Intelligent multi-objective optimization for building


energy and comfort management
Pervez Hameed Shaikh a,b,*, Nursyarizal Bin Mohd Nor b, Perumal Nallagownden b,
Irraivan Elamvazuthi b

a
Department of Electrical Engineering, Mehran University of Engineering and Technology, Jamshoro 76062, Pakistan
b
Department of Electrical & Electronic Engineering, Universiti Teknologi PETRONAS, Malaysia

Received 30 January 2015; accepted 6 March 2016

KEYWORDS Abstract The rapid economic and population growth in developing countries, effective and effi-
Energy; cient energy usage has turned out to be crucial due to the rising concern of depleting fossil fuels,
Buildings; of which, one-third of primary energy is consumed in buildings and expected to rise by 53% up
Comfort; to 2030. This roaring sector posing a challenge, due to 90% of people spend most of their time
Management; in buildings, requires enhanced well-being of indoor environment and living standards. Therefore,
Optimization; building operations require more energy because most of the energy is consumed to make the
Trade-off indoor environment comfortable. Consequently, there is the need of improved energy efficiency
to decrease energy consumption in buildings. In relation to this, the primary challenge of building
control systems is the energy consumption and comfort level are generally conflicting to each other.
Therefore, an important problem of sustainable smart buildings is to effectively manage the energy
consumption and comfort and attain the trade-off between the two. Thus, smart buildings are
becoming a trend of future construction that facilitates intelligent control in buildings for the
fulfillment of occupants comfort level. In this study, an intelligent multi-objective system has been
developed with evolutionary multi-objective genetic algorithm (MOGA) optimization method. The
corresponding case study simulation results for the effective management of users comfort and
energy efficiency have been carried out. The case study results show the management of energy sup-
ply for each comfort parameter and maintain high comfort index achieving balance between the
energy consumption and comfort level.
2016 The Authors. Production and hosting by Elsevier B.V. on behalf of King Saud University. This is
an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).

* Corresponding author at: Department of Electrical Engineering,


Mehran University of Engineering and Technology, Jamshoro 76062, 1. Introduction
Pakistan.
E-mail address: engr.pervezhameed@gmail.com (P.H. Shaikh).
The prompt rise in worlds energy consumption has been
Peer review under responsibility of King Saud University.
observed for last two decades and is estimated to rise by
53% until 2030 (International Energy Agency, 2007). The sec-
ond largest energy-consuming sector after transport is build-
Production and hosting by Elsevier ings (which includes residential and commercial sectors) hold

http://dx.doi.org/10.1016/j.jksues.2016.03.001
1018-3639 2016 The Authors. Production and hosting by Elsevier B.V. on behalf of King Saud University.
This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
Please cite this article in press as: Shaikh, P.H. et al., Intelligent multi-objective optimization for building energy and comfort management. Journal of King Saud
University Engineering Sciences (2016), http://dx.doi.org/10.1016/j.jksues.2016.03.001
2 P.H. Shaikh et al.

approximately, one-third of the global energy, thus touching meta-heuristic, population based technique can instanta-
40% of buildings primary energy consumption in developing neously explore and utilize various solution space regions.
countries (Costa et al., 2013). The factors contributing this GA being very suitable for Pareto optimality set in complex
energy level mainly involve population growth, increased spaces. Various multi-objective genetic algorithm techniques
building amenities, and improved comfort index along with exist for assigned fitness, maintaining diversity and preserving
the time spent inside the buildings, show an upward trend elite solutions. Multi-islanded genetic algorithm (MIGA) and
for rise in building energy demand in near future. simple genetic algorithm (GA) have been used for energy con-
The building operations need improved energy efficiency to servation and comfort management developed in Safdar and
decrease energy consumption. Conversely, the attainment of Dohyeun (2013), and this employs MIGA at the input fuzzy
quality indoor environment requires more energy. Hence, an parameters optimization for environmental difference. Wang
important problem of sustainable smart buildings is to achieve et al. (2011), proposed multi-agent controller structure to man-
the trade-off between the requirement of power and the occu- age energy consumption and occupants comfort. It employed
pants comfort. The main factors in the tropical areas, which particle swarm optimization (PSO) at the central agent to
define quality lives of occupants in the indoor environment observe the trade-off solutions for informed decision-making.
are temperature, humidity, illumination and air quality. There- However, yet multi-objective genetic algorithm needs to be
fore, an intelligent control of the thermal, humidification, illu- employed for several strategies. To accomplish, the distributed
mination and air quality, comfort factors, is important for control of several comfort demands, the main task of the
energy efficiency and occupants quality of living. intended building control systems is to figure out the feasible
Generally, temperature defines thermal comfort in indoor distribution of energy for the higher comfort level possible.
building environment, whereas other factors are supposed to Besides optimization the studies consider individual comfort
be subjective for simplification of the control system. Auxiliary parameters such as mostly thermal and visual, while air quality
cooling and heating system is employed to maintain the temper- is considered in combination of the two others. However, the
ature inside the building environment. Relative humidity is a ris- thermal loading is increased in tropical climatic regions where
ing concern inside the buildings of tropical climate areas, due to heavy rainfall, in this context relative humidity parameter
very hot and humid environment. Thus, relative humidity factor within the buildings is significant for various health issues.
indicates humidity comfort inside the buildings. Auxiliary dehu- Therefore, the system should be capable to accommodate the
midifiers and humidifiers are employed to maintain the relative varying user preferences. Therefore, the intended building con-
humidity in indoor building environment. Illumination level trol systems may take both maximizing the comfort level (ther-
describes the visual comfort and artificial lighting systems are mal, relative humidity, visual, air quality) and minimizing the
used with actuators for illumination controls. CO2 concentra- energy consumption as objective. This should also provide
tion is used as an index to measure the air quality comfort and multiple optimized trade-off solutions to users for their specific
ventilation system is employed for attaining low CO2 concentra- choices. This is considered as multi-faceted problem, in which
tions (Hussin et al., 2014). The prime objective of the control of the objective functions to be optimized generally are in conflict
building energy management system (BEMS) was to maintain with each other.
high comfort index and reduce total energy consumption. This study is the advancement of our previous works as in
Various conventional on/off and proportional integral Shaikh et al. (2014b) and Shaikh et al. (2016). The major con-
derivative (PID) control schemes have widely been applied in tribution of this study is an added comfort parameter of relative
buildings (Mathews et al., 2000). These have shown unsatisfac- humidity. Therefore, in this study, a multi-agent coordinator
tory performance at instants when, system peak demand system has been developed for energy consumption and envi-
occurs, prompt overshoot of set point and enormous time- ronmental comfort management. The system aids in developing
delays with nonlinearity been observed (Li et al., 2006). Several the energy consumption of the actuator system. In addition to
artificial intelligent techniques have been anticipated including this, an evolutionary multi-objective genetic algorithm
fuzzy logic systems (FLCs) (Kukolj et al., 2001; Kolokotsa, (MOGA) has been employed for attaining trade-off between
2003), neural networks (Curtis et al., 1996), neuro-fuzzy sys- energy consumption and comfort. The significant contributions
tems (Chen et al., 2006) which have been intensive on specific of this manuscript are the addition of humidity comfort param-
types of buildings. The pervasive monitoring of human atti- eter along with its model function. This parameter of humidity
tude has been addressed in Liu et al. (2010). Multi-agent con- comfort has been integrated with other three parameters of
trol scheme has been proposed to manage energy consumption thermal, visual and air quality comfort. Implementation of
and comfort employing particle swarm optimization (PSO) multi-objective genetic algorithm has not been employed in this
(Yang and Wang, 2013). It also uses graphical user interface kind of study and the modification of the comfort function as
(GUI) for occupants in order to manage building operations an additional parameter has been integrated. The remainder
(Wang et al., 2010). The model predictive optimization with of the paper is organized as follows: Section 2 describes the
linear programming method has been employed in overall system model and framework, and Section 3, in detail
Dagdougui et al. (2012) using LINDO system tool. Moreover, the algorithm for multi-objective optimization problem. Simu-
the detail review on control systems and the optimizations in lation results and analysis are given in Section 4, whereas Sec-
buildings have been presented in Shaikh et al. (2014a). tion 5 presents the conclusion and future works.
Nonetheless, multi-objective optimization techniques have
been proposed (Nguyen et al., 2014) to instantaneously deal
with multi-modal problems generally in conflict with each 2. System framework and modeling
other. The evolutionary algorithms turned to be the most
popular and widely used optimization method for resolving The multi-agent coordinator system comprises of the master
multi-objective problems. Genetic algorithm (GA) being the coordinator agent and peripheral coordinator agents for each

Please cite this article in press as: Shaikh, P.H. et al., Intelligent multi-objective optimization for building energy and comfort management. Journal of King Saud
University Engineering Sciences (2016), http://dx.doi.org/10.1016/j.jksues.2016.03.001
Intelligent multi-objective optimization for building energy and comfort management 3

comfort parameter. The master agent coordinator is capable of The management of building energy and comfort is through
coordinating all peripheral coordinating agents. It allows the distributing the entire system into various subordinate systems.
occupants preferences and coordinates with the optimization Primarily four comfort parameters have been considered,
algorithm in order to maximize the user set value as quick as include thermal, visual, air quality and humidity. These com-
possible. The evolutionary optimization method uses the net- fort indexes have been corresponding to temperature for ther-
work knowledge and permits consumer to state the required mal comfort, artificial illumination for visual comfort, CO2
comfort range to tune and update the best set points in each concentrations in air for air quality comfort and relative
step. Its function is to optimize and update the set point values humidity for humidity comfort respectively. Moreover, the
of master and peripheral coordinator agent, thus, adding intel- actuator systems that drive the comfortable environment con-
ligence to the system. The main aim was that, when the periph- stitutes of auxiliary heating and cooling system for thermal
eral coordinator agent cannot reach the required target, the comfort, electrical lighting system for visual comfort, auto-
master coordinator agent will offer more power for attaining mated window and fan operations to maintain CO2 concentra-
the desired set value as soon as possible. The entire optimiza- tions for air quality comfort and dehumidifier/humidifier
tion system framework has been shown in Fig. 1. systems for humidity comfort.
The users can set their different comfort range based on The fuzzy controllers are utilized to compute the power
their preferences, which is represented as, [Cmin, Cmax], where, demand by each environmental parameter to maintain a high
C denotes the required comfort parameter. In this study, the comfort level with the control of corresponding actuators.
parameters selected are thermal, relative humidity, visual and The implication of the fuzzy controllers helps to overcome
air quality comfort. The users are allowed to set their specific the nonlinear problems in the control process. The inputs to
requirement of the comfort value. This signifies the optimizer the fuzzy inference system (FIS) of each parameter are random
to achieve the targeted comfort in contrast to its best capabil- data set processed within the standard ASHARE (ASHARE
ities ensuring all the indoor and outdoor information satisfying Standard, 1992) comfortable range. The range has been pro-
their needs. vided with the set of intervals as proposed in the base quality

Figure 1 Optimization system framework.

Please cite this article in press as: Shaikh, P.H. et al., Intelligent multi-objective optimization for building energy and comfort management. Journal of King Saud
University Engineering Sciences (2016), http://dx.doi.org/10.1016/j.jksues.2016.03.001
4 P.H. Shaikh et al.

assurances plan (Mark, 1996) for sensor measurement accu- ator system to maintain the required comfort level. However,
racy. These set of inputs has been supplied to the FIS system fuzzy rule base and membership function help to compute
of each comfort parameter, which gives an output in terms the required power during indefinite circumstances. In this
of power demand. Since all the parameters have been pro- proposed system, it is primarily supposed that the building
cessed in form of error values it transforms into a unit-less sys- indoor environment is very sensitive to the outdoor environ-
tem with common output power demand. Therefore, the mental variations. Therefore, the building indoor environment
inputs and outputs of the FIS system have been treated with is closely following the change of outdoor environmental con-
the statistical curve to fit empirical model development. The ditions, if no optimal system is applied. In that case, the ambi-
empirical models for each comfort parameter are capable of ent environmental parameters can serve as the input signals for
closely intimating the behavior of the developed FIS system. the building control system. Besides, building optimization
The FIS system characteristic membership functions and rule system it also considers the inhabitants preferences for the
bases have been discussed in detail in our previous work attaining the user centered design.
(Shaikh et al. (2013a,b)). Moreover, the FIS provides empirical
Comfort 1  DiscomfortN 1
model functions as shown in Eqs. ((6)(9)) having been
observed through the fuzzy inference system. The developed Broadly, when dealing with each comfort parameter into a
functions for the power requirement of multi-agent coordina- single function the weighting factor needs to be added and can
tor of each comfort parameter are determined as follows. be written mathematically as follows:
The four control variables of temperature, relative humidity, X
n
CO2 concentration and illumination are provided through sen- Overall comfort wi  comfort 2
sors as inputs to compute the desired power. i1

Meanwhile, all the power demand empirical models have where wi is the weighting coefficient and for comforti is the
been added together that constitute of four variables (that each factor. Furthermore, in Eq. (2) expressively for each com-
are four comfort parameters). On the other hand, comfort fort parameter of thermal, relative humidity, visual and air
model function has been utilized from the literature (Wang quality comfort it can be written in the form as follows:
et al., 2011) and has been modified with an additional relative "  2 # "  2 #
humidity comfort factor constituted in the range of [0, 1]. This eThermal eRHr
is due to the subjectivity of the comfort index; therefore, con- Comfort w1 1  w2 1 
Tempset RHrset
sider 0 being the lowest comfort level and 1 being the highest. "  2 # "  2 # 3
As comfort for each individual varies, so, it is measured in eLux eCO2
w3 1  w4 1 
terms of dwellers percentage satisfaction; defined in terms of Luxset AQset
discomfort, utilizing the error between the measured sensor
values and the user set points. The prime control goal is to maximize comfort under vari-
The two objective functions power demand and overall able operating conditions. w1, w2, w3 and w4 are the user defined
comfort constitute of four similar variables to be dealt with weighting coefficients of importance provided for each comfort
the multi-objective optimization techniques. Since the opti- parameter. These weighting coefficients are in the range of [0, 1]
mization has to be simplified in form of either minimization and generally expressed as w1 w2 w3 w4 1. On the other
or maximization, indeed power demand needs to be minimized hand, Tempset, RHrset Luxset and AQset are the set points of
whereas, overall comfort has to be maximized. Here as the temperature, relative humidity, illumination and indoor air
overall comfort is subjective represented in percentage there- quality respectively. The user preferences and adaptive rules,
fore the function has been transformed to minimize the overall which reflect the human behavior pattern to determine four
discomfort, simply by subtracting the overall comfort from the set points. nThermal ; nHumidity ; nLux , and nCO2 are the differences
highest possible comfort level. Therefore, for the objective between the measured sensor values and set point values of
functions of overall comfort and energy consumption of the the each comfort demand factors. The weighting coefficients
targeted comfort parameters are set as the vectors of four deci- and set points of environmental parameters are defined by
sion variables. the users based on the occupants preferences. On the other
The demanded power in the building, allows the actuator hand, the measured values of the environmental parameters
system of each comfort parameter to cause variation in the are obtained from the peripheral agents for computing the
indoor environmental parameter of the building. The key goal differences.
of the entire automation process is to achieve the required The power requirement function will be computed at the
comfort index in the building. The level sensor sub-systems will local control level, but as the demand rises by the individual
give feedback to the environmental variation for calculating agents, the power demand function will supply accordingly
the input error to the fuzzy system. This feeds back the power as described in the following pattern;
demand to the master coordinator agent determining further
PTemp t PRHr t PLux t PAQ t Pin t 4
adjustment of power demand. In relation to this, when the dif-
ference between set point and sensor value decreases, the
Pin t 6 Pmax t 5
power demand by the actuator system decreases and ulti-
mately, the comfort value increases. Consequently, the selec- The Pin is the actual power supplied from the utility electric
tion of comfort set points has impact on both the energy grid and Pmax is the maximum power that can be supplied by
consumption and the comfort level. the electric grid.
These coordinator agents acquire adjusted set points from The peripheral controller agents were developed to control
the master agent controller and real time indoor environmental thermal, humidity, visual and air quality comfort factors. The
parameter. It provides the actual power demand for the actu- fuzzy controllers were utilized to calculate the power demand

Please cite this article in press as: Shaikh, P.H. et al., Intelligent multi-objective optimization for building energy and comfort management. Journal of King Saud
University Engineering Sciences (2016), http://dx.doi.org/10.1016/j.jksues.2016.03.001
Intelligent multi-objective optimization for building energy and comfort management 5

by each environmental parameter for maintaining high com- requiring the optimization of n objectives may be formu-
fort level with the control of corresponding actuators. The gen- lated as follows: General MO problem can be mathematically
eralized functions were developed for the power required by represented in Eqs. (10)(12);
each subsystem. This power function has been compared to 2 3
f1 x
the power determined by the supervisory agent to adjust the 6 f x 7
real amount of power used. The actuator systems then drive 6 1 7
6 7
the auxiliary heating/cooling system, electrical lighting system 6 : 7
MOP min Fx 6 6 7nP2 10
7
and air-quality system for all environmental parameters. x2C
6 : 7
The temperature index is utilized to evaluate the thermal 6 7
4 : 5
comfort in the building environment; thus, a linear best fit
fn x
stochastic empirical model is derived with 98% confidence fit
interval. Subject to,
PTemp 5:655  TTemp 2:961 6 C fx : hx 0; gx 6 0; a 6 x 6 bg 11
where PTemp is power required for the temperature control
where; x x1 ; x2 ; x3 ; . . . ; xp T X Parameter Space 12
actuator and TTemp is the temperature control difference input

value. A point x 2 C is Pareto Optimal (or non-dominated) for
The per unit relative humidity is used to evaluate humidity multi-objective optimization problem (MOP) if and only if
comfort in the building environment; thus, a Gaussian model there is no x 2 C such that fi x 6 fi x for all
best fit stochastic model is derived with 98% confidence fit i 2 1; 2; 3; . . . ; n with at least one strict inequality.
interval. F(x) is the objective vector, the C represent the con-
straints and x is a P-dimensional vector representing the
PRHr 13:23  e 0:6572
RHr0:9594 2
7 decision variables within a parameter space X. The space
PRHr is power required for the temperature control actuator spanned by the objective vectors is called the objective space.
and RHr is the relative humidity control difference input value. The subspace of the objective vectors, which fulfills, the con-
The lux metric is used to evaluate the illumination level of straints, has been called the feasible space.
the building environment; thus, the sum of sine model is best A genetic algorithm (GA) is a population based stochastic
fitted and shows 99% confidence level fit. approach and is suitable for multi-objective problems. GA is
capable to stochastically search various regions, instanta-
PLux 4:428  Sin0:9603  ILux  0:4234 8 neously in a solution space and discover trade-off solutions
PL is power required for the lighting control actuator and IL is for different problems with discontinuous, non-convex and
the lux control difference input value. On the other hand, the multi-modal solution space. The GA is capable of intuitive-
CO2 concentration is used to evaluate the air quality index ness, easy in implementation, and solves nonlinear problems
measured in ppm in building indoor environment; thus, the and mixed integer optimizations. It simply works with objec-
Gaussian model is best fitted and shows 99% confidence level tive functions rather than the requisite of derivative and other
fit. auxiliary information. It parallel searches in population and
 WAQ 11632 implements probabilistic rules, which proceed toward opti-
PAQ 9:444  e  389 9 mum solutions using genetic operators and converge to high
quality solutions within the few generations with minimized
PAQ is power required for the air quality control actuator and computational costs (Horn et al., 1994). In order to generate
WAQ is the CO2 concentration control difference input value. fresh non-dominated solutions in unmapped Pareto front mea-
sures, the GA crossover operator uses creditable solutions with
3. Multi-objective optimization (MO) algorithm regard to various objectives. Adding to this, MOGA does not
necessitate scale, order or weigh objectives, thus being the most
Multi-objective optimization tries to improve vector-valued popular heuristic approach for multi-objective design and
cost function components generally in conflict with each other problems (Horn et al., 1994). Fig. 2 below shows the pseudo
(Nguyen et al., 2014). The aim of multiple objective optimiza- code that depicts the working of MOGA.
tions was to find the solution set diversity, decisive with trad-
ing off among various objective functions. Multi-objective 4. Results and discussion
optimization has been applied in various fields of electrical
engineering problems and yet at initial stages developing inter- In this section, a case study has been presented. The building is
ests of researchers, where optimal decisions required for the assumed to be in the islanded mode and has been supplied dis-
presence of trade-offs between two or more contradictory tributed renewable energy sources. Here, six 4.5-kW solar pan-
objective functions. Moreover, the Pareto optimal solution els and equally 5-kW wind turbine generators are used (green
set points will be generated in contrast to single solution as energy ohio, 2013). The total amount of power being generated
in single objective optimization. The solution is known as with these renewables is shown in Fig. 7 on a 24-h time
non-dominated, non-inferior Pareto efficient, mean if no domain. The storage bank constitutes batteries of 45 kWh,
objective function can be improved without degrading the with minimum storage threshold of 4.5 kWh have been
other objective function. Therefore, MO usually looks for selected for distributed energy storage. In most of the entire
trade-offs, rather than single solutions when dealing with day, the distributed energies are not capable to fulfill the com-
multi-objective optimization problems. The MO problem plete power demand of the building. In this regard, the

Please cite this article in press as: Shaikh, P.H. et al., Intelligent multi-objective optimization for building energy and comfort management. Journal of King Saud
University Engineering Sciences (2016), http://dx.doi.org/10.1016/j.jksues.2016.03.001
6 P.H. Shaikh et al.

Lset = 800 lux and AQset = 800 ppm and equal weighting
coefficient for each comfort parameter has been set as one-
fourth (1/4).
Begin
t=0 The MATLAB simulation platform has been used for the
Initialize population of chromosomes P(g);
,
building energy and comfort management. The optimization
Evaluate the initialized population by computing its fitness measure
, ,,
tool box has been used for the MOGA algorithm for the gen-
P(g); ,

eration of Pareto front trade off solution set. The initial set
Whilenot termination criteriado
, ,

parameters for the GA has been selected as the following:


g:=g+1;
Select P(g+1) from P(g); number of variables are four as the comfort parameters repre-
Crossover P(g+1);
, ,
senting temperature, relative humidity, illumination level and
Mutate P(g+1);
, , CO2 concentration. Constraints provided in the simulation
Evaluate P(g+1); were Lower bound [67 0.40 750 400] and upper bound
End While [78 0.60 880 850] representing the respective comfort parameter.
Output results to external archive
End
GA parameters use the following; population was selected as
500, selection function employs tournament method, crossover
rate was set at 0.8, mutation rate was selected default of con-
straint dependent, migration was in forward direction with
Figure 2 Pseudo code for multi-objective genetic algorithm
the fraction of 0.2 and an interval of 20 has been kept. On
(MOGA).
the other hand, the multi-objective problem settings use
default distance crowding for the function of distance measure
and the Pareto front population fraction was selected as 0.35.
However, the simulation stopping criteria were having the
stochastic optimized, control system distributes the available default settings; comprising of generations: 200 * number of
power, sensibly and maximizes the overall comfort index inside variables, time and fitness limit was set infinite, stall genera-
the building. tions use default value of 100 and the fault tolerance was set
In the simulation, the occupants comfort ranges for the at 1e-4. The simulation output describes problem type as
various control tasks are set at Temp = [67, 78] (F), RHr = bound constrained and generates 175 points on the Pareto
[0.40, 0.60] (p.u), Lux = [750, 880] (lux) and AQ = [400, 880] front. The average distance measure of solutions on the Pareto
(ppm). These comfort ranges, sever as the bound constraints front has been observed at 0.0063. The spread measure of the
in the stochastic MOGA to drive out the optimal set points Pareto Front was 0.5049 and the number of generations was
tuning in each time step. The set points targeted for each com- 125. On the other hand, the function counts were observed
fort parameter are set at Tset = 71.6 F, RHrset = 0.5 p.u, as 62,401 and the final message was displayed as optimization

75
Tact
Topt

70
Temperature (F)

65

60

55

50
2 4 6 8 10 12 14 16 18 20 22 24

Time (Hours)

Figure 3 Temperature set points with and without MOGA.

Please cite this article in press as: Shaikh, P.H. et al., Intelligent multi-objective optimization for building energy and comfort management. Journal of King Saud
University Engineering Sciences (2016), http://dx.doi.org/10.1016/j.jksues.2016.03.001
Intelligent multi-objective optimization for building energy and comfort management 7

100
Hact
90 Hopt

80

70

Humidity (%)
60

50

40

30

20

10

0
2 4 6 8 10 12 14 16 18 20 22 24
Time (Hours)

Figure 4 Relative humidity set points with and without MOGA.

1800

Lact

1600 Lopt

1400

1200
Illumination (lux)

1000

800

600

400

200

0
2 4 6 8 10 12 14 16 18 20 22 24
Time (Hours)

Figure 5 Illumination set points with and without MOGA.

terminated: average change in the spread of Pareto solutions overall actual and optimized comfort index has been shown
less than options.TolFun. in Fig. 8. On an average the overall actual comfort 87.25%,
The optimized indoor environmental set point variations whereas, the optimized comfort after MOGA has been
over a day of 24 h are shown. On the other hand, the optimized improved to 99.73%. In spite of energy shortage from the
temperature, humidity, illumination and air quality set point renewable energy generation, the intelligent optimized system
variations are shown in Figs. 36 respectively. However, the has distributed the energy appropriately for attaining the
overall power consumption has been shown in Fig. 7. The improved indoor comfort level. These results make evident
overall power consumption is 654.082 kWh, whereas the total that the system can be optimized by regulating the comfort
power been generated with the distributed renewable is ranges and along with this, it also proves the effectiveness of
971.803 kWh, showing significant amount energy saving. The multi-agent coordinator system and MOGA optimizer.

Please cite this article in press as: Shaikh, P.H. et al., Intelligent multi-objective optimization for building energy and comfort management. Journal of King Saud
University Engineering Sciences (2016), http://dx.doi.org/10.1016/j.jksues.2016.03.001
8 P.H. Shaikh et al.

1800

AQact

1600 AQopt

1400

1200
CO2 Concentration (ppm)

1000

800

600

400

200

0
2 4 6 8 10 12 14 16 18 20 22 24

Time (Hours)

Figure 6 Air quality set points with and without MOGA.

60
Psupp
Preq
55

50

45
Power (KW)

40

35

30

25

20

15
2 4 6 8 10 12 14 16 18 20 22 24
Time (Hours)

Figure 7 Overall power consumption with MOGA.

Please cite this article in press as: Shaikh, P.H. et al., Intelligent multi-objective optimization for building energy and comfort management. Journal of King Saud
University Engineering Sciences (2016), http://dx.doi.org/10.1016/j.jksues.2016.03.001
Intelligent multi-objective optimization for building energy and comfort management 9

1.1
Copt

Cact
1.05

0.95

0.9
Comfort

0.85

0.8

0.75

0.7

0.65

0.6
2 4 6 8 10 12 14 16 18 20 22 24
Time (Hours)

Figure 8 Overall comfort level with MOGA.

5. Conclusion References

The major challenge of building automation system is to bal- ASHARE Standard, ANSI/ASHRAE Standard 55, 1992. Thermal
Environmental Conditions for Human Occupancy. American
ance the conflict between the occupants comfort and the total
Society of Heating, Refrigerating and Air-Conditioning Engineers.
energy consumption. Thus, in this paper, the multi-agent con- Inc., Atlanta.
trol system technology has been developed for the optimized Chen, K., Jiao, Y., Lee, E.S., 2006. Fuzzy adaptive networks in
and intelligent control of the building indoor environment. thermal comfort. Appl. Math. Lett. 19, 420426.
Thus, it is more concerned about occupants preferences and Costa, A., Keane, M.M., Torrens, J.I., Corry, E., 2013. Building
attaining their desired comfort. The multi-agent system has operation and energy performance: monitoring, analysis and
presented its capability in controlling a convoluted building optimization toolkit. Appl. Energy 101, 310316.
system. The designed control system considers both energy Curtis, P.S., Shavit, G., Kreider, K., 1996. Neural networks applied to
efficiency in terms of power supply and consumption of entire buildings a tutorial and case studies in prediction and adaptive
system balanced while maintaining occupants comfort. More- control. ASHRAE Trans. 1, 102.
Dagdougui, H., Minciardi, R., Ouammi, A., Robba, M., Sacile, R.,
over, the users preferences are also taken into consideration
2012. Modeling and optimization of a hybrid system for the energy
for maintaining the required comfort level. In spite of total supply of a Green building. Energy Convers. Manage. 64, 351363.
energy supply of renewable resources, MOGA has shown to Green Energy Ohio, 2013. Accessed October 05 from, <www.greenen-
be advantageous for maintaining high comfort level. This will ergyohio.org>.
make the occupants more informed prior to make their deci- Horn, J., Nafpliotis, N., Goldberg, D.E., 1994. A niched Pareto
sion. Furthermore, other optimization techniques will be genetic algorithm for multiobjective optimization. In: Proceedings
employed for evaluation of added intelligence in future work. of the First IEEE Conference on Evolutionary Computation. IEEE
World Congress on Computational Intelligence, pp. 2729.
Hussin, M., Ismail, M.R., Ahmad, M.S., 2014. Air-conditioned
Acknowledgments
university laboratories: comparing CO2 measurement for central-
ized and split-unit systems. J. King Saud Univ. Eng. http://dx.doi.
The authors are thankful to the Universiti Teknologi Petronas, org/10.1016/j.jksues.2014.08.005.
Malaysia for the financial support and motivation to conduct International Energy Agency, 2007. International organization for
research. They would also thank to Mehran University of standardization (IEAISO), international standards to develop and
Engineering and Technology, Jamshoro, Pakistan for allowing promote energy efficiency and renewable energy sources, special
to accomplish higher studies smoothly. ISO focus. In: Proceedings of the World Energy Congress, pp. 510.

Please cite this article in press as: Shaikh, P.H. et al., Intelligent multi-objective optimization for building energy and comfort management. Journal of King Saud
University Engineering Sciences (2016), http://dx.doi.org/10.1016/j.jksues.2016.03.001
10 P.H. Shaikh et al.

Kolokotsa, D., 2003. Comparison of the performance of fuzzy and comfort management of buildings. Aust. J. Basic Appl. Sci. 7,
controllers for the management of the indoor environment. Build. 137144.
Environ. 38, 14391450. Shaikh, P.H., Nor, N.B.M., Nallagownden, P., Elamvazuthi, I., 2013b.
Kukolj, D.D., Kuzmanovic, S.B., Levi, E., 2001. Design of a PID-like Building energy management through a distributed fuzzy inference
compound fuzzy logic controller. Eng. Appl. Artif. Intell. 14, 785 system. Int. J. Eng. Technol. 4, 32363242.
803. Shaikh, P.H., Nor, N.B.M., Nallagownden, P., Elamvazuthi, I.,
Li, Y., Ang, K.H., Chong, G.C.Y., 2006. PID control system analysis Ibrahim, T., 2014a. A review on optimized control system for
and design problems, remedies, and future directions. IEEE building energy and comfort management of smart sustainable
Control Syst. Mag. 26, 3241. buildings. Renewable Sustainable Energy Rev. 34, 409429.
Liu, K., Nakata, K., Harty, C., 2010. Pervasive informatics: theory, Shaikh, P.H., Nor, N.B.M., Nallagownden, P., Elamvazuthi, I., 2014b.
practice and future directions. Intell. Build. Int. 2, 519. Stochastic optimized intelligent controller for smart energy efficient
Mark, A.C., 1996. BASE quality assurance project plan, environmen- buildings. Sustainable Cities Soc. 13, 4145.
tal health and engineering, 60 Wells Avenue Newton, MA 02159- Shaikh, P.H., Nor, N.B.M., Nallagownden, P., Elamvazuthi, I., 2016.
3210 (MS report). In: Womble, Susan (Ed.), Office of Radiation Intelligent multi-objective control and management for smart
and Indoor Air United States Environmental Protection Agency, energy efficient buildings. Int. J. Electr. Power Energy Syst. 74,
pp. 2432, Washington, DC 20460. 403409.
Mathews, E.H., Arndt, D.C., Piani, C.B., Heerden, E., 2000. Devel- Wang, Z., Yang, R., Wang, L., 2010. Multi-agent control system with
oping cost efficient control strategies to ensure optimal energy use intelligent optimization for smart and energy efficient building. In:
and sufficient indoor comfort. Appl. Energy 66, 135159. Proceedings: IEEE Industrial Electronics Society, Phoenix, AZ, pp.
Nguyen, A.T., Reiter, S., Rigo, P., 2014. A review on simulation-based 11441149.
optimization methods applied to building performance analysis. Wang, Z., Yang, R., Wang, L., 2011. Intelligent multi-agent control
Appl. Energy 113, 10431058. for integrated building and micro-grid system. In: Proceedings:
Safdar, A., Dohyeun, K., 2013. Energy conservation and comfort IEEE PES Innovative Smart Grid Technologies Anaheim, CA, pp.
management in building environment. Int. J. Innovative Comput. 17.
Inf. Control 9, 22292244. Yang, R., Wang, L., 2013. Multi-zone building energy management
Shaikh, P.H., Nor, N.B.M., Nallagownden, P., Elamvazuthi, I., using intelligent control and optimization. Sustainable Cities Soc.