HDPE pipe Hydraulic test procedure

Pressurizes water to 1.6MPa

After 5 minutes progress

Pressurizes water again to 1.6MPa

Reduce pressure to 1.35MPa

Keep 1 hour
hour

Remained water pressure Remained water pressure


> 0.95MPa < 0.95MPa

Check a leak of water of the


Hydraulic test passed
pipe by viewing

Cut off a leak of water


position and weld pipe

Hydraulic test again