reactance Ground Fault
Bolted ground fault: A highly inductive reactance ground fault in series with
system capacitance can create a resonant circuit causing high transient over-
voltages.
i.e. grounding of one side of the operating coil of a motor starter, grounding of one
control wire to a push button station, or grounding of one side of a transformer
winding
480V Delta Source
R fe 3 Load
V V
L fa
Ca Ca
Bolted Ground Faults
Highly Inductive Reactance Ground Fault
The voltage across Lfa is increasing due to resonance.
Resonance occurs when L = 1 / ( C).
OCPDs do not trip because ground fault current is low due to high
values of Lfa and Ca.
System Resonance:
L = 1 / ( C)
260*700mH = 1/ (260*0.01mF)
263.9 265.3
Bolted Ground Faults
Highly Inductive Reactance Ground Fault
Plot of transient over-voltage for a bolted ground fault
Arcing Ground Faults
Intermittent or Re-strike
Intermittent ground fault: A re-striking ground fault can create a high
frequency oscillator (RLC circuit), independent of L and C values, causing
high transient over-voltages.
i.e. re-striking due to ac voltage waveform or loose wire caused by vibration
480V Delta Source
R fe 3 Load
V V
Cb Cb
S fa
Arcing Ground Faults
Intermittent or Re-strike
The voltage across Cb is increasing due to intermittent contact or
re-striking (shown below as switches Sfa and Sfb) between phase
conductor and ground causes an oscillator effect.
OCPDs do not trip because ground fault current is low due to high
value of Rf.
Arcing Ground Faults
Intermittent or Re-strike
Plot of transient over-voltage for a bolted ground fault
Locating Ground Faults
Good Luck!
No direct return to source, only way is through system
capacitance.
Use over-voltage
Indicator light and relay method to indicate ground
fault.
De-energize one feeder at a time.
Very time consuming and dangerous!
Unknown ground fault may be on system for long period of time.
May de-energize vital equipment trying to find fault.
Advantages / Disadvantages
with Ungrounded Systems
Advantages
Low fault current for line-to-ground faults (typically < 5A)
No Flash Hazard for ground faults
Continue operation during FIRST ground fault
Disadvantages
Difficult to locate ground faults
Severe transient over-voltages possible during ground faults
Higher costs due to labor and downtime locating ground faults
Second ground fault on another phase will result in phase-phase
fault
Do others agree?
TO HRG OR NOT TO HRG?
Dont need
the red in a
HRG System
LSG LSG
A
B
C
N
Extra Expense due to SG System
NEC 250.95 GFP Requirement
Systems over 150Vlg to less than 600Vll
Each disconnect switch 1000A or more
Maximum setting of 1200A
Maximum time delay of 1sec
Must be performance tested upon installation
C
Solidly Grounded Systems
Intentionally grounded through ground wire
A B
~0
In Icc Icb Ica
I ca + I cb + I cc = 0
Bolted Ground Faults
Ground fault current distribution on A
480V W ye Source
3 Load
A B
In I cc I cb I ca If
~60kA
Estim ated Total Fault Current Exam ple (2500kVA, 480V, Z = 5 % )
~0A (3A)
1 1
If = * I fla + (I cb + I cc ) = ~I n In = If = * 3000A = ~60,000A
Z pu 0.05
Bolted Ground Faults
Bolted ground fault: A high fault current
causing severe damage. If properly
coordinated and installed, OCPDs will clear No transient
fault after acceptable damage. over-voltages
High fault
current
Arcing Ground Faults
Ground fault current distribution on A
480V W ye Source
3 Load
A B
In I cc I cb I ca
If
~23kA
Estim ated Total Fault Current Exam ple (2500kVA, 480V, Z = 5 % )
~0A (3A)
1 1
If = * I fla * .38 + (I cb + I cc ) = ~I n In = If = * 3000A * .38 = ~23kA
Z pu 0.05
Arcing Ground Faults
Arcing ground fault: Lower fault current, so
OCPDs may not clear fault. Delay will cause
severe equipment and personnel damage due to No transient
tremendous amount of energy released. over-voltages
High fault
current
Disadvantages
Severe Arc Flash Hazard
Loss of production
Higher costs to due equipment damage
High values of ground fault current
High probability of ground fault escalating into 3-phase fault
Creates problems on primary
High Resistance Grounding
How does HRG solve these hazards?
Inserts a resistor between neutral and ground
Eliminates 100% of Electrocution
Eliminates 90% of Arc Flash / Blast Injuries
Source
(Wye)
A B
HRG C
High Resistance Grounding
What if no neutral exists (i.e. delta systems)?
A grounding transformer is installed (either a zig-zag or a wye-
delta) from all three phases to create an artificial neutral for
grounding purposes only.
See Appendices B,C and D for examples and calculations.
A B C A B C A B C
Zig-Zag
Grounding HRG
Transformer
Wye-Delta Wye-Delta
Grounding Grounding
Transformers Transformers
HRG HRG
High Resistance Grounding
Intentionally grounded through neutral resistor
480V Wye Source
3 Load
A B
N
C
HRG
277V
Vng0V
c c c
Ir Ic Ib Ia
Ground 0V
High Resistance Grounding
Compared to Ungrounded Systems (voltage rise)
480V Wye Source
3 Load
A B
N
C
HRG
480V
VngVan
(277V) Ir
c
Ic
c
Ib
c
Ia If
A B
C
L fa
HRG
Ca
c c c
Ir Ic Ib Ia If
A B
C
HRG
S fa
Ca
c c c
Ir Ic Ib Ia
If
Dischage Path
A B
C
HRG
Ca
c c c
Ir Ic Ib Ia If
Resistor (HRG) in lieu of wire adds significant amount of resistance to lower ground
fault to a predetermined value preventing destructive fault currents and shut-down!
High Resistance Grounding
Compared with Solidly Grounded (current rise)
480V Wye Source
3 Load
A B
C
HRG
55.4
277
c c c
5.00A Ir Ic Ib Ia If
5.83A
1.73A
Fault conditions
c c c
( I a + I b + I c ) = (0 + 1.7360o + 1.73120o ) = 3.0090o A
2 c c c
Vng 277V I f = I r + ( I a + I b + I c ) 2 = 5.83 A
Ir = = = 5.000o A
Rr 55.4 I f = 3.0090o + 5.000o = 5.8331o A
High Resistance Grounding
Another advantage of return path: ground fault location
480V Wye Source
3 Load
A B
C
HRG
Ca
c c c
Ir Ic Ib Ia
If
Contactor shorts out part of the resistor changing the resistance, hence, changing the
current. Ground fault current now is a pulse signal that allows for detection!
High Resistance Grounding
Contactor shorts out resistance, thus, doubling
current to 10A at ~30 pulses / minute.
High Resistance Grounding
Meter reading will alternate
Method to quickly locate ground faults. from 5A to 10A every 2
seconds.
480V Wye Source
85A 55A
5A
A B 80A 50A
C
HRG
55.4 80A 50A
ohms
30A 30A 30A 55A 50A 50A
0A 5A
ZSCT ZSCT
5A
Meter Meter
5A
0A
ZSCT
Motor Motor
Ground Faults
Damage to Power System Components:
Ungrounded HRG
1000V Cables
Only CSA listed, not UL
5000V Cables
Non-shielded: Should be used on 2400V systems (HRG)
Shielded: Should be used on 4160V systems (HRG)
8000V Cables
Non-shielded: Should be used on 4160V systems (HRG)
Loss of Ground Hazard
A B A B A B
N N N
C C C C
HRG HRG HRG