PCC1301 for Producer Gas Engine TB-3 Details

From PCC OEM/CUSTOMER


1301 Panel Responsibility
TB-3

TB3-1 1 1 B + (Ve)
TB3-2 2 2 B + (Ve) 24VDC B+(20A Fused) supply
TB3-3 3 3 B + (Ve) continious available for
TB3-4 4 4 B + (Ve) Customer Use
TB3-5 5 5 B + (Ve)
6 6 Spare
TB3-7 7 7 B - (Ve)
TB3-8 8 8 B - (Ve) GND ENG for Customer
TB3-9 9 9 B - (Ve) Use
TB3-10 10 10 B - (Ve)
TB3-11 11 11 To Gas Shut OFF -(Ve)
TB3-12 12 12 Valve +(Ve)
TB3-13 13 13 NO Gas Shut-off Aux Relay
TB3-14 14 14 Com Use N/O in series with Bkr
TB3-15 15 15 NC U/V Coil to Trip Bkr
TB3-16 16 16 Remote Start (NO)
TB3-17 17 17 Return
TB3-18 18 18 Ready To Load
TB3-19 19 19 Ready To Load (Com)
TB3-20 20 20 Remote Emm Stop (NC)
TB3-21 21 21 Return
TB3-22 22 22 Cust Fault I/P 1
TB3-23 23 23 Com
TB3-24 24 24 Com
TB3-25 25 25 Cust Fault I/P 2
TB3-26 26 26 Common
TB3-27 27 27 Warning Fault
TB3-28 28 28 Common
TB3-29 29 29 Shutdown Fault
TB3-30 30 30 RS485-A Signal
TB3-31 31 31 RS485-B Signal
TB3-32 32 32 Speed Raise
TB3-33 33 33 Speed Lower
TB3-34 34 34 B+(Ve)
TB3-35 35 35 Engine Idle
TB3-36 36 36 Return
TB3-37 37 37 S1 From Alternator
TB3-38 38 38 S2 /5Amp, 5VA CT
TB3-39 39 39 R Phase 230VAC Supply
TB3-40 40 40 Neutral From Alternator
TB3-41 41 41 (NO) High Intake Manifold Temp
TB3-42 42 42 Com Shutdown Fault
TB3-43 43 43 (NC)
TB3-44 44 44 (NO) Hight Compess Outlet Temp
TB3-45 45 45 Com Shutdown Fault
TB3-46 46 46 (NC)
TB3-47 47 47 (NO) High CWT
TB3-48 48 48 Com Shutdown Fault
TB3-49 49 49 (NC)
TB3-50 50 50 (NO) LLOP
TB3-51 51 51 Com Shutdown Fault
TB3-52 52 52 (NC)
TB3-53 53 53 (NO) Engine O/S
TB3-54 54 54 Com Shutdown Fault
TB3-55 55 55 (NC)
TB3-56 56 56 (NO) Over Current
TB3-57 57 57 Com Shutdown Fault
TB3-58 58 58 (NC)
TB3-59 59 59 (NO) Over Voltage
TB3-60 60 60 Com Shutdown Fault
TB3-61 61 61 (NC)
TB3-62 62 62 (NO) PCC NOT IN AUTO
TB3-63 63 63 Com Warning
TB3-64 64 64 (NC)
65 65
66 66
67 67
68 68

You might also like