HYDRO-GUARD
HG-1
table of contents PAGE
Installation Instructions 2
Automatic
Programming Unit 3-6
Flushing
Troubleshooting
Options 9
8
System Parts 10
Notes 11
! WARNING:
Failure to read and follow the instructions contained within this manual
could result in serious personal injury, and/or damage to the Hydro-Guard
Automatic Flushing Device.
1. Each person involved in the assembly, installation and/or maintenance
of the Hydro-Guard Automatic Flushing Device must read this manual
carefully and follow all instructions prior to performing any installation or
maintenance procedures involving the Unit.
2. Verify the drainage path prior to installation to ensure that pedestrian
and vehicular hazards will not be created by the installation and use of the
Hydro-Guard Automatic Flushing Device (In areas in which freezing may
occur, special attention should be given to this procedure).
3. Never assemble, disassemble, or perform Hydro-Guard maintenance
unless the influent supply valve has been closed, verified and secured, Reliable Connections
TM
Installation Instructions
General
Overview Please read and retain this manual. drainage patterns for the intended
The Hydro-Guard HG-1 Automatic It will be helpful for future reference, installation location should be
Flushing System, the industrys training, troubleshooting, and reviewed. The drainage pattern must
premium patented, programmable maintenance. permit discharged water to flow
flushing apparatus, is suitable for away from the Hydro-Guard Unit in
year-round use in warm climates. Site Evaluation the case of a backflow situation. In
This Automatic Flushing System has Each Hydro-Guard installation is cold-weather applications, multiple
been designed, engineered, and unique and will require a minimum nightly flushes are effective in
manufactured to provide outstanding of advance planning. Prior to managing discharge volumes and
dependability and performance. the installation of the device, the preventing the accumulation of ice.
2
hydro-guard HG-1 Flushing System
Programming Unit
Discharged water flushed from Rechargeable battery (low battery TBOS-II Handheld Home
the Hydro-Guard Unit should be indicator shows both handheld and Screen Menu
routed away from the device into the controller battery conditions) with 1. TBOS infra-red accessible only
surrounding environment. Proper recharging adaptor (9-volt lithium when connected to programming
preparation of the area around the battery can be used in the built-in interface via the IR cable:
device is essential. Use of sod or programming interface) select to connect handheld to
rock is recommended (See typical programming interface via infrared
NOTE: In that the handheld was
installation illustration on page 2). cable and access programs
designed by its manufacturer to
program flush systems, many on it, or to transfer programs
Technical Data
displays use flush terminology. from handheld to programming
Operating temperature range of interface.
32 to 120 F In the following instructions,
Operating Pressure: 7 to 200psi in such cases the equivalent 2. Templates (TBOS-II) select
flushing terminology is shown in to program handheld without
Note: Where sustained parentheses. connecting to programming
pressures may exceed 120psi interface.
the installation of a pressure ! CAUTION: Leaving the infra-
reducing valve (PRV) is red connector connected to the 3. Settings select to access and
recommended. built-in programming interface set time, date, and various other
can significantly reduce the available user settings.
Battery Life battery life of the 9-volt batteries
Will vary based on number of in the programming interface and First Time Use
cycles per year, operating pressure, the rechargeable battery in the 1. Press HOME key for three
and temperature. We recommend TBOS-II handheld. seconds to turn on handheld.
checking the battery every 6 months, 2. Press RIGHT ARROW key or the
but in many cases, you will get more TBOS-II Handheld Keys OK key to access Settings
life out of them. HOME press three seconds to turn
3. Use DOWN ARROW to select
handheld on.
and set the following:
HG-1 (Requires Handheld) ABC press to choose from three
a) Date and Time
TBOS-II Programming available programs (to store a
program when preprogramming, or b) Contrast of the screen
Instructions
uploading a program to controller). c) Name of the handheld controller
The TBOS-II handheld uses on
LEFT and RIGHT ARROWS (can be assigned to a specific
screen prompts for intuitive
move curser left or right, also go operator)
programming. It will control current
back or forward one screen. d) Language (English, French,
programming interface (T-2: dark
ON and OFF/+ and /UP and Spanish, Italian, Dutch,
gray case), as well as the previous
DOWN ARROWS Used to set Portuguese, Turkish, etc.)
model of programming interface (T-1
flushing events on or off, move
modules programmed by the TBOS-
selector up and down on screen, or
US handheld).
increase or decrease duration and
Features
other values.
1 to 24 possible flushing events OK press to make selection final.
daily, or on selected days weekly,
365-day calendar
Flush duration 1 minute to 12 hours
(1 minute increments)
Preprogram and store up to 3
different schedules
3
hydro-guard HG-1 Flushing System
Programming Unit
Programming Flushing 7. Use LEFT ARROW to navigate 3. From TBOS-II infra-red settings
Schedule back to the program Settings screen select Transmit and
There are two ways to proceed: menu. press OK again. When program to
8. Select Start times, press OK to be transmitted appears, press OK
select TBOS-II infra-red if IR
set. to confirm.
cable is connected to a TBOS-II
programming interface to access, 9. Use ABC to select program to 4. To clear programs A, B, or C: from
change or load programs there, or be set up. TBOS-II infra-red welcome
select Templates (TBOS-II) to screen, use DOWN ARROW
a) Set hours and minutes for
create or change programs stored to select Clear Programs
each start time (up to 8 per
on the handheld to load onto a and press OK, then select type
program) using ON/OFF keys,
programming interface at a later of program to clear and follow
press OK to set each (hours are
time (IR cable not used). prompts.
indicated using 24 hour clock).
NOTE: The home screen for [When exiting this screen, start 5. To check programs A, B, or C:
TBOS-II infra-red shows battery times will automatically sort into from TBOS-II infra-red welcome
condition for programming inter- chronological order.] screen, use DOWN ARROW to
face and ON/OFF state of any select Programs and press OK,
10.Use LEFT ARROW to navigate
current operation in progress. then select what is to be checked
back to the program Settings
1. Press HOME key for three and follow prompts.
menu.
seconds to turn handheld on. a) Use DOWN ARROW to select
Manual Flushing
2. Press RIGHT ARROW key or the Valve Run Times (Flush
Using TBOS-II handheld on the T-2
OK key to access Settings. Duration), press OK to set.
built-in programming interface (dark
3. Use DOWN ARROW to select NOTE: Although six valves may
gray in color).
Templates and press OK. be shown on screen, only Valve
NOTE: Manual start cannot be
1 is used to manage the Hydro-
4. Use DOWN ARROW to select initiated if there is no program in
Guard unit.
Programs and press OK. the programming interface.
b) Use ON/OFF keys to select
5. Use DOWN ARROW to select 1. To start manual flushing from
program A, B and/or C (one or
Watering Days (Days to Flush) TBOS-II infra-red welcome
more can be assigned).
and press OK. screen.
c) Then use ON/OFF keys to
6. Use UP/DOWN ARROWS to a) Use DOWN ARROW to select
set Flush duration (hours and/or
select one of the following: Manual Watering (Manual
minutes) for program just set, use
a) Custom Cycle (Week): use Flush) and press OK,
LEFT/RIGHT ARROW keys to
RIGHT/LEFT ARROWS to move move between hours and minutes b) Select Start Valve (Open
to days of the week, use ON/OFF and + and keys to set times Control Valve) then using ON/OFF
keys to highlight days on which to (1 minute to 12 hours), press OK keys select Valve 1 and press
flush, then press OK to confirm to set. OK,
days when selections are complete. c) Use ON/OFF keys to set the
b) Even Days: to Flush on even Transmitting Time, Date and manual Flush Time (1 minute
dates, press OK to set. Programs to Programming to 12 hours) and press OK to
c) Odd Days: to Flush on odd Interface, Clearing/Checking confirm. Flushing will start after a
dates including 31st, press OK to Programs, Manual Start four (4) second delay.
set. Connect handheld to programming
interface using IR cable. Stop Manual Flush Sequence
d) Odd Days 31: to Flush on odd
dated except 31st, press OK to 1. Reconnect IR cable to built-in
1. To transmit: from home screen,
set. interface, then hold down HOME
use DOWN ARROW to select
key on handheld.
e) Cyclical: to Flush every X TBOS-II infrared and press OK.
days, set X using ON/OFF keys TBOS-II handheld will receive 2. Use RIGHT ARROW to select
(X=1 to 31), press OK to set; then data (settings) from built-in TBOS-II infra-red menu and
set start date dd/mm/yyyy using programming interface. select Manual Watering.
ON/OFF keys, press OK to set. 2. Once data receipt is complete 3. Select Cancel Flush to cease
press RIGHT ARROW to move to the manual flush sequence.
Settings menu.
4
hydro-guard HG-1 Flushing System
Programming Unit
5
hydro-guard HG-1 Flushing System
Programming Unit
6
hydro-guard HG-1 Flushing System
TOOLS NEEDED: HG-A104 Security Wrench, HG-A2023 Security Tool, Philips screwdriver, flat-head screwdriver
Battery Replacement
HG-1 Removable TBOS-II 5. Screw protective cap back into 2. Connect fresh industrial grade
Controller place and hand tighten securely. 9-volt alkaline battery and reinsert it
1. Use HG-A2023 Security Tool to 6. Use Handheld Controller to reset with harness into Programmer (an
unlock and remove protective all programs and assure flushing optional battery harness is provided
Exterior Housing Cover. sequence is correct prior to returning for redundancy and extended battery
the HG-1 Unit to service. life).
2. Unscrew protective cap from gray
Programming Interface located at 7. Reinstall Exterior Housing Cover 3. Screw protective cap back into
top of unit. and restore water supply to unit. place and hand tighten securely.
3. Extract battery harness and 4. Confirm that desired flushing
remove old battery (dispose of HG-1 Built-In Node Controller sequences are correct prior to
battery appropriately). 1. Follow HG-1 Removable TBOS-II returning the HG-1 Unit to service.
4. Connect fresh industrial grade Controller steps 1 3 (left) to access 5. Reinstall Exterior Housing Cover
9-volt lithium or alkaline battery. Re- on-board Programmer. and restore water supply to unit.
insert with harness into Programmer.
7
hydro-guard HG-1 Flushing System
Troubleshooting
If your Hydro-Guard Unit does Run a manual flush and confirm Connection loss from battery box
not activate: the solenoid plunger is kicking out to solenoid.
Possible Causes and pulling back in by listening for The solenoid is loose or there is
a click. debris in the adapter.
Water pressure off or low.
Check to make sure the flow There is a hole in or debris around
Batteries weak or dead.
control knob is open on the the diaphragm.
Connection loss from controller to valve OR Check the pipes for
solenoid. Try this Correction
obstructions OR Check the valve.
Solenoid not working properly. Run a manual flush for 1 minute.
Obstruction in flow of water. The Hydro-Guard Unit will not Change batteries.
Try this Correction shut off: Check connections for corrosion,
Possible Causes breaks, or lack of connection.
Check if curb stop is open.
The solenoid is stuck in the open Check the adapters and solenoid
Change batteries.
position or debris is interfering with for debris Run the electrical
Check connections for corrosion, systems check.
the plunger.
breaks, or lack of connection.
Batteries weak or dead. Refer to valve troubleshooting for
possible corrective measures.
8
hydro-guard HG-1 Flushing System
Options
The following is a brief overview protection, consider the HG-3 and automatically initiate a flush
and introduction to Hydro-Guard design. The HG-3 (18 to 108 bury) event when water quality conditions
Options. can be equipped with an optional warrant.
patented freeze protection system
Low Lead Brass Internal that allows the water in the service The Hydro-Guard S.M.A.R.T.
Components and Piping piping to drain from the piping when flushing system:
Freeze Protection a flush sequence is ceased. Monitors chlorine levels (total or
The Hydro-Guard HG-1 Unit is free).
freeze protected to 18 by virtue of S.M.A.R.T. Monitoring and Flush
Flushes distribution line when
the bury depth of the main 2 valve. Management
residual disinfectant drops below
The HG-1 offers a valve bury depth The Hydro-Guard HG-1 can be acceptable levels.
of approximately 16 with above upgraded to include a S.M.A.R.T.
controller and a variety of water Monitoring of pH, flow, temperature
ground electronics that can be
quality sensors. The S.M.A.R.T. or turbidity available.
powered by a 9-volt Lithium battery
(operational in temperatures as low equipped HG-1 will allow a utility to Two-way real-time communication
as -20 F). For additional freeze remotely monitor, in real-time, the via cellular, wifi, ethernet or
water quality at a specific flush point BlueTooth.
9
hydro-guard HG-1 Flushing System
Parts
Replacement Parts
ID Part # Description
12
2
1 546284 UV Protective Housing
1
HG-123104 Quick Connect/B-QC
2
3
HG-123105 Quick Connect Sanitary Cap
Controller Options
10
12 13
11
or
Built-In Controller
(shown above on
illustration) Removable Controller
HG1ARM2PVC018LPLG PVC
HG1AIN2PVC018LPLG Brass