Professional Documents
Culture Documents
Teja 2014
Teja 2014
AbstractIntegration of renewable energy based Distributed location of DG, the voltage sensitive nodes are identified by
Generation (DG) units provides potential benefits to conventional penetration DG with size 20% of the total feeder load at each
distribution system. In this paper, the analysis of unbalanced node (except at source node). Then the node with least voltage
mesh distribution system (UMDS) has been done with and sensitive index will be selected as best location for the DG
without DG placement in an optimal location. The location of DG placement. After identifying the optimal location, variational
can be determined by using voltage index analysis and the size of algorithm is used to find the optimal DG capacity.
DG can be computed with the help of variational technique
algorithm. The impact of different power factors (unity and 0.9 The voltage index at each node can be calculated by using
lagging) on optimal placement of DG is analyzed. Eqn. (1)
(1)
tn
I. INTRODUCTION
Where Vk is the voltage at kth node.
Presently, the justification for large central power plants is
weakening due to depleting conventional resources, m is the node at which DG is connected.
deregulation trends and increased transmission and
distribution costs etc. Distributed Generations (DG) are tn is the total number of nodes.
offering solutions to many of these new challenges [1]. N A. Algorithm for DG placement and sizing
Acharya, et al [2] presented an analytical expression based on
real power loss sensitivity to calculate optimal DG size and Step 1: Run the base case load flow for UMDS.
location of DG while minimizing power losses in a Step 2: By penetrating the DG of size 20% of the total
distribution network. V.V.S.N.Murty, et al [3] presented feeder load at each node (except at source node); calculate the
modified novel method for optimal placement of DG in voltage index at the respective node.
balanced radial distribution system based on minimization of
both real and reactive power losses. Mohab M. Elnashar, et al Step 3: Select the bus with lowest value of voltage index as
[4] proposed new approach to optimally determine the size the optimal location for placing the DG.
and location of DG in large mesh connected system. SNRaju, Step 4: At optimal location, Vary the DG size in small
et al [5] proposed a method for optimal placement of DG in steps and calculate the total power losses at each step by
unbalanced radial distribution systems. Optimal location is running UMDS load flow.
identified by calculating Voltage index at each node and then
variational technique is used to find the DG size. While most Step 5: Select the DG size at which the total real power
of the work have been done on DG placement in balanced losses are minimum.
distribution systems and very little research has been done on Step 6: Stop.
DG placement and sizing in UMDS. In this paper, the method
proposed in Ref. [5] is extended to analyze the UMDS with III. RESULTS AND DISCUSSIONS
optimal DG placement.
The load flow algorithm developed in Ref. [6] is used to
II. METHODOLOGY FOR DG PLACEMENT IN UMDS solve the load flow analysis of 25 bus UMDS. The entire
analysis has been carried out on 25 bus UMDS [7].
For placement of DG, location and its size are two
important things. Inappropriate location and size of DG may
lead to increase in system losses. To find out the optimal
100
120
140
160
180
200
220
240
260
280
300
320
340
360
380
400
the optimal location, size of the DG can be obtained by
variational technique (Step 4). Variation of total real power DG size (kW for UPF / kVA for LPF)
loss with respect to DG size at bus 13 is shown in Fig. 1 for
unity power factor (UPF) and 0.9 lagging power factor (LPF).
From the Fig. 1, it is observed that the minimum real power with DG at UPF with DG at LPF
loss is obtained with DG of size 225 kW for UPF and 280
kVA for 0.9 LPF respectively. Fig. 1. Variation of total real power loss with respect to DG size for 25 bus
UMDS at light loading condition
At UPF; by placing the DG of size 225 kW at bus 13, the
total real and reactive power losses are reduced to 34.199 %
and 37.5383 % from its base case. The minimum voltage (p.u) 1.01
is increased to 0.9801, 0.98091 and 0.98205 and the voltage 1
unbalance (%) is reduced to 1.67744, 1.60537 and 1.46927 in
phases A, B and C respectively. With the DG placement in 0.99
Voltage (p.u)
200
230
260
290
320
350
380
410
440
470
500
530
560
590
620
650
680
710
740
and 0.9 LPF. From the Fig. 3, it is observed that the minimum
real power loss is obtained with DG of size 460 kW for UPF DGDG
with sizeat(kW
UPFfor UPF/kVA
with DGfor LPF)
at LPF
and 570 kVA for 0.9 LPF respectively.
Fig. 3. Variation of total real power loss with respect to DG size for 25 bus
At UPF; by placing the DG of size 460 kW at bus 13, the UMDS at normal loading condition
total real and reactive power losses are reduced to 34.9557 %
and 38.4341 % from its base case. The minimum voltage (p.u)
is increased to 0.95952, 0.96129 and 0.96359 and the voltage 1.02
unbalance (%) is reduced to 3.46921, 3.30577 and 3.02184 in 1
phases A, B and C respectively. With the DG placement in
UMDS, the total feeder capacity (in kVA) is reduced by 0.98
Voltage (p.u)
The results for 25 bus UMDS at medium loading condition Fig. 4. Voltage profile for 25 bus UMDS with and without DG at normal
without and with DG are given in Table 2. The voltage profile loading condition
of 25 bus UMDS with and without DG are shown in Fig. 4.
TABLE II. RESULTS FOR 25 BUS UMDS AT NORMAL LOADING CONDITION
Without DG With DG at UPF With DG at 0.9 LPF
A-phase B-phase C-phase A- B-phase C-phase A-phase B-phase C-phase
phase
DG rating 570 570 570
- - - 460 kW 460 kW 460 kW kVA kVA kVA
Location - 13 13
TPL (kW) 47.4217 49.3595 36.3343 30.5718 31.5614 24.4509 22.3059 22.8452 18.4528
Reduction in TPL (%) - - - 35.5321 36.0581 32.7058 52.9628 53.7167 49.2139
TQL (kVAr) 55.2314 50.1738 52.3253 33.7855 30.8204 32.5023 23.1922 21.3127 22.5301
Reduction in TQL (%) - - 38.8293 38.5728 37.884 58.009 57.5222 56.9421
Vmin (p.u) 0.94034 0.94136 0.94843 0.95952 0.96129 0.96359 0.96743 0.96897 0.97181
Voltage unbalance (%) 4.96742 4.82819 4.18344 3.46921 3.30577 3.02184 2.47433 2.39485 2.11971
Total active power
demand (kW) 1120.72 1132.66 1119.63 1103.87 1114.86 1107.75 1095.61 1106.15 1101.75
Total reactive power
demand (kW) 847.231 851.174 852.325 825.785 831.82 832.502 815.192 822.313 822.53
Total feeder capacity
(kVA) 1404.93 1416.83 1407.14 1378.57 1390.99 1385.7 1365.61 1378.32 1374.92
Total released feeder
capacity (kVA) - - - 26.3567 25.8469 21.4359 39.3165 38.5164 32.2151
C. Analysis of UMDS under high loading condition 200
At high loading condition, total real and reactive power
400
430
460
490
520
550
580
610
640
670
700
730
760
790
820
850
880
size at bus 13 is shown in Fig. 5 for UPF and 0.9 LPF. From
the Fig. 5, it is observed that the minimum real power loss is DG size (kW for UPF/kVA for LPF)
obtained with DG of size 600 kW for UPF and 750 kVA for with DG at UPF with DG at LPF
0.9 LPF respectively.
Fig. 5. Variation of total real power loss with respect to DG size for 25 bus
At UPF; by placing the DG of size 600 kW at bus 13, the UMDS at high loading condition
total real and reactive power losses are reduced to 35.446 %
and 38.8797 % from its base case. The minimum voltage (p.u) 1.02
is increased to 0.94661, 0.94904 and 0.9521 and the voltage 1
unbalance (%) is reduced to 4.62673, 4.39713 and 4.01313 in
phases A, B and C respectively. With the DG placement in 0.98
UMDS, the total feeder capacity (in kVA) is reduced by Voltage (p.u) 0.96
46.8706, 45.7969 and 37.7017 in phases A, B and C 0.94
respectively.
0.92
At 0.9 LPF; by placing the DG of size 675 + j326.917 0.9
kVA at bus 13, the total real and reactive power losses are
reduced by 52.979 % and 58.284 % from its base case. The 0.88
minimum voltage (p.u) is increased to 0.95736, 0.95944 and 1 3 5 7 9 11 13 15 17 19 21 23 25
0.96316 and the voltage unbalance (%) is reduced to 3.2528, Bus Number
3.14169 and 2.77821 in phases A, B and C respectively. With Va - without DG
the DG placement in UMDS, the total feeder capacity (in Vb - without DG
Vc - without DG
kVA) is reduced by 69.9812, 68.2654 and 56.8007 in phases Va - with DG at UPF
A, B and C respectively. Vb - with DG at UPF
The results for 25 bus UMDS at high loading condition Fig. 6. Voltage profile for 25 bus UMDS with and without DG at high
without and with DG are given in Table 3. The voltage profile loading condition
of 25 bus UMDS with and without DG are shown in Fig. 6.
TABLE III. RESULTS FOR 25 BUS UMDS AT HIGH LOADING CONDITION
Without DG With DG at UPF With DG at 0.9 LPF
A-phase B-phase C-phase A-phase B-phase C-phase A-phase B-phase C-phase
DG rating (kVAr) - - - 600 kW 600 kW 600 kW 750 kVA 750 kVA 750 kVA
Location - 13 13
TPL (kW) 83.0929 86.1814 63.2692 53.1046 54.6726 42.338 38.385 39.2375 31.7218
Reduction in TPL (%) 36.0901 36.561 33.0827 53.8047 54.471 49.8622
TQL (kVAr) 96.7567 87.7227 90.9322 58.7109 53.4235 56.1981 39.8103 36.54 38.5405
Reduction in TQL (%) 39.3211 39.0995 38.1979 58.8552 58.3461 57.6162
Vmin (p.u) 0.92094 0.92247 0.93193 0.94661 0.94904 0.9521 0.95736 0.95944 0.96316
Voltage unbalance (%) 6.68799 6.48075 5.59495 4.62673 4.39713 4.01313 3.2528 3.14169 2.77821
Total active power
demand (kW) 1478.38 1494.47 1471.56 1448.39 1462.96 1450.63 1433.67 1447.53 1440.01
Total reactive power
demand (kW) 1126.36 1129.02 1130.93 1088.31 1094.72 1096.2 1069.41 1077.84 1078.54
Total feeder capacity
(kVA) 1858.57 1873 1855.93 1811.7 1827.21 1818.23 1788.59 1804.74 1799.13
Total released feeder
capacity (kVA) - - - 46.8706 45.7969 37.7017 69.9812 68.2654 56.8007
IV. CONCLUSIONS [1] Satish Kansal, B. B. R. Sai, Barjeev Tyagi and Vishal Kumar, Optimal
placement of distributed generation in distribution networks
In this paper, an unbalanced meshed distribution system International Journal of Engineering, Science and Technology, Vol. 3,
has been analyzed with and without DG placement at optimal No. 3, pp. 47-55, 2011.
location. Results have been obtained on 25 bus UMDS. The [2] N. Acharya, P. Mahat, and N. Mithulananthan, An analytical approach
for DG allocation in primary distribution network, Electrical Power
effect of different loading conditions (low loading, normal Energy Systems, Vol. 28, Issue 10, pp. 669-678, 2006.
loading and high loading) on DG placement, voltage profile,
[3] V.V.S.N.Murthy and Ashwani Kumar, Comparison of Optimal DG
total power losses and percentage of voltage unbalance are Allocation Methods in Radial Distribution systems based on Sensitivity
analyzed. From the results it can be concluded that, (i) the Approaches, Elect. Power and Ener. Syst., Vol. 53, pp. 450467, 2013.
percentage of real and reactive power loss reduction is more [4] M. M. Elnashar, R. El Shatshat and M.M.A. Salama, Optimum siting
with 0.9 LPF than UPF, (ii) voltage profile is better in case of and sizing of a large distributed generator in a mesh connected system,
DG with 0.9 LPF than UPF. Electric Power Systems Research, Vol. 80, pp. 690-697, 2010.
[5] T. Ramana, V. Ganesh and S. Sivanagaraju, Distributed generator
ACKNOWLEDGMENT placement and sizing in unbalanced radial distribution system
Cogeneration & Distributed Generation Journal, Vol. 25, Issue 1, pp. 52-
This is a part of the work that has been carried out under 71, 2010.
the project sponsored by the Department of Science and [6] J.H. Teng, A direct approach for distribution system load flow
Technology, DST, New Delhi under the project grant: solutions IEEE Transactions on Power Delivery, Vol. 18, No. 3, pp.
SR/S3/EECE/0035/2012, SERB, New Delhi. The authors 882-887, 2003.
acknowledge DST, New Delhi for the grant of the project. [7] G.K.Viswanadha Raju and P. R. Bijwe, Efficient reconfiguration of
balanced and unbalanced distribution systems for loss minimization,
REFERENCES IET Generation, Transmission and Distrbution, Vol. 2, Issue 1, pp. 7-12,
2008.