Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

SEI GREEN FLASH PVT LTD_33KV POWER CABLE SCHEDULE & TERMINATION

SOURCE DESTINATION 10% Tolerance TOTAL


MEASURED GLAND
S.No Core No. TYPE FUNCTION on Measure ESTIMATED NOTES
EQUIPMENT Cable Tag Term No. Term No. Cable Tag EQUIPMENT LENGTH (Mtr) TYPE
Length (Mtr) LENGTH

HTP1-1-TRF1 :R PHASE 1 :R PHASE HTP1-1-TRF1 Actual Lenghts to


INV.TRANSFORM
INVERTER BLOCK-1 HT 33kV,3core,185 sqmm, XLPE be verified at site
1 ER1 _HV CABLE HTP1-1-TRF1 :Y PHASE 2 :Y PHASE HTP1-1-TRF1 POWER CABLE 13 1.3 14.00 2
PANEL (ICOG) Aluminium cable ,Rolling is to be
BOX
prefarable
HTP1-1-TRF1 :B PHASE 3 :B PHASE HTP1-1-TRF1

HTP1-1-HTP2 :R PHASE 1 :R PHASE HTP1-1-HTP2 INVERTER BLOCK-2 HT


Actual Lenghts to
INVERTER BLOCK- PANEL (5 BOARD PANEL)
HTP1-1-HTP2 :Y PHASE 2 :Y PHASE HTP1-1-HTP2 33kV,3core,185 sqmm, XLPE be verified at site
2 1 HT PANEL - INCOMER FROM POWER CABLE 225 22.5 248.00 2
Aluminium cable ,Rolling is to be
(ICOG) INVERTER BLOCK 1
prefarable
HTP1-1-HTP2 :B PHASE 3 :B PHASE HTP1-1-HTP2 ICOG

INVERTER BLOCK-2 HT
HTP2-1-TRF2 :R PHASE 1 :R PHASE HTP2-1-TRF2 Actual Lenghts to
INV.TRANSFORM PANEL (5 BOARD PANEL)
33kV,3core,185 sqmm, XLPE be verified at site
3 ER2 _HV CABLE - INCOMER FROM POWER CABLE 16 1.6 18.00 2
HTP2-1-TRF2 :Y PHASE 2 :Y PHASE HTP2-1-TRF2 Aluminium cable ,Rolling is to be
BOX INVERTER
prefarable
TRANSFORMER I
HTP2-1-TRF2 :B PHASE 3 :B PHASE HTP2-1-TRF2

HTP4-1-TRF4 :R PHASE 1 :R PHASE HTP4-1-TRF4 Actual Lenghts to


INV.TRANSFORM
INVERTER BLOCK-4 HT 33kV,3core,185 sqmm, XLPE be verified at site
4 ER4_HV CABLE POWER CABLE 13 1.3 14.00 2
HTP4-1-TRF4 :Y PHASE 2 :Y PHASE HTP4-1-TRF4 PANEL (ICOG) Aluminium cable ,Rolling is to be
BOX
prefarable
HTP4-1-TRF4 :B PHASE 3 :B PHASE HTP4-1-TRF4

INVERTER BLOCK-2 HT
HTP4-1-HTP2 :R PHASE 1 :R PHASE HTP4-1-HTP2 Actual Lenghts to
INVERTER BLOCK- PANEL (5 BOARD PANEL)
33kV,3core,185 sqmm, XLPE be verified at site
5 4 HT PANEL - INCOMER FROM POWER CABLE 510 51 561.00 2
HTP4-1-HTP2 :Y PHASE 2 :Y PHASE HTP4-1-HTP2 Aluminium cable ,Rolling is to be
(ICOG) INVERTER BLOCK 4
prefarable
ICOG
HTP4-1-HTP2 :B PHASE 3 :B PHASE HTP4-1-HTP2

HTP2-1-AUTF :R PHASE 1 :R PHASE HTP2-1-AUTF


INVERTER
BLOCK-2 HT PANEL 06 (OUTGOING Actual Lenghts to
PANEL (5 BOARD 160KVA AUX.TFR (HV 33kV,3core,185 sqmm, XLPE TO AUX be verified at site
6 50 5 55.00 2
PANEL)- SIDE ) Aluminium cable TRANSFORMER ,Rolling is to be
HTP2-1-AUTF :Y PHASE 2 :Y PHASE HTP2-1-AUTF
OUTGOING TO 160KVA) prefarable
160KVA AUX.TFR

HTP2-1-AUTF :B PHASE 3 :B PHASE HTP2-1-AUTF

INVERTER
HTP2-1-MCR4 :R PHASE 1 :R PHASE HTP2-1-MCR4
BLOCK-2 HT Actual Lenghts to
MCR HT PANEL-
PANEL (5 BOARD 33kV,3core,300 sqmm, XLPE be verified at site
7 INCOMING FROM POWER CABLE 1625 162.5 1788.00 1
PANEL)- HTP2-1-MCR4 :Y PHASE 2 :Y PHASE HTP2-1-MCR4 Aluminium cable ,Rolling is to be
INVERTER BLOCK-2
OUTGOING TO prefarable
MAIN PSS
HTP2-1-MCR4 :B PHASE 3 :B PHASE HTP2-1-MCR4

HTP6-1-TRF6 :R PHASE 1 :R PHASE HTP6-1-TRF6 Actual Lenghts to


INV.TRANSFORM
INVERTER BLOCK-6 HT 33kV,3core,185 sqmm, XLPE be verified at site
8 ER6 _HV CABLE POWER CABLE 13 1.3 14.00 2
HTP6-1-TRF6 :Y PHASE 2 :Y PHASE HTP6-1-TRF6 PANEL (ICOG) Aluminium cable ,Rolling is to be
BOX
prefarable
HTP6-1-TRF6 :B PHASE 3 :B PHASE HTP6-1-TRF6

Page 1 of 3
HTP6-1-MCR5 :R PHASE 1 :R PHASE HTP6-1-MCR5 Actual Lenghts to
INVERTER BLOCK- MCR HT PANEL-
33kV,3core,185 sqmm, XLPE be verified at site
9 6 HT PANEL INCOMING FROM POWER CABLE 52 5.2 57.00 2
HTP6-1-MCR5 :Y PHASE 2 :Y PHASE HTP6-1-MCR5 Aluminium cable ,Rolling is to be
(ICOG) INVERTER BLOCK-6
prefarable
HTP6-1-MCR5 :B PHASE 3 :B PHASE HTP6-1-MCR5

HTP5-1-TRF5 :R PHASE 1 :R PHASE HTP5-1-TRF5 Actual Lenghts to


INV.TRANSFORM
INVERTER BLOCK-5 HT 33kV,3core,185 sqmm, XLPE be verified at site
10 ER5 _HV CABLE HTP5-1-TRF5 :Y PHASE 2 :Y PHASE HTP5-1-TRF5 POWER CABLE 13 1.3 14.00 2
PANEL (ICOG) Aluminium cable ,Rolling is to be
BOX
prefarable
HTP5-1-TRF5 :B PHASE 3 :B PHASE HTP5-1-TRF5

HTP5-1-TRF5 :R PHASE 1 :R PHASE HTP5-1-TRF5 INVERTER BLOCK-8 HT


Actual Lenghts to
INVERTER BLOCK- PANEL (4 BOARD PANEL)
33kV,3core,185 sqmm, XLPE be verified at site
11 5 HT PANEL HTP5-1-TRF5 :Y PHASE 2 :Y PHASE HTP5-1-TRF5 - INCOMER FROM POWER CABLE 716 71.6 788.00 2
Aluminium cable ,Rolling is to be
(ICOG) INVERTER BLOCK 5
prefarable
HTP5-1-TRF5 :B PHASE 3 :B PHASE HTP5-1-TRF5 ICOG

HTP7-1-TRF7 :R PHASE 1 :R PHASE HTP7-1-TRF7 Actual Lenghts to


INV.TRANSFORM
INVERTER BLOCK-7 HT 33kV,3core,185 sqmm, XLPE be verified at site
12 ER7 _HV CABLE POWER CABLE 13 1.3 14.00 2
HTP7-1-TRF7 :Y PHASE 2 :Y PHASE HTP7-1-TRF7 PANEL (ICOG) Aluminium cable ,Rolling is to be
BOX
prefarable
HTP7-1-TRF7 :B PHASE 3 :B PHASE HTP7-1-TRF7

INVERTER BLOCK-8 HT
HTP7-1-MCR8 :R PHASE 1 :R PHASE HTP7-1-MCR8 Actual Lenghts to
INVERTER BLOCK- PANEL (4 BOARD PANEL)
33kV,3core,185 sqmm, XLPE be verified at site
13 7 HT PANEL - INCOMER FROM POWER CABLE 415 41.5 457.00 2
HTP7-1-MCR8 :Y PHASE 2 :Y PHASE HTP7-1-MCR8 Aluminium cable ,Rolling is to be
(ICOG) INVERTER BLOCK-7
prefarable
ICOG
HTP7-1-MCR8 :B PHASE 3 :B PHASE HTP7-1-MCR8

HTP8-1-TRF8 :R PHASE 1 :R PHASE HTP8-1-TRF8 INVERTER BLOCK-8 HT


Actual Lenghts to
INV.TRANSFORM PANEL (4 BOARD PANEL)
33kV,3core,185 sqmm, XLPE be verified at site
14 ER8 _HV CABLE HTP8-1-TRF8 :Y PHASE 2 :Y PHASE HTP8-1-TRF8 - INCOMER FROM POWER CABLE 16 1.6 18.00 2
Aluminium cable ,Rolling is to be
BOX INVERTER
prefarable
TRANSFORMER
HTP8-1-TRF8 :B PHASE 3 :B PHASE HTP8-1-TRF8

INVERTER HTP2-1-MCR3 :R PHASE 1 :R PHASE HTP2-1-MCR3


BLOCK-8 HT Actual Lenghts to
MCR HT PANEL-
PANEL (4 BOARD 33kV,3core,300 sqmm, XLPE be verified at site
15 INCOMING FROM POWER CABLE 925 92.5 1018.00 1
PANEL)- Aluminium cable ,Rolling is to be
HTP2-1-MCR3 :Y PHASE 2 :Y PHASE HTP2-1-MCR3 INVERTER BLOCK-8
OUTGOING TO prefarable
MAIN PSS

HTP2-1-MCR3 :B PHASE 3 :B PHASE HTP2-1-MCR3

HTP3-1-TRF3 :R PHASE 1 :R PHASE HTP3-1-TRF3 Actual Lenghts to


INV.TRANSFORM
INVERTER BLOCK-3 HT 33kV,3core,185 sqmm, XLPE be verified at site
16 ER3 _HV CABLE POWER CABLE 13 1.3 14.00 2
HTP3-1-TRF3 :Y PHASE 2 :Y PHASE HTP3-1-TRF3 PANEL (ICOG) Aluminium cable ,Rolling is to be
BOX
prefarable
HTP3-1-TRF3 :B PHASE 3 :B PHASE HTP3-1-TRF3

HTP3-1-MCR2 :R PHASE 1 :R PHASE HTP3-1-MCR2 Actual Lenghts to


INVERTER BLOCK- MCR HT PANEL-
33kV,3core,185 sqmm, XLPE be verified at site
17 3 HT PANEL INCOMING FROM POWER CABLE 448 44.8 493.00 2
HTP3-1-MCR2 :Y PHASE 2 :Y PHASE HTP3-1-MCR2 Aluminium cable ,Rolling is to be
(ICOG) INVERTER BLOCK-3
prefarable
HTP3-1-MCR2 :B PHASE 3 :B PHASE HTP3-1-MCR2

Page 2 of 3
HTP9-1-TRF9 :R PHASE 1 :R PHASE HTP9-1-TRF9 Actual Lenghts to
INV.TRANSFORM
INVERTER BLOCK-9 HT 33kV,3core,185 sqmm, XLPE be verified at site
18 ER9 _HV CABLE POWER CABLE 13 1.3 14.00 2
HTP9-1-TRF9 :Y PHASE 2 :Y PHASE HTP9-1-TRF9 PANEL (ICOG) Aluminium cable ,Rolling is to be
BOX
prefarable
HTP9-1-TRF9 :B PHASE 3 :B PHASE HTP9-1-TRF9

HTP9-1-MCR1 :R PHASE 1 :R PHASE HTP9-1-MCR1 Actual Lenghts to


INVERTER BLOCK- MCR HT PANEL-
33kV,3core,185 sqmm, XLPE be verified at site
19 9 HT PANEL INCOMING FROM POWER CABLE 814 81.4 895.00 2
HTP9-1-MCR1 :Y PHASE 2 :Y PHASE HTP9-1-MCR1 Aluminium cable ,Rolling is to be
(ICOG) INVERTER BLOCK-9
prefarable
HTP9-1-MCR1 :B PHASE 3 :B PHASE HTP9-1-MCR1

MCR3-1-AUTF :R PHASE 1 1 MCR3-1-AUTF Actual Lenghts to


MCR HT PANEL-
MCR3-1-AUTF :Y PHASE 2 2 MCR3-1-AUTF 33kV,3core,185 sqmm, XLPE be verified at site
20 O/G TO 1160KVA AUX.TFR HV SIDE POWER CABLE 50 5 55.00 2
Aluminium cable ,Rolling is to be
AUX.TFR
prefarable
MCR3-1-AUTF :B PHASE 3 3 MCR3-1-AUTF

PSS-1-MCR-1 :R PHASE 1 :R PHASE PSS-1-MCR-1 Actual Lenghts to


MCR HT PANEL-
33kV,3core,300 sqmm, XLPE be verified at site
21 O/G TO 132/33KV 33/132KV TFR LV SIDE POWER CABLE 37 3.7 41.00 1
PSS-1-MCR-1 :Y PHASE 2 :Y PHASE PSS-1-MCR-1 Aluminium cable ,Rolling is to be
S/S
prefarable
PSS-1-MCR-1 :B PHASE 3 :B PHASE PSS-1-MCR-1

PSS-2-MCR-1 :R PHASE 1 :R PHASE PSS-2-MCR-1 Actual Lenghts to


MCR HT PANEL-
33kV,3core,300 sqmm, XLPE be verified at site
22 O/G TO 132/33KV 33/132KV TFR LV SIDE POWER CABLE 37 3.7 41.00 1
PSS-2-MCR-1 :Y PHASE 2 :Y PHASE PSS-2-MCR-1 Aluminium cable ,Rolling is to be
S/S
prefarable
PSS-2-MCR-1 :B PHASE 3 :B PHASE PSS-2-MCR-1

PSS-3-MCR-1 :R PHASE 1 :R PHASE PSS-3-MCR-1 Actual Lenghts to


MCR HT PANEL-
33kV,3core,300 sqmm, XLPE be verified at site
23 O/G TO 132/33KV 33/132KV TFR LV SIDE POWER CABLE 37 3.7 41.00 1
PSS-3-MCR-1 :Y PHASE 2 :Y PHASE PSS-3-MCR-1 Aluminium cable ,Rolling is to be
S/S
prefarable
PSS-3-MCR-1 :B PHASE 3 :B PHASE PSS-3-MCR-1

GLAND TYPE CABLE TYPE LENGTH (Mts) GLANDS


1 33kV,3core,300 sqmm, XLPE Aluminium cable 2929 10
2 33kV,3core,185 sqmm, XLPE Aluminium cable 3743 36

Client : SEI GREENFLASH PVT. LTD.


Title: 33KV POWER CABLE SCHEDULE & TERMINATION
GREENFLASH

Substation: 30MW SOLAR PV POWER PLANT AT CHEJERLA (V), SPSR NELLORE (DIST), ANDHRAPRADESH STATE.

Rev.
Drawing. No. 3014 -S1-E-03-006-027-002
A

Page 3 of 3