Air System Sizing Summary for CORRIDOR 4

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:55AM

Air System Information


Air System Name .................................... CORRIDOR 4 Number of zones ............................................................. 1
Equipment Class ......................................... SPLT AHU Floor Area ................................................................. 626.0 m
Air System Type ................................................ SZCAV Location .................................................... Masqat, Oman

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s .......................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 106.6 kW Load occurs at ..................................................... Jul 1600
Sensible coil load ................................................... 92.0 kW OA DB / WB ...................................................... 45.8 / 30.0 C
Coil L/s at Jul 1600 ................................................ 6958 L/s Entering DB / WB ............................................. 24.5 / 17.5 C
Max block L/s ........................................................ 6958 L/s Leaving DB / WB .............................................. 13.5 / 12.8 C
Sum of peak zone L/s ........................................... 6958 L/s Coil ADP ..................................................................... 12.3 C
Sensible heat ratio ............................................... 0.863 Bypass Factor .......................................................... 0.100
m/kW ....................................................................... 5.9 Resulting RH ................................................................. 60 %
W/m ..................................................................... 170.3 Design supply temp. ................................................... 12.5 C
Water flow @ 5.6 K rise ......................................... N/A Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 K

Supply Fan Sizing Data

Actual max L/s ....................................................... 6958 L/s Fan motor BHP ........................................................... 0.86 BHP
Standard L/s .......................................................... 6946 L/s Fan motor kW ............................................................. 0.64 kW
Actual max L/(s-m) .............................................. 11.12 L/(s-m) Fan static ....................................................................... 50 Pa

Outdoor Ventilation Air Data


Design airflow L/s ........................................................ 0 L/s L/s/person ................................................................... 0.00 L/s/person
L/(s-m) ................................................................... 0.00 L/(s-m)

Hourly Analysis Program v4.50 Page 1 of 1