IRJET Experimental Investigations of Double Pipe Heat Exchanger With Triangular Baffles PDF
IRJET Experimental Investigations of Double Pipe Heat Exchanger With Triangular Baffles PDF
ujjwalnayak77@gmail.com
------------------------------------------------***---------------------------------------------
Abstract - A set of the experiments were carried out for heavy industries, such as power or metallurgy, chemical,
this dissertation to investigate and compare the heat automotive, through the high technique ones such as
transfer behaviour in a double pipe concentric tube heat electronics, to production of every day consumers goods
exchanger with and without triangular baffles for both like refrigeration, air conditioning systems, etc. [1]
parallel and counter flow arrangements. The test section Here an experimental investigation has been
is a horizontal annular passage formed by two concentric performed to study the effects of the baffles on a
tubes with an inner to outer diameter ratio of 3.17 and concentric tube heat exchanger. Baffles are attached to
length of 2438 mm. Heat is only transferred from the the heated surface so that it provide an additional heat
inner tube in which hot fluid is flowing to the annulus transfer surface area and to promote useful turbulence.
which is well insulated. Triangular baffle with dimensions Due to the presence of baffles the flow is separated,
of 4 mm base, 8mm height and 1.5 mm thickness are used reattached and creates reverse flow. Recently, many
in the present study. In the beginning we conducted the experiments have been carried out. Most investigation
experiment without any baffle to get the performance tells about the optimal baffle geometry that increases
parameter for plane heat exchanger and then with baffle heat transfer performance for a flow rate.
of pitches 50 mm and 100 mm. The effects of the baffles
spacing and mass flow rate of fluid is examined on the An investigation had been carried out to compare the
thermal performance of heat exchanger. It is found that heat transfer performance of hexagonal pin-fin heat
the effectiveness increases with increase in flow rate of sinks with various commonly used fin geometries. It is
cold fluid and average effectiveness also increases when found that for the given flow rate and pressure
pitch of baffles are 100 mm and 50 mm by 1.42 and 1.62 gradient, the Nusselt number of hexagonal fin geometry
times in parallel flow and 1.34 and 1.62 in counter flow yield a higher in comparison to square fins, and a lower
that of smooth tube respectively. The other performance in comparison to circular fins. The heat transfer
parameter like heat transfer coefficient and heat transfer performance in staggered hexagonal fin geometry is
rate obtained through experiment is also increases. The similar in-line circular performance at most Reynolds
effectiveness method is used for calculation of overall heat numbers in the range considered here[2].Experimental
transfer coefficient and effectiveness. investigation is performed to know the effects of the
baffle alignment (staggered and in-line), open area ratio,
Reynolds number, baffle height and baffles pitch on the
Key Words: Double pipe, Heat capacity, LMTD ( ), heat transfer increment, friction factor and the different
Triangular baffles heat exchanger, Overall Heat Transfer thermal performance parameter for turbulent flow of air
Coefficient, Effectiveness ( ) etc. in a rectangular duct with perforated baffles[3].
Reported experimental and numerical analysis of
hydrodynamic and heat transfer characteristics of a heat
1. INTRODUCTION exchanger with single- helical baffles. CFI model is used
and compared the performance of heat exchanger with
Heat exchangers are the equipment that is commonly
single - segmental baffles [4]. Experimental and analytical
used to transfer heat between two flowing fluids at
study has been carried out on water-to-water heat
different temperatures without any mixing of fluid with
transfer in tube-tube heat exchanger. These tubetube
each other. Transfer of the energy from one fluid to
heat exchangers are successfully demonstrated for
another fluid can be done either by conduction,
condenser and evaporator in heat pumps, milk chilling
convection or radiation or with all modes of heat
and pasteurizing application [5]. In this paper the study
transfer. Heat exchangers are very important
of shell and tube heat exchanger is carried out also the
components in engineering systems, ranging from the
factors which affect the performance of heat exchanger
2016, IRJET | Impact Factor value: 4.45 | ISO 9001:2008 Certified Journal | Page 1137
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056
Volume: 03 Issue: 08 | Aug-2016 www.irjet.net p-ISSN: 2395-0072
2016, IRJET | Impact Factor value: 4.45 | ISO 9001:2008 Certified Journal | Page 1138
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056
Volume: 03 Issue: 08 | Aug-2016 www.irjet.net p-ISSN: 2395-0072
= = ...(8)
Now the effectiveness is known, the heat transfer rate can
be very easily calculated by using the equation
0.3
= ... (5) HE with
baffles pitch
0.2 100 mm
The actual heat transfer rate Q can be determined by HE with
writing an energy balance over either side of the heat 0.1 baffles pitch
50 mm
exchanger
0
0.118 0.16 0.19 0.219 0.244 0.266
Q= (th1 th2 ) = (tc2 tc1). (6) Mass Flow Rate (kg/second)
Thus, Effectiveness,
2016, IRJET | Impact Factor value: 4.45 | ISO 9001:2008 Certified Journal | Page 1139
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056
Volume: 03 Issue: 08 | Aug-2016 www.irjet.net p-ISSN: 2395-0072
0.4
coeff.(w/m2k)
4000
0.3
HE with
3000
0.2 baffles pitch HE with
100 mm 2000 baffle pitch
0.1
HE with 100 mm
0 baffles pitch 1000
0.118 0.16 0.19 0.2190.2440.266 50 mm HE with
Mass Flow Rate (kg/second) 0 baffle pitch
0.118 0.16 0.19 0.219 0.244 0.266 50 mm
Figure 7: Variation of effectiveness with mass flow rate Mass Flow Rate(kg/sec)
of counter flow
The variations of overall heat transfer coefficient with Figure 9: Variation of Overall heat transfer coefficient
mass flow rate which is calculated by experimentally with mass flow rate of counter flow
observed data for parallel and counter flow heat
exchanger is shown in figure 8 and figure 9 The value of effectiveness for parallel and counter flow
respectively. The plot clearly shows that the heat arrangements are compare in plot for increasing mass
transfer coefficient increases by using triangular baffles flow rates are shown in the figure 10, 11 and 12 for all
in both set-ups as compare to heat exchanger without three experimental set up of heat exchanger without
baffles. However from two graphs it is also clearly seen baffles, with baffle pitches of 100 and 50 mm
that the heat transfer coefficient of triangular baffle heat respectively. From the plot it is clearly seen that the
exchanger with 50 mm pitch is more than 100 mm value of effectiveness for counter flow is more than
baffled pitch. So it can be concluded that using of baffles parallel flow for the all three set of heat exchanger. From
in heat exchanger heat transfer coefficient increases the graph it is seen that there is an optimum mass flow
however it also increases when pitch of baffles rate at which gap of effectiveness for parallel counter
decreases. flow is minimum
0.35
Parallel Flow 0.3
Parallel
4500 0.25 Flow of
Effectiveness
Overall Heat Transfer coeff.(w/m2k)
Mass Flow Rate(kg/sec) Figure 10: variation of effectiveness with mass flow rate
of parallel and counter flow of plane heat exchanger i.e.
without baffles
Figure 8: Variation of Overall heat transfer coefficient
with mass flow rate of parallel flow
2016, IRJET | Impact Factor value: 4.45 | ISO 9001:2008 Certified Journal | Page 1140
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395 -0056
Volume: 03 Issue: 08 | Aug-2016 www.irjet.net p-ISSN: 2395-0072
pitch
0.3 Triangular baffles of 100 and 50 mm pitches
100mm enhance the average heat transfer rate by 1.6
0.25 Counter
0.2 and 1.9 times in parallel flow and 1.48 and 1.67
Flow with
in counter flow that of smooth tube respectively.
0.15 baffles
We found that the insulation has a significant
0.1 pitch 100
effect on heat exchanger performance. From the
0.05 mm calculation it can be seen that in many
0 observations the heat loss by hot fluid is more
0.118 0.16 0.19 0.219 0.244 0.266 than the heat gain by cold fluid this is because of
Mass Flow Rate (kg/second) insulations provided is not sufficient to stop
heat loss.
From the results it can be concluded that the
Figure 11: variation of effectiveness with mass flow rate performance of triangular baffled heat
of parallel and counter flow of plane heat exchanger with exchanger is much better than that of smooth
baffles pitch 100 mm tube HE, therefore improvement in the energy
saving lead to validate its use in different
0.6 applications. Also similar results had been found
by Sarmad A. Abdal Hussein when he carried out
0.5 the investigation of double pipe heat exchanger
Parallel
by using semi-circular disc baffles.
Flow with
0.4 baffles
REFERENCES
Effectiveness
pitch
0.3 50mm
Counter [1] Sarmad A. Abdal Hussein (2015), Experimental
Flow with Investigation of Double Pipe Heat Exchanger by using
0.2 Semi Circular Disc Baffles, International Journal of
baffles
Computer Applications, Volume 115 No. 4,pp 13-17.
pitch 50
0.1
mm [2] Eaman Hassan Muhammad (2013), A Comparison of
0 the Heat Transfer Performance of a Hexagonal Pin Fin
with Other Types of Pin Fin Heat Sinks, International
0.118 0.16 0.19 0.219 0.244 0.266
Journal of Science and Research (IJSR),pp 1781-1788
Mass Flow Rate (kg/second)
[3] Abd-Elghanyand Afify, R. I.(1997), "Turbulence and
heat transfer measurements baffles in circular pipe",
Figure 12: variation of effectiveness with mass flow rate Engineering over doughnut-and-disc Research Journal,
of parallel and counter flow of plane heat exchanger with Vol. 52, pp1-20
baffles pitch 50 mm [4] Yong-Gang Lei et al., (2008) Design and Optimization
of heat exchanger with helical baffles, chemical
4. CONCLUSION Engineering science, 63, pp.4386-4395.
Experimental investigations of effectiveness and overall [5]Rane and Tandale (2003), Tubetube heat
heat transfer coefficient of double pipe heat exchanger exchangers Filed PCT/IN03/00377
without triangular baffles and with baffles spacing of 100
[6] Gajanan P Nagre, A. V. Gadekar (2013), Design and
mm and 50 mm carried out for both parallel and counter
Thermal Performance Analysis of Shell and Tube Heat
flow. The following conclusion could be made:
Exchanger by Using CFD-A Review International Journal
of Science and Research (IJSR), ISSN (Online): 2319-
The effectiveness, heat transfer coefficient and
7064,pp 953-955
heat transfer rate increases with the decrease in
baffle spacing and baffled tube heat exchanger
2016, IRJET | Impact Factor value: 4.45 | ISO 9001:2008 Certified Journal | Page 1141