A60ADLS

You might also like

Download as rtf, pdf, or txt
Download as rtf, pdf, or txt
You are on page 1of 1

Air System Design Load Summary for CORRIDOR 4b

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:56AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.2 C / 30.0 C HEATING OA DB / WB 12.0 C / 10.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 47 m 15988 - 47 m - -
Wall Transmission 0 m 0 - 0 m 0 -
Roof Transmission 267 m 3057 - 267 m 2161 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 47 m 4582 - 47 m 1615 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 211 m 5206 - 211 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 11738 W 8216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 52 4512 6954 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 8% / 5% 3450 348 0% 0 0
>> Total Zone Loads - 46575 7302 - 3776 0
Zone Conditioning - 44758 7302 - 257 0
Plenum Wall Load 20% 0 - 0 0 -
Plenum Roof Load 70% 7132 - 0 0 -
Plenum Lighting Load 30% 3521 - 0 0 -
Return Fan Load 4600 L/s 0 - 4600 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 4600 L/s 426 - 4600 L/s -426 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 466 - 1% 38 -
>> Total System Loads - 56302 7302 - -131 0
Central Cooling Coil - 56302 7308 - 0 0
>> Total Conditioning - 56302 7308 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.50 Page 1 of 1