System Psychrometrics for CONTROL ROOM

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:55AM

July DESIGN COOLING DAY, 1800

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 44.3 0.02037 0 400 0 0
Vent - Return Mixing Outlet 22.7 0.00922 547 1835 - -
Central Cooling Coil Outlet 13.4 0.00896 547 1835 6130 420
Supply Fan Outlet 13.4 0.00896 547 1835 51 -
Cold Supply Duct Outlet 13.5 0.00896 541 1835 - -
Zone Air - 21.7 0.00923 541 1836 5310 420
Return Plenum Outlet 22.8 0.00923 541 1836 714 -
Duct Leakage Air Outlet 13.4 0.00896 5 1835 - -
Return Duct Outlet 22.7 0.00922 547 1835 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.3 W/(L/s)
Site Altitude = 14.9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone 1 5542 Cooling 5310 21.7 541 1836 0 0

Hourly Analysis Program v4.50 Page 1 of 2


System Psychrometrics for CONTROL ROOM
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:55AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 12.0 0.00682 0 400 0 0
Vent - Return Mixing Outlet 19.2 0.01028 547 800 - -
Central Cooling Coil Outlet 19.2 0.01028 547 800 0 0
Supply Fan Outlet 19.3 0.01028 547 800 51 -
Cold Supply Duct Outlet 19.3 0.01028 541 800 - -
Zone Air - 19.2 0.01028 541 800 -32 0
Return Plenum Outlet 19.2 0.01028 541 800 0 -
Duct Leakage Air Outlet 19.3 0.01028 5 800 - -
Return Duct Outlet 19.2 0.01028 547 800 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.3 W/(L/s)
Site Altitude = 14.9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone 1 -322 Deadband -32 19.2 541 800 0 0

Hourly Analysis Program v4.50 Page 2 of 2