Applied Energy

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Applied Energy xxx (2017) xxxxxx

Contents lists available at ScienceDirect

Applied Energy
journal homepage: www.elsevier.com/locate/apenergy

Impacts of microgrids with renewables on secondary distribution


networks q
Mustafa Alparslan Zehir a,, Alp Batman a, Mehmet Ali Sonmez a, Aytug Font a, Dimitrios Tsiamitros b,
Dimitris Stimoniaris b, Theofano Kollatou b, Mustafa Bagriyanik a, Aydogan Ozdemir a, Evangelos Dialynas c
a
Department of Electrical Engineering, Istanbul Technical University, Ayazaga Campus 34469, Istanbul, Turkey
b
Department of Electrical Engineering, Western Macedonia University of Applied Sciences, Koila Kozanis 50100, Kozani, Greece
c
Department of Electrical Engineering, National Technical University of Athens, Zografou 15780, Athens, Greece

h i g h l i g h t s

 Low voltage distribution networks are severely affected from high DG penetrations.
 High-resolution and stochastic supply and demand profiles provide valuable insight.
 Determination of DG capacity depending on the worst-case scenarios is limiting.
 The voltage increases and line losses do not reach extreme levels.

a r t i c l e i n f o a b s t r a c t

Article history: High penetration of distributed generation (DG) in secondary (low-voltage) distribution networks (SDN)
Received 25 August 2016 is one of the primary challenges of network operators. Particularly in radial LV networks, renewable
Received in revised form 7 December 2016 intermittency and bidirectional power flow may cause critical problems such as under/over voltages, line
Accepted 27 December 2016
overloads and high energy losses. System operators usually consider the worst-case scenarios for the
Available online xxxx
assessment of the impacts of new integrations and usually they prefer passive methods to mitigate the
negative effects. However, analysis of daily operation with high resolution, stochastic DG supply and res-
Keywords:
idential demand profiles can reveal both the occurrence rates and the severities of the critical events,
Distributed generation
Microgrids
while paving the way for the development of active mitigation methods. This study is focused on detailed
PV systems daily operation analysis of SDNs with renewable-based microgrids. Seasonal DG output and residential
Renewable energy demand profiles throughout a day were simulated using a virtual test bed to investigate the critical cases.
Secondary distribution networks 2016 Elsevier Ltd. All rights reserved.

1. Introduction renewables [9] and limit the penetration of DGs in generation


mix [10,11].
The concept of distributed generation grows in popularity Low voltage (LV) radial distribution networks with high R/X
throughout the world [1]. There are numerous technical, financial ratios are more severely affected by DG penetration than the distri-
and environmental advantages that foster its development [2,3]. bution and transmission networks with higher voltage levels.
Contrarily, high penetration of renewable-based DG into existing While bidirectional power flows in a radial network may cause
power systems can breed new issues. The prominent challenges overvoltage and line overloading problems, they can also increase
are increasing volatility in daily net load profiles (which is named the system losses. In addition to the point of connection, neighbor-
as duck curve) [46], extreme surplus supply from DGs [7] and ing busses are also being affected [8]. Since distribution networks
bidirectional power flows [8]. These stimulate the use of high are not designed for bidirectional power flow, impact analysis is
cost/low efficient peaking plants, cause periodical avoidance of a vital assessment prior to new DG integrations into existing distri-
bution networks.
There are plenty of studies in the literature that concentrate on
q DG impact on LV networks. The studies are focused on the analysis
The short version of the paper was presented at REM2016 on April 1921,
Maldives. This paper is a substantial extension of the short version. of technical challenges [12], evaluation of hosting capacity [13],
Corresponding author. investigation of negative impact mitigation options [14,15] and
E-mail address: zehirm@itu.edu.tr (M.A. Zehir).

http://dx.doi.org/10.1016/j.apenergy.2016.12.138
0306-2619/ 2016 Elsevier Ltd. All rights reserved.

Please cite this article in press as: Zehir MA et al. Impacts of microgrids with renewables on secondary distribution networks. Appl Energy (2017), http://
dx.doi.org/10.1016/j.apenergy.2016.12.138
2 M.A. Zehir et al. / Applied Energy xxx (2017) xxxxxx

sizing of the devices that will be used for mitigation [16]. It is sta- the minimum load on that feeder [37]. Relevant literature lacks
ted in [8,17,18] that the most severely affected bus in a LV distri- of the studies that compare the worst case analysis with high res-
bution system was the furthermost one to the substation, while olution and stochastic daily profile analysis in LV networks. Inves-
the negative impact on the closest bus was very minor. Doumbia tigation of the occurrence rates and magnitudes of extreme
et al. focused on the voltage variation in a small scale network conditions in daily operation can foster the development and eval-
for three critical cases; namely, minimum generation-maximum uation of active mitigation methods and sizing of solutions. What
demand, maximum generation minimum demand and maximum is more, seasonal differences in PV profiles are rarely included in
generation-maximum demand [19]. Conventionally, distribution the related studies, restricting possible variabilities of analysis
network operators consider the most threatening operating condi- results. Additionally, microgrids require particular attention since
tions to scale the capacity of new DG installations. However, deter- local generation and consumption are at the same point of connec-
mination of tolerable DG capacity depending solely on the worst- tion to distribution feeder, with more possibility of hosting higher
case scenarios is very constraining for the utilities [20,21]. Wind penetration of renewables.
turbines generally operate at a level less than their rated capacities, This paper is therefore devoted to detailed daily operation anal-
because of variation in wind speed. The highest output from wind ysis of SDNs including renewable-based microgrids. Note that the
turbines is generally provided in a couple of hours after midnight, analysis is also valid for a SDN where renewable DG and loads
while photovoltaic (PV) panels reach their peaks during midday are located at the same feeder with short distances. Profiles of PV
just for a short period of time [22]. Therefore, peak outputs of wind panels in the microgrid and typical residential loads in a SDN were
generation and photovoltaic generation rarely coincides. Moreover, simulated using a virtual test bed to monitor the changes in bus
recent developments in distributed storage facilities provide more voltage magnitudes and network losses. Steady-state voltage vari-
uniform generating profiles and more effective utilization of ation in radial SDN including microgrids or DG penetration is
renewable generation. Besides, common load factors for buildings explained in section 2. Section 3 describes the virtual test bed used
are approximately 40% [23] which reduces the occurrence possibil- in the study and section 4 includes the detailed daily analysis of a
ity of extreme (minimum generation-maximum loading) sample system. The last section is devoted to the discussion of the
conditions. results and real applications.
Most of the precautions taken according to the worst-case sce-
narios are hard to implement and costly. Reduction of line impe- 2. Steady-state voltage variation and line losses in distribution
dance by reinforcing the distribution feeder or moving networks with renewable-based microgrids
connection point closer to the substation may not be applicable
due to physical and economic conditions in small scale systems Conventionally, secondary distribution networks have been
[8]. Power factor control (PFC) may not be very effective as well, designed for one-way power flow from substation to consumers
particularly in networks with low X/R ratio (compared to active using a radial topology (Fig. 1).
power control) [22]. Advanced control of tap changer at SDN sub- The cross-sectional areas of the LV distribution lines are smaller
station is another prospective solution, since it is an existing con- and their R/X ratios are higher when compared with MV and HV
trol option in many places [24]. However, it may not be effective lines [8]. Therefore, the relative voltage drops are high in these sys-
for local under/over voltage issues at feeders with multiple DGs tems. The substation voltage phasor of a distribution network, V_ s ,
[25]. Therefore, more proactive and effective solutions are can be expressed as in Eq. (1).
required. Additionally, microgrids including renewable based DGs
P  jQ
and improved measurement and control capabilities can be bene- V_ s V_R R jX 1
fited in proactive studies. According to a comprehensive survey V_ 
S
study on DG and microgrids, the primary areas that the microgrids
Here, P and Q denote the active and the reactive powers sup-
will be deployed in the following years are public buildings, hospi-
tals, military facilities and rural areas with LV and MV distribution plied by the utility, respectively. V_R represents the voltage phasor
networks [26]. According to the results of the same study, the key at the receiving end. R and X are the line parameters and the super-
enablers of microgrids are distribution management and energy script denotes the conjugate of a complex quantity. Due to the
management systems which can play significant role in mitigation fact that the angle difference between the substation and con-
of negative impacts of DG penetration. Thus, there is an increasing sumer voltage phasors is very small, the real part of the voltage
need for detailed analysis in which daily supply/demand profiles drop dominates the expression (2).
are considered [27]. Advanced analysis of LV networks with vari- RP XQ
able daily generation and load profiles can provide valuable insight DV V_ s  V_R 2
VS
into long term operation of the system and enable development of
active mitigation methods. In addition, stochastic and quasi-steady The expression can be adopted to represent the voltage relation
state simulations can reveal magnitudes of critical events in daily between each consecutive bus pair of an N bus system (Fig. 2).
operation, contributing to studies on evaluation and sizing of solu- Active line losses for this operational condition can be calcu-
tion options. The works proposed in [2830] include consideration lated using Eq. (3).
of daily PV and load profiles in LV distribution network operation.
However, interruptions in PV panel output due to cloudiness are
not reflected to the PV models. Cloudiness is taken into account
in some studies as in [31], without covering daily profiles. Further-
more, studies with daily profiles mostly use hourly data, neglecting
the minutely changes in PV supply and residential consumption,
which are of importance for the development of corrective power
management methods [3234]. Moreover, most of the studies
use aggregated load profiles, while individual consumption behav-
ior of each consumer can be used to simulate more realistic cases
[3536]. A study of the International Energy Agency (IEA) states Fig. 1. Unidirectional power flow in a traditional radial distribution system with
that, the level of PV penetration on a specific feeder depends on two busses.

Please cite this article in press as: Zehir MA et al. Impacts of microgrids with renewables on secondary distribution networks. Appl Energy (2017), http://
dx.doi.org/10.1016/j.apenergy.2016.12.138
M.A. Zehir et al. / Applied Energy xxx (2017) xxxxxx 3

Fig. 2. Unidirectional power flow in a radial distribution system with multiple busses.

X
N
PLoss Rij  I2ij 3
i1

Iij is the magnitude of the current that flows through the line
between two neighboring busses (i and (j) in a system with mul-
tiple busses.
If a distributed generator or a microgrid with surplus generation
is established at one of the SDN busses, the microgrid connection
bus serves as a sending bus for some neighboring busses (Fig. 3).
Note that the power flow directions determine the receiving and
sending ends for the branches in the network.
The voltage relation can be written as in (4).

PN  jQ N
V_R V_S R jX 4
V_ R

PN PDG  PL 5

Q N Q DG  Q L 6
Fig. 4. The difference between the real data and fitted curve for the PV model.
In Eqs. (5) and (6) the subscripts DG and L denote distributed
generation and load, respectively. It can be stated that the load X
N

profile of a renewable-based microgrid will significantly change PLossnew Rij  I2ijnew 8


i1
the net power exchange (PN and Q N ) in the network. Voltage drop
for reverse power flow conditions can be calculated using (7).
P Lossnew and Iijnew are the new active power losses and branch cur-
RP N XQ N rents following the connection of the microgrid. Depending upon
DV 7
VR the network configuration and net power conditions there is a risk
of increasing the line losses.
In this case, V_R represents the voltage phasor at the bus of the
microgrid. PN and Q N are the net amount of active power and reac-
tive power supplied by the renewable-based microgrid or equiva- 3. Virtual microgrid test bed
lently by the DG. As can be inferred from Eq. (7), the DG or
microgrid bus voltage should be greater than the substation volt- The virtual test bed used in this study was previously developed
age to supply the net amount of power over the line. The amount as a part of Smart Electric Energy Management and Buildings
of voltage difference depends on the net supplied power (P N and Energy Efficiency Technologies (SEEMBEET) bilateral research pro-
Q N ), line parameters (R and X) and substation voltage (V S ). ject conducted by the authors [38]. During its design and testing
In conventional radial distribution system, line cross-sectional stages, field data of a microgrid laboratory were used. The main
areas are generally in descending order from the substation to idea behind the virtual test bed development is to make research
the consumers assuming that the line currents will decrease along beyond the laboratory scale. Experimental small scale systems
the sending-receiving route. Such a configuration decreases the are limited by physical factors, such as single point of connection
installation costs. However, when a microgrid (or equivalently a to the grid, available device number, capacity and dependency on
DG) is connected to the network, it will primarily feed the neigh- local conditions. On the other hand, a virtual system that imitates
boring loads through the gradually thinner distribution lines. This the operation of the real system can be connected to different parts
case will increase the active power losses, as formulated in (8). of a larger system, several scenarios can be implemented to

Fig. 3. Bidirectional power flow in a radial distribution system with DG.

Please cite this article in press as: Zehir MA et al. Impacts of microgrids with renewables on secondary distribution networks. Appl Energy (2017), http://
dx.doi.org/10.1016/j.apenergy.2016.12.138
4 M.A. Zehir et al. / Applied Energy xxx (2017) xxxxxx

simulate different operating conditions, and long term operation Table 1


can be inspected. This section briefly describes the virtual test R/X values for the line types of the sample LVDN.

bed and the purpose of its use in this study. Line type R/X ratio
Model development and simulations were performed using AMKA 3  35 + 50 8.35
PSCAD software [39]. At the first stage, local generation, storage AMKA 3  25 + 30 11.32
and loads were modeled individually, representing their quasi AMKA 3  16 + 25 17.69
steady-state operational behavior. A data set of PV outputs (gener- AXMK 4  50S 7.28
MCMK 3  10 + 10 20.8
ated using the existing PV array block of the software together with MCMK 3  6 + 6 34.22
the developed MPPT and inverter models) for several source input

Fig. 5. Overall structure of the virtual test bed.

AMKA 35 AXMK 50
95 m 571 m B
AMKA 35
60 m
AMKA 35 A MC 6
1 AMKA 35
89 m MC 10 AMKA 16 11 m
38 m
248 m 45 m AMKA 35
137 m
50 kVA
AMKA 35 33 m
Ulity
MC 10
20/0.4 kV
38 m

AMKA 35 AMKA 35 AMKA 25


2
85 m 52 m 58 m

Fig. 6. Sample LVDN with two feeders and 10 consumer nodes.


Power Demand (W)

12000
10000
8000
6000
4000
2000
0
00:42

05:36

16:06
00:00

01:24
02:06
02:48
03:30
04:12
04:54

06:18
07:00
07:42
08:24
09:06
09:48
10:30
11:12
11:54
12:36
13:18
14:00
14:42
15:24

16:48
17:30
18:12
18:54
19:36
20:18
21:00
21:42
22:24
23:06
23:48

Time (hour)
House 1 Demand House 2 Demand House 3 Demand House 4 Demand
House 5 Demand House 6 Demand House 7 Demand House 8 Demand
House 9 Demand House 10 Demand House 11 Demand

Fig. 7. Daily load profiles of 11 houses in spring season case.

Please cite this article in press as: Zehir MA et al. Impacts of microgrids with renewables on secondary distribution networks. Appl Energy (2017), http://
dx.doi.org/10.1016/j.apenergy.2016.12.138
M.A. Zehir et al. / Applied Energy xxx (2017) xxxxxx 5

(solar irradiation and temperature) values was used to model PV of the system are shown in Fig. 4. The maximum difference
generation. It covers the whole operational range of the PV system between the simulated and the actual output powers of PV gener-
and fill factor of the PV panel and is used to derive a first order Eq. ation is about 15 W (1%) at the operational limits of solar irradia-
(9). tion values; i.e. 0 and 1400 W/m2.
The loads in the microgrid laboratory were modeled by modify-
Ppv 8:542173377  0:1719887T 0:170425778Ir 9 ing the existing load block in the software. The modified model can
In Eq. (9), Ppv is the output power in W, while T is the temper- read the values from an external file and reflect the changes in sys-
ature of panels in C and Ir is solar irradiance in W/m2. The R- tem voltage and frequency to its profile. All the models were
squared fitting performance for PV generation is found as 0.9968. equipped with measurement and control devices to monitor
The test data and the fitted curve for the whole operational range supply/demand behavior.

(a) Spring
27000
Power Demand (W)

24000
21000
18000
15000
12000
9000
6000
3000
0
00:00
01:00
02:00
03:00
04:00
05:00
06:00
07:00
08:00
09:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
Time (hour)

(b) Summer
27000
Power Demand (W)

24000
21000
18000
15000
12000
9000
6000
3000
0
00:00
01:00
02:00
03:00
04:00
05:00
06:00
07:00
08:00
09:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
Time (hour)

(c) Autumn
27000
Power Demand (W)

24000
21000
18000
15000
12000
9000
6000
3000
0
00:00
01:00
02:00
03:00
04:00
05:00
06:00
07:00
08:00
09:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00

Time (hour)

(d) Winter
27000
Power Demand (W)

24000
21000
18000
15000
12000
9000
6000
3000
0
00:00
01:00
02:00
03:00
04:00
05:00
06:00
07:00
08:00
09:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00

Time (hour)

Fig. 8. Total daily load profile of 11 houses in the season of (a) spring, (b) summer, (c) autumn, (d) winter.

Please cite this article in press as: Zehir MA et al. Impacts of microgrids with renewables on secondary distribution networks. Appl Energy (2017), http://
dx.doi.org/10.1016/j.apenergy.2016.12.138
6 M.A. Zehir et al. / Applied Energy xxx (2017) xxxxxx

At the second stage of test bed development, all the blocks were 4. Case study
connected together through a main bus like in a real system and
formed the microgrid (Fig. 5). Their interconnected operation was The developed test bed was used to investigate the intercon-
already tested in a previous study [39]. More details about the nected operation of a microgrid with a LV distribution network.
development process and performance testing of the virtual test This section summarizes the details of the distribution network,
bed can be found in [39]. daily supply/demand profiles for different seasons, simulation
and the results of daily operation of the system.

(a) Spring
1200
Solar Irradiance (W/m2)

1000
800
600
400
200
0
00:00
01:00
02:00
03:00
04:00
05:00
06:00
07:00
08:00
09:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
Time (hour)

(b) Summer
1200
Solar Irradiance (W/m2)

1000
800
600
400
200
0
00:00
01:00
02:00
03:00
04:00
05:00
06:00
07:00
08:00
09:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
Time (hour)

(c) Autumn
1200
Solar Irradiance (W/m2)

1000
800
600
400
200
0
00:00
01:00
02:00
03:00
04:00
05:00
06:00
07:00
08:00
09:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00

Time (hour)

(d) Winter
1200
Solar Irradiance (W/m2)

1000
800
600
400
200
0
00:00
01:00
02:00
03:00
04:00
05:00
06:00
07:00
08:00
09:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00

Time (hour)

Fig. 9. Daily solar irradiance profiles used to represent a day of (a) spring, (b) summer, (c) autumn, (d) winter.

Please cite this article in press as: Zehir MA et al. Impacts of microgrids with renewables on secondary distribution networks. Appl Energy (2017), http://
dx.doi.org/10.1016/j.apenergy.2016.12.138
M.A. Zehir et al. / Applied Energy xxx (2017) xxxxxx 7

4.1. Sample SDN and daily supply/demand profiles The network has long lines with small cross-sectional areas. The
R/X value for each line type of the sample SDN is illustrated in Table 1.
The microgrid was aimed to be connected to a small scale SDN A realistic analysis for daily operational behavior requires the
which represents a rural, an islanded or a small part of an urban adequate modeling of residential loads. It was previously stated
network. For this purpose, a 50 kVA, 400/230 V, 50 Hz typical in several studies that the low resolution load models (above
SDN, which was previously proposed and used in [4] was chosen 10 min) were not sufficient to represent the steady state operation
for the analysis (Fig. 6). Its two feeders with 10 load busses were of the system accurately and high resolution load models (1 min)
modeled in PSCAD program. were recommended [4042]. In order to use different load profiles,

(a) Spring
250
240
Voltage(V)

230
220
210
200
190
00:00
00:45
01:30
02:15
03:00
03:45
04:30
05:15
06:00
06:45
07:30
08:15
09:00
09:45
10:30
11:15
12:00
12:45
13:30
14:15
15:00
15:45
16:30
17:15
18:00
18:45
19:30
20:15
21:00
21:45
22:30
23:15
Time (hour)

(b) Summer
250
240
Voltage (V)

230
220
210
200
190
00:00
00:45
01:30
02:15
03:00
03:45
04:30
05:15
06:00
06:45
07:30
08:15
09:00
09:45
10:30
11:15
12:00
12:45
13:30
14:15
15:00
15:45
16:30
17:15
18:00
18:45
19:30
20:15
21:00
21:45
22:30
23:15
Time (hour)

(c) Autumn
250
240
Voltage (V)

230
220
210
200
190
00:00
00:45
01:30
02:15
03:00
03:45
04:30
05:15
06:00
06:45
07:30
08:15
09:00
09:45
10:30
11:15
12:00
12:45
13:30
14:15
15:00
15:45
16:30
17:15
18:00
18:45
19:30
20:15
21:00
21:45
22:30
23:15

Time (hour)

(d) Winter
250
240
Voltage (V)

230
220
210
200
190
00:00
00:45
01:30
02:15
03:00
03:45
04:30
05:15
06:00
06:45
07:30
08:15
09:00
09:45
10:30
11:15
12:00
12:45
13:30
14:15
15:00
15:45
16:30
17:15
18:00
18:45
19:30
20:15
21:00
21:45
22:30
23:15

Time (hour)

Fig. 10. Voltage variation of the microgrid bus for the cases of (a) spring, (b) summer, (c) autumn, (d) winter.

Please cite this article in press as: Zehir MA et al. Impacts of microgrids with renewables on secondary distribution networks. Appl Energy (2017), http://
dx.doi.org/10.1016/j.apenergy.2016.12.138
8 M.A. Zehir et al. / Applied Energy xxx (2017) xxxxxx

a previously proposed, high-resolution residential load profile gen- of the tool together with its performance verification can be found
erator was preferred [40]. It is an open-source tool that was devel- in [40]. The tool can also generate daily solar irradiance data, based
oped using Excel, based on the household usage statistics of UK, on meteorological statistics, including cloudiness [43]. Daily
meteorological data and appliance parameters. It provides the demand profiles of 11 houses (10 for the distribution network
specification of the number of people, the day of the year and busses and 1 for the microgrid) and solar irradiance that represent
assignment of appliances in a dwelling. Following a bottom-up a day of each season are generated using the tool. Demand profiles
approach and using stochastic programming methods, it aggre- for each house in spring case is provided in Fig. 7. Total demand
gates the consumption behavior of each appliance and produces data and solar irradiance profiles for PV system are given in
residential load profile for a day with 1 min resolution. The details Figs. 8 and 9 respectively.

(a) Spring
1,5
1
0,5
Power (kW)

0
00:00
00:45
01:30
02:15
03:00
03:45
04:30
05:15
06:00
06:45
07:30
08:15
09:00
09:45
10:30
11:15
12:00
12:45
13:30
14:15
15:00
15:45
16:30
17:15
18:00
18:45
19:30
20:15
21:00
21:45
22:30
23:15
-0,5
-1
-1,5
-2
-2,5
Time (hour)

(b) Summer
1,5
1
0,5
0
Power (kW)

00:00
00:45
01:30
02:15
03:00
03:45
04:30
05:15
06:00
06:45
07:30
08:15
09:00
09:45
10:30
11:15
12:00
12:45
13:30
14:15
15:00
15:45
16:30
17:15
18:00
18:45
19:30
20:15
21:00
21:45
22:30
23:15
-0,5
-1
-1,5
-2
-2,5
-3
Time (hour)

(c) Autumn
2
1,5
1
0,5
Power (kW)

0
00:00
00:45
01:30
02:15
03:00
03:45
04:30
05:15
06:00
06:45
07:30
08:15
09:00
09:45
10:30
11:15
12:00
12:45
13:30
14:15
15:00
15:45
16:30
17:15
18:00
18:45
19:30
20:15
21:00
21:45
22:30
23:15

-0,5
-1
-1,5
-2
-2,5
-3
Time (hour)

(d) Winter
1,5
1
0,5
Power (kW)

0
09:00
09:45
10:30
11:15
12:00
12:45
13:30
14:15
15:00
15:45
16:30
17:15
18:00
18:45
19:30
20:15
21:00
21:45
22:30
23:15
06:45
07:30
08:15
00:00
00:45
01:30
02:15
03:00
03:45
04:30
05:15
06:00

-0,5
-1
-1,5
-2
-2,5
Time (hour)

Fig. 11. Power exchange between the microgrid and the distribution network for the cases of (a) spring, (b) summer, (c) autumn, (d) winter.

Please cite this article in press as: Zehir MA et al. Impacts of microgrids with renewables on secondary distribution networks. Appl Energy (2017), http://
dx.doi.org/10.1016/j.apenergy.2016.12.138
M.A. Zehir et al. / Applied Energy xxx (2017) xxxxxx 9

4.2. Critical and daily operation analysis end of 89 m long AMKA 35 line (Point A). This analysis is used to
infer the highest and the least impacts of the microgrid on the net-
At the first stage of the analysis, system operation was simu- work. In the case that the microgrid was connected closer to the
lated for 5 min (a time range at which transient phase following substation, R/X ratio between the microgrid bus and the substation
a switching from grid-connected mode to islanded mode is sup- was much lower when compared with of the far point of connec-
posed to finish and the system switches to steady-state) for the tion. Such a case resulted in less severe negative impact on the
furthest and nearest connection of renewable-based microgrid. neighboring lines and the busses. The highest impact occured
The furthest connection point is the right end of 571 m long AXMK when the microgrid is connected from the furthest bus. Two
50 line (Point B), while the nearest connection point is the right extreme cases were simulated. The first was the maximum local

(a) Spring
5

0 03:38

08:43

13:49
00:00
00:43
01:27
02:10
02:54

04:21
05:05
05:49
06:32
07:16
08:00

09:27
10:11
10:54
11:38
12:22
13:05

14:33
15:16
16:00
16:43
17:27
18:11
18:54
19:38
20:22
21:05
21:49
22:33
23:16
-5
Power (kW)

-10

-15

-20

-25
Time (hour)

(b) Summer
5

0
03:38

08:43

13:49
00:00
00:43
01:27
02:10
02:54

04:21
05:05
05:49
06:32
07:16
08:00

09:27
10:11
10:54
11:38
12:22
13:05

14:33
15:16
16:00
16:43
17:27
18:11
18:54
19:38
20:22
21:05
21:49
22:33
23:16
-5
Power (kW)

-10

-15

-20

-25
Time (hour)

(c) Autumn
5

0
13:49

18:11
18:54
19:38
20:22
21:05
21:49
22:33
23:16
14:33
15:16
16:00
16:43
17:27
03:38

08:43
00:00
00:43
01:27
02:10
02:54

04:21
05:05
05:49
06:32
07:16
08:00

09:27
10:11
10:54
11:38
12:22
13:05

-5
Power (kW)

-10

-15

-20

-25
Time (hour)

(d) Winter
5

0
03:38

08:43

13:49
04:21
05:05
05:49
06:32
07:16
08:00

09:27
10:11
10:54
11:38
12:22
13:05

14:33
15:16
16:00
16:43
17:27
18:11
18:54
19:38
20:22
21:05
21:49
22:33
23:16
00:00
00:43
01:27
02:10
02:54

-5
Power (kW)

-10

-15

-20

-25
Time (hour)

Fig. 12. Power exchange between the distribution network and the utility for the cases of (a) spring, (b) summer, (c) autumn, (d) winter.

Please cite this article in press as: Zehir MA et al. Impacts of microgrids with renewables on secondary distribution networks. Appl Energy (2017), http://
dx.doi.org/10.1016/j.apenergy.2016.12.138
10 M.A. Zehir et al. / Applied Energy xxx (2017) xxxxxx

14%

Dierence with respect to the


operaon without MG (%)

13,0%
12%

12,1%
11,8%
10%

10,1%
9,5%
9,0%
08%

8,0%
06%
04%

4,5%
3,8%

3,5%
3,3%

3,0%
2,7%
2,7%

2,8%
02%
00%
Maximum Voltage Minimum Voltage Network Losses

Extreme Case Analysis Spring Daily Operaon Summer Daily Operaon


Autumn Daily Operaon Winter Daily Operaon

Fig. 13. Comparison of the results of the extreme case analysis with the daily operation analysis of different seasons.

100

74,3
90
80

56,7
70
Duraon (%)

49,6

49,4
44,6
60
40,1

36,2
50
40

21,6
30
9,3

20
6,5

5,2
3,3
0,7
1,1

0,7
0,6

10
0
200-210 210-220 220-230 230-240
Voltage Range (V)
Spring Summer Autumn Winter

Fig. 14. Microgrid bus voltage level duration for each simulated day.

generation-minimum demand in both the microgrid and SDN, without microgrid. The results of extreme case analysis and daily
while the second was minimum local generation-maximum operation analysis are comparatively illustrated in Fig. 13.
demand in both microgrid and SDN. The resulting maximum volt- The microgrid main bus voltage level durations according to 10
age increase for these extreme operational cases was found to be V ranges for each simulated day are given in Fig. 14. The results
9%, exceeding 250 V, while the highest voltage decrease was 13% indicate that, although the highest voltage drop is close to the
and below 205 V. Simulations showed that, furthest point of micro- extreme case analysis, it is for short periods of time. On the other
grid connection to the SDN with maximum generation and mini- hand, voltage rise is for longer periods; but far better from the
mum demand can cause line losses up to 8%. worst case results as magnitude.
At the second stage of the analysis, minutely residential load
profiles and solar irradiation data that represent a day from each 5. Conclusion and discussions
season were used in daily operation simulations. The impacts of
far point of connection was investigated. The results showed that, The study has presented the impacts of a renewable-based
the microgrid bus voltage magnitude did not exceed 240 V, but it microgrid on a secondary distribution network. By the use of a vir-
decreased below 210 V at some critical times of operation (Fig. 10). tual test bed and a LV network model, high resolution solar irradi-
Power exchange between the microgrid and the distribution ance data considering cloudiness and residential consumption
network for daily operation cycles are illustrated in Fig. 11. Power profiles that represent a day of each season were simulated. The
exchange between the distribution network and the utility is severity of critical operating conditions in terms of voltage varia-
shown in Fig. 12. tion and line losses was investigated for daily operation. The
The increase in microgrid bus voltage did not exceed 4.5%, while results of the daily analysis are compared with those of the
the decrease was up to 12.1%. The voltage rises were relatively less extreme-case analysis.
when compared to the critical case analysis results, which was up It can be inferred from the results that the voltage increases do
to 9%. This was due to short period of maximum DG output during not reach extreme levels since the duration of maximum microgrid
midday period which did not coincide with the minimum network supply does not coincide with the duration of minimum overall
loading durations (late night and early evening). However, voltage consumption. Similarly, active power losses for daily analysis are
drop was still considerable. The reason was longer periods of min- much smaller than those of the extreme cases. On the other hand,
imum DG output duration which intersected with the maximum similar to the critical case analysis, under voltage problems can
network loading periods (evening hours). System losses were reach extreme levels. It is because of high coincidence of maximum
found to be up to 3.5% more when compared to system operation demand times with minimum generation periods. Duration

Please cite this article in press as: Zehir MA et al. Impacts of microgrids with renewables on secondary distribution networks. Appl Energy (2017), http://
dx.doi.org/10.1016/j.apenergy.2016.12.138
M.A. Zehir et al. / Applied Energy xxx (2017) xxxxxx 11

analysis of voltage values in daily operation revealed that the volt- [6] Janko SA, Arnold MR, Johnson NG. Implications of high-penetration renewables
for ratepayers and utilities in the residential solar photovoltaic (PV) market.
age drop can still reach extreme levels after the integration of PV
Appl Energy 2016;180:3751.
generation. The main improvement was shortened durations. On [7] Moura PS, Almeida AT. The role of demand-side management in the grid
the other hand, the voltage increases were found far lower than integration of wind power. Appl Energy 2010;87:25818.
the extreme case analysis; but with longer durations. Similarly, [8] Mahmud MA, Hossain MJ, Pota HR. Voltage variation of distribution
networks with distributed generation: worst case scenario. IEEE Syst J
the power losses were lower compared to the worst case analysis. 2014;8:1096103.
The analysis provides important insight into the operation of [9] McKenna E, Grnewald P, Thomson M. Going with the wind: temporal
renewable-based microgrids in weak LV networks. It can be stated characteristics of potential wind curtailment in Ireland in 2020 and
opportunities for demand response. IET Renew Power Gener 2015;9:6677.
that the load factor of microgrid connection bus and neighboring [10] Ackermann T, Carlini EM, Ernst B, Groome F, Orths A, OSullivan J, et al.
busses allows more renewable integration into the system without Integrating variable renewables in Europe. IEEE Power Energy Mag
causing overvoltage and significant power loss problems. Investi- 2015;13:6777.
[11] Stadler I. Power grid balancing of energy systems with high renewable energy
gation of the magnitudes and the durations of voltage drops and penetration by demand response. Utilities Policy 2008;16:908.
rises can contribute to the development and sizing of mitigation [12] Karimi M, Mokhlis H, Naidu K, Uddin S, Bakar AHA. Photovoltaic penetration
options. There are some preliminary field applications on real time issues and impacts in distribution network a review. Renew Sustain Energy
Rev 2016;53:594605.
monitoring and mitigation of voltage changes in secondary distri- [13] Gaunt CT, Namanya E, Herman R. Voltage modelling of LV feeders with
bution networks and microgrids. A company in US provides real- dispersed generation: limits of penetration of randomly connected
time voltage monitoring service at end-user connection points to photovoltaic generation. Electr Power Syst Res 2017;143:16.
[14] Shivashankar S, Mekhilef S, Mokhlis H, Karimi M. Mitigating methods of power
the utility operator [44]. Moreover, battery storage facilities at cus-
fluctuation of photovoltaic (PV) sources- a review. Renew Sustain Energy Rev
tomer sites can be remotely controlled by the company for 2016;59:117084.
responding to events happening on the utility side. According to [15] Haque MM, Wolfs P. A review of high PV penetrations in LV distribution
the results of the experimental studies proposed in [25], batteries networks: present status, impacts and mitigation measures. Renew Sustain
Energy Rev 2016;62:1195208.
can mitigate power and voltage fluctuations, influencing the net [16] Bucciarelli M, Giannitrapani A, Paoletti S, Vicino A, Zarilli D. Energy storage
power supplied to the network. The researchers in [24] investi- sizing for voltage control in LV networks under certainty of PV generation. In:
gated tap changer operation performance with battery storage on IEEE 2nd international forum on research and technologies for society and
industry. p. 16.
a hardware-in-the-loop (PHIL) test bed. Active power management [17] Hoke A, Butler R, Hambrick J, Kroposki B. Steady-state analysis of maximum
can be another mitigation option. In [45], lighting load was photovoltaic penetration levels on typical distribution feeders. IEEE Transact
dimmed to improve voltage profile of the main bus in an experi- Sustain Energy 2013;4(2):3507.
[18] Kabir MN, Mishra Y, Ledwich G, Dong ZY, Wong KP. Coordinated control of
mental microgrid system benefiting from building automation grid-connected photovoltaic reactive power and battery energy storage
devices. The study proposed in [46] showed that a group of PV pan- systems to improve the voltage profile of a residential distribution feeder.
els can be divided into several dispatchable units through addition- IEEE Trans Industr Inf 2014;10(2):96777.
[19] Doumbia ML, Agbossou K. Voltage variation analysis in interconnected
ally installed switches (rather than being switched as a whole) and electrical network-Distributed generation. In: IEEE Canada electrical power
controlled to improve the main bus voltage profile of a microgrid. conference. p. 52530.
The researchers in [47] tested their management approach for net- [20] Scott NC, Atkinson DJ, Morrell JE. Use of load control to regulate voltage on
distribution networks with embedded generation. IEEE Trans Power Syst
worked microgrids and reduced the voltage and power fluctuations
2002;17:5105.
in the active distribution system. The results found in this paper [21] Hatziargyriou ND, Karakatsanis TS, Papadopoulos M. Probabilistic load flow in
can contribute to studies on sizing of devices that will be used in distribution systems containing dispersed wind power generation. IEEE Trans
real systems by revealing the critical cases that will more likely Power Syst 1993;8:15965.
[22] Wong J, Lim YS, Tang JH, Morris E. Grid-connected photovoltaic system in
to occur during daily operation. Malaysia: a review on voltage issues. Renew Sustain Energy Rev
The future studies will be on mitigation of negative impacts of 2014;29:53545.
renewable-based microgrids on distribution networks using [23] Peacock AD, Newborough AD. Controlling micro-CHP systems to modulate
electrical load profiles. Energy 2007;32:1093103.
microgrid energy management systems. [24] Liu X, Aichhorn A, Liu L, Li H. Coordinated control of a distributed energy
storage system with tap changer transformers for voltage rise mitigation
under high photovoltaic penetration. IEEE Transact Smart Grid 2012;3
Acknowledgement
(2):897906.
[25] Hara R, Kita H, Tanabe T, Sugihara H, Kuwayama A, Miwa S. Testing the
This research is funded as a part of Smart Electric Energy Man- technologies. IEEE Power Energy Mag 2009;7(3):7785.
[26] Zpryme and IEEE. Power Systems of the Future: The Case for Energy Storage,
agement and Buildings Energy Efficiency Technologies-SEEMBEET
Distributed Generation, and Microgrid, <https://building-microgrid.lbl.gov/
project under the framework of the Bilateral Research and Tech- sites/all/files/the_case_for_energy_storage_distributed.pdf> [accessed
nology Cooperation Turkey-Greece 2013-2014 organized by 09.05.16].
The Scientific and Technological Research Council of Turkey [27] Gozel T, Navarro A, Ochoa LN. Deliverable 3.5 Creation of aggregated profiles
with and without new loads and DER based on monitored data, <https://www.
(TUBITAK) and General Secretariat for Research and Technology escholar.manchester.ac.uk/api/datastream?publicationPid=uk-ac-man-scw:
(GSRT). 244636&datastreamId=full-text.pdf> [accessed 18.06.16].
[28] Elam MJE, Muttaqi KM, Sutanto D. A comprehensive assessment tool for solar
PV impacts on low voltage three phase distribution networks. In: 2nd
References International conference on the developments in renewable energy
technology. p. 15.
[1] U.S. Energy Information Administration. International Energy Statistics- [29] Baran ME, Hooshyar H, Shen Z, Huang A. Accomodating high PV penetration on
Renewables, <https://www.eia.gov/cfapps/ipdbproject/IEDIndex3.cfm?tid=6& distribution feeders. IEEE Transact Smart Grid 2012;3(2):103946.
pid=29&aid=12> [accessed 21.06.2016]. [30] Solanki SK, Ramachandran V, Solanki J. Steady state analysis of high
[2] Colmenar-Santos A, Reino-Rio C, Borge-Diez D, Collado-Fernndez E. penetration PV on distribution feeder. In: IEEE PES transmission and
Distributed generation: a review of factors that can contribute most to distribution conference and exposition. p. 16.
achieve a scenario of DG units embedded in the new distribution networks. [31] Schoene J, Zheglov V, Houseman D, Smith JC, Ellis A. Photovoltaics in
Renew Sustain Energy Rev 2016;59:113048. distribution systems- integration issues and simulation challenges. In: IEEE
[3] Stadler M, Cardoso G, Mashayekh S, Forget T, DeForest N, Agarwal A, et al. power and energy society general meeting. p. 15.
Value streams in microgrids: a literature review. Appl Energy 2016;162:9809. [32] Kabir MN, Mishra Y, Ledwich G, Xu Z, Bansal RC. Improving voltage profile of
[4] California ISO. Flexible Resources Help Renewables - Fast Facts, <http:// residential distribution systems using rooftop PVs and battery energy storage
www.caiso.com/Documents/FlexibleResourcesHelpRenewables_FastFacts. systems. Appl Energy 2014;134:290300.
pdf> [accessed 13.07.16]. [33] Mandelli S, Brivio C, Colombo E, Merlo M. Effect of load profile uncertainty on
[5] Bomann T, Staffell I. The shape of future electricity demand: exploring load the optimum sizing of off-grid PV systems for rural electrification. Sustain
curves in 2050s Germany and Britain. Energy 2015;90:131733. Energy Technol Assess 2016;18:347.

Please cite this article in press as: Zehir MA et al. Impacts of microgrids with renewables on secondary distribution networks. Appl Energy (2017), http://
dx.doi.org/10.1016/j.apenergy.2016.12.138
12 M.A. Zehir et al. / Applied Energy xxx (2017) xxxxxx

[34] Hung DQ, Mithulananthan N, Bansal RC. Integration of PV and BES units in [41] Marszal-Pomianowska A, Heiselberg P, Larsen OK. Household electricity
commercial distribution systems considering energy loss and voltage stability. demand profiles- a high-resolution load model to facilitate modelling of
Appl Energy 2014;113:116270. energy flexible buildings. Energy 2016;103:487501.
[35] Yan R, Saha TK. Investigation of voltage stability for residential customers due [42] Wright A, Firth S. The nature of domestic electricity-loads and effects of time
to high photovoltaic penetrations. IEEE Trans Power Syst 2012;27(2):65162. averaging on statistics and on-site generation calculations. Appl Energy
[36] Stenzel P, Linssen J, Fleer J. Impact of different load profiles on cost optimal 2007;84:389403.
system designs for battery supported PV systems. Energy Procedia [43] Richardson I, Thomson M. Integrated simulation of photovoltaic micro-
2015;75:18628. generation and domestic electricity demand: a one-minute resolution open-
[37] Povlsen A. International Energy Agency report, IEA PVPS T5-10, <http://www. source model. J Power Energy 2011;227:7381.
hme.ca/gridconnect/IEA_PVPS_Task_5-10_Impacts_of_PV_Power_Penetration. [44] Stem. Grid services with Stem, <http://www.stem.com/grid/> [accessed
pdf> [accessed 01.12.16]. 30.11.16].
[38] Istanbul Technical University (ITU), Western Macedonia University of Applied [45] Stimoniaris D, Kollatou T, Tsiamitros D, Zehir MA, Batman A, Bagriyanik M,
Sciences (TEIWM). Smart Electric Energy Management and Buildings Energy et al. Demand-side management by integrating bus communication
Efficiency Technologies (SEEMBEET), <http://www.edalab.itu.edu.tr/ technologies into smart grids. Electric Power Syst Res 2016;136:25161.
seembeet> [accessed 27.06.16]. [46] Stimoniaris D, Tsiamitros D, Dialynas E. Improved energy storage management
[39] Zehir MA, Batman A, Sonmez MA, Font A, Tsiamitros D, Stimoniaris D, et al. and PV-active control infrastructure and strategies for microgrids. IEEE
Development of a field data-based virtual test bed for microgrid integration of Transact Power Syst 2016;31(1):81320.
building automation technologies. In: 9th International conference on [47] Lv T, Ai Q. Interactive energy management of networked microgrids-based
electrical and electronics engineering. p. 515. active distribution system considering large-scale integration of renewable
[40] Richardson I, Thomson M, Infield D, Clifford C. Domestic electricity use: a high- energy resources. Appl Energy 2016;163:40822.
resolution energy demand model. Energy Build 2010;42:187887.

Please cite this article in press as: Zehir MA et al. Impacts of microgrids with renewables on secondary distribution networks. Appl Energy (2017), http://
dx.doi.org/10.1016/j.apenergy.2016.12.138

You might also like