Identification
of Line Reactance
in the Realization of
Adaptive Slip Stabilization
@ BROWN BOVERI
Publication No. CHIE 203 060 EIdentification of Line Reactance in the Realization
of Adaptive Slip Stabilization
A Roth, Baden
The line reactance has a considerable influence on the
static and dynamic stabilty of the generator. The article
Gescrives the way i which the BBC 'X,-identiication
Unit operates. n particular how it determines the external
reactance from the given measuranas and adapts the in
fence of the slip stabilization equipment according to
the actual operating point.
Because of the increased unit ratings of power plants
land the resulting higher line reactances, great impor-
tance is being attached today to stable transmission of
‘generator power.
Introduction
‘The object of adaptive sip stabilization equipment is to
raise the generator exciter’s contribution to improved
stability to the highest possible operating range of the
generator. It has been shown in various treatments (1, 2]
that the stability of synchronous generators can be sub-
stantially improved by influencing the excitation via
stabilization equipment. The operating points of the ac-
tive power P, reactive power Q and the line reactance
have a strong influence on the damping of electro-me=
chanical oscillations of a generator.
The proven slip stabilization unit from BBC derives ad-
tional signals trom the active power, frequency or
speed, which considerably improve the stability of the
Power transmission. K and Kz are the amplification tac-
tors of these two variables. Non-adaptive slip stabilization
in which ; and Xz are fixed, represent a certain compro-
mise when power system conditions are eritical, although
this also permits the static stability limit to be substantially
improved
Adaptive slip stabilization, however, ensures high sta
bility during both static and transient operation of the
generator by optimizing the weighting of the stabilizing
signals at each operating point
‘The advantages this offers are as follows:
~ Secure energy transport, even with @ high line reac-
tance,
— Improves utilization of the generator at certain operat-
ing points, e.g. when the generators are underexcites.
~ Greater security during transient generator operation
28 @ result of load-flow changes due to, for example,
load shedding or short circuits in the network.
The variables upon which the adaptation ofthe stabilz.
ing signals is based are the instantaneous active power P,
Fig. 1 — Digplacement of he optimum setting values K, Ky as a
funetion of,
2 = 09
03
ba
= 08
‘Ke = Amoliticaton factors ofthe sip stabilization
Curves of onetant camping
Curved: damping = 0 unstable)
Gurve 2 damping = ~0-157
Curve 3: damping = ~0-47
A & optimum sating for
Pt: optimum setting for
the reactive power Qand the external reactance X,. The
active and reactive pawers are given, while the external
reactance X, has to be determined by the ‘X,identiti-
cation’ unit from the signals obtained at the measuring
point
Figure 1 shows the decisive effect which the external
reactance has on the generator stability. The curves dem-
onstrate the constant damping of the rotor oscillations as
8 function of the amplification factors Ky and Ke ofthe slip
stabilization system. Point A shows that for X= 03 pu
{damping is good, whereas for X, = 0:8 p.u. the generator
would be absolutely unstable. In this case point 8 wouldX,-Identification
‘The value of the extemal reactance referred 10 a
‘measuring point can be determined fundamentally trom
the overall network configuration, under consideration of
the given load conditions. In practice, however, due to
the complexity of the network configuration, which also
‘changes continually, this is not realistic, not least be-
‘cause it would necessitate an extremely complex data
‘communications network.
The task of the Xridentification unit is theretore to de-
termine the external reactance %, using only the meas-
turands present atthe measuring point.
‘Determination of the external reactance is based upon
the mode! “power plant—iine—load centre’, ie, one or
more generators operate over a reactance on an infinite
bus. For the purpose of the model, the load-centre volt-
‘age Uy. which is assumed to be amplitude and phase-
locked, s designated the infinite bus.
“The power conditions along aline such as that in Fig. 2
are given by the following expressions:
sin o
gt cos @
From (1) and (2) we obtain
Pp
5 = arctg —>— ®
ug
4 a
‘Since the voltage Us is assumed, by definition, to have
‘a locked phase and amplitude, the variation of the phase
“angie 0, with respect to time corresponds to the variation
Of the phase position for the voltage across the generator
terminals with respect to time.
“The method used to determine X, involves calculating
the phase angles &, 4, fy... 4h for n (the number to De
expected in practice) given values of X, under the con
ditions present at the measuring point (active power P,
Teactive power Q and generator voltage Us) and com-
paring their variation with time with the phase-angle
Variation jen measured, The closest agreement between
the phase-angle variation calculated with an assumed Xe-
value and the measured phase-angle variation therefore
etermines the X-value for the generator.
Operating Mode of the BBC Unit (Fig. 3)
By definition, the section of the network under con-
sideration is represented by the generator with the volt=
‘age Us, the line reactance X, and the infinite bus with the
‘source voltage Uy. At test point M, the active power P, re-
4
Fig 2 — Equivalent oiagram forthe ine reactance
Gonorator
Up = Generator votage
Xe = Line reactance
Phase angie between Us and Uy
OG, = intinite bus vottage
B= Active power flow
MZ Measuring point
active power Q and the actual generator voltage Us are
measured.
“The time characteristics of the corresponding phase
angle 8-8 are then calculated from P, Qand Us? accord-
‘ng to equation (2), The calculation takes place in several
functional generators (Ggy-Ges), each with a given value
for Xe (Xe—%as)
in the phase-angle measuring unit PM, the generator
voltage phase angle is formed from the generator voltage
Us and a voltage from an internal oscillator whose phase
land angle are practically locked, In Figure 3 this Is rep-
resented by a phase locked loop (PLL) with PM, Fs and a
veo.
Special filters F\-F, eliminate the dc. voltage com.
ponents and the ramp components of the ealoulated and
measured phase angles, so that only the calculated
phase-angle variations 4d}, Ad), dé, appear at the output
Of the fiters F;-Fs and the measured change in phase
angle Sdjay at the output of F,. These eliminations are es
Sential to prevent the subsequent similariy tests from be-
ing unnecessarily complicated. Suitable correlation cir-
cuits Gy-Gia now subject the calculated characteristics
of the phase-angle variations Ad, Ad, Ad and the
‘characteristic of the measured phase variation Aja 10 &
similarity test. X, is determined by the calculated curve
Characteristic which agrees best with the measured
characteristic. After a plausibility test, only that output of
the largest-value selector GA is activated which corre
sponds to the highest correlative (Koy~Kos)
jas.Fig, 3 — Basie aagram of the X identi
Cation system
= Generator voltage
= Retval value of gnerator
voltage
, et power
it
Eirdy = Coaoncecuts
mt enter
wo lage consoled
: ~ iru mera
Boer iva Opuatn station
as ee
Teck = ontance values
Guw ete, bs Meese, = Calculated phase-angie
—< differences
— * Mion = Measured phase-angle
- ‘serene
= seit
et
ty em |
| operat. Tab TA
Shit” F~}spe ate MPO Xo Ka
~ T 1
sh
The correlation takes place over the period T with an
exactly defines number of measuring cycles. A new set of
data is stored in the memory each time a cycie is complet
4. For this purpose a so-called ‘rotating’ memory is used
\which updates its contents every cycle and in which the
data containing the calculated and measured values over
the period Tare stored. Updating involves overwriting the
oldest data set with the most recently recorded data. The
data stored in the memory is therefore always up to date.
Figure 4 shows a time characteristic of the calculated
phase angle and the measured phase angle. At time &
the external reactance of 0.4 p.u. increases to 08 pu
and at time f decreases again to 0:4 p.u. tis evident that
from f; 10 f the measured phase angle dq, corresponds
to the calculated phase angle 6; for X, = 0-8 and from
to & 10 the calculated phase angle & for % = 0-4. The
phase angles are recorded before subtraction of the dic
‘and ramp components.
The Xcidentification unit detects the following operat
ing states
= Steady-state operation of the generator
= Transient state
= Switching operations, short circuits and end of short
circuits‘Steady-state operation
In this mode, the generator is capable of handling the
‘given situation without stability problems arising anc with
‘nly minor weighting of the stabilizing signals. In steady
State operation, the amplitication value of the stabilizing
Signal is minimized. The identification is suppressed
since the changes in the measured values are too small
10 provide useful results.
Transient operation
The identification algorithm starts during the transient
state (variation of the duty point). Each new identification
's followed by optimum adaptation of the amplification
factors with the aim of returning to the steady state
Identification continues until the algorithm determines
that the oscillations are to small to provide reasonable re-
sults,
Prevention of identilication errors
‘Switching operations, short circuits and the end of
short circuits are detected in order to exclude for a cer-
tain length of time consideration of values occurring dur-
ing such events. and thereby prevent identification errors.
Short circuits and the end of short circuits are detected
by monitoring the generator voltage and active power
over @ defined period. It the increase or decrease in these
values exceeds a certain rate of change, either a short
Fig. 5 ~ Structure ofthe adaptive sip stabilization system
= Reactive power
= Generator vattage
y= Setting values
= Time constants
= stabilizing signal
Fow= Compouing reisors
ip Mamnphers
ROAR EOY
Fig. 4 = Comparison of measured phase angle
free calculated phase angles
tance from 04-0.8-04
X= Identities line reactance
on with the
tora change in Heine reac
eid voltage
fat =Reterence valve
Ye = Voltage regulator
CC _SGate control unt
Sp = Aeveleration signal
SPS Frequency signa!
dab deeloraton signa
Sf T Asse fequeney Sonat
‘Sip stabazton |
Xe
\aenticavonicin anki ibs tm pit
circuit or end of short circuit will be determined. in the
‘same way a circult-breaker opening or closing a line can
be detected by monitoring the active power and measur-
e ed phase angie.
Seittest
The Xridentiication function includes various. sel
tests, An internal fault causes the unit to switch off
automatically, and this tact to be signalled. The ampli
cation factors of the slip stabilization are switched to
values which ensure secure, although not optimized
operation. With the slip stabilization unit alone it is pos-
sible to select an amplification pair in relation to a certain
duty point (1, 2} The X,-identification enables the stabilz-
ing signals to be weighted on the basis of two Fivalues,
three Qvalues and three X-values per channel, ie. 18
Values of the Ap channel and 18 values of the / channel
—a total of 36 possible settings. itis these which make it
possible to optimize the weighting of the stabilizing sig-
hals for each duty point of the generator. The weightings
‘py and Ay, are stored in the Table TA.
Xe Identiication in multi-machine systems
‘The identification method chosen by BBC also ensures,
‘correct identification for each generator in multimmachine
installations, respective of how many generators are in
@ operation. Further signals providing information on the
Status ofthe overall instalation are not necessary.
Figure 5 shows the basic diagram of an adaptive slip
stabilization system.
Conclusions
The purpose of X-identification is to ensure high sta-
bility during steady-state and transient operation of the
‘generator by adapting the slip stabilization. This is
Achieved by optimum weighting of the stabilizing signal at
each generator duty point. The result is improved uti
zation and greater operating security of the generator.
[1] F:Poneder. A. Bertschi: Sip stabizaion. Brown Boveri Rev
61 1974 (10) Aaetod
[2] F Peneder, A Bertsch: Optimizing the setting ot sip stabii-
ation equipment by sigial computers and special computing
procestres: Brown Bove ev. 69 1976 (8) 580-587,
[8] P.Bonanomi, G.Guth, F Blaser, Glavtsch: Concept of
practical acaptve regulator Yor exctation control. IEEE paper
Ro. A 704888
[4] P.Bonanomy, R.Bertsch: Ontine identtication of an equie
Valent reactance for stabilly applications. IEEE PES Summor
Meeting, Vancouver, Canada, July 15-20, 1979, SM 502-5,
e BibliographyBBC
BROWN BOVERI
BBC Brown, Boveri & Company, Lid
(CH-6401 Baden/ Switzerland
Division for industrial Plants, Electric Drives and Power Electronics