Professional Documents
Culture Documents
I M P A C T o F V o L T A G e P H A S e A N G L e C H A N G e S o N L o W - V o L T A G e R I D e - T H R o U G H P e R F o R M A N C e o F D G - U N I T S
I M P A C T o F V o L T A G e P H A S e A N G L e C H A N G e S o N L o W - V o L T A G e R I D e - T H R o U G H P e R F o R M A N C e o F D G - U N I T S
I M P A C T o F V o L T A G e P H A S e A N G L e C H A N G e S o N L o W - V o L T A G e R I D e - T H R o U G H P e R F o R M A N C e o F D G - U N I T S
Paper 329
The approach is to first apply a fault in the grid, and then constant-impedance loads. It is assumed, however, that
make separate records of the voltage magnitude and the this approach of applying change in in voltage amplitude
phase angle time series on the DG bus. The recorded time only will not reflect real grid fault situations. Therefore
series are used as input to new simulations where the grid this case will not be discussed further.
is replaced with a voltage source with controllable voltage
magnitude and phase angle on the DG bus. In this way Earth fault with residual voltage
separate simulations with change only in voltage A 3-phase symmetrical fault is applied on BUS66_1 of the
magnitude and only in voltage phase angle can be run, and system model. The fault has a resistive character. The
corresponding DG-responses can be recorded. transition resistance of the fault has been adjusted to give a
significant change in both amplitude and phase angle of
SIMULATION MODEL the voltage throughout the system (towards the DG-unit).
The fault clearing time is set at 250 ms in all simulations.
The system model under study is depicted in Figure 1. The This case is named Case 1 in the following. The next case,
system consists of a simple 132 and 66 kV radial regional Case 2, implies that a 3-phase symmetrical fault is applied
grid, a 22 kV high voltage distribution grid and a 300 kV on BUS22_2 of the system under study. Besides the same
"stiff grid" (swing bus). There are two loads in the system, comment apply as for Case 1.
at BUS22_1 and BUS66_1, respectively. The loads are
modeled as constant impedance loads. The synchronous The faults in Case 1 and Case 2 are applied one at a time.
generator is connected to the 22 kV grid via a 0.69/22 kV The generator is connected to the grid in these cases. The
transformer. Data for lines, transformers, loads and power production of the generator (SN=5 MVA) is set at
generator are given in Appendices 1, 2, 3, and 4. 4 MW and 0 Mvar for all cases. The AVR is operating in
normal voltage-control mode. The fault is applied at t=1 s
in the simulations.
Bus132_3
Bus132_2
Bus22_1
Bus66_2
Bus66_1
Bus22_2
Results
L1 T2 L2 T3 L3 Modelling and simulations of the system under study have
T1
Bus_GEN
L4 been performed in SIMPOW [7]. Selected results from
Load 1 Load 2
Bus132_1 the dynamic simulations are given in the following figures.
DG T4
~ S = 5 MVA
n
Bus_300 Voltage amplitude and phase angle
The change in voltage amplitude in relation to time on the
SWING
generator bus, Bus_GEN, as a result of the faults applied
Figure 1. Single line diagram of system under study. under Case1 and Case 2, respectively, is showed in Figure
2. The corresponding change in voltage phase angle is
The synchronous generator model includes brushless given in Figure 3.
excitation and an automatic voltage regulator. The
excitation system model corresponds to model Type
AC8B in Ref. [6]. Data for the excitation system are given
in Appendix 5. The generator is operated with constant
mechanical torque for all of the dynamic simulation cases
studied, i.e. no turbine/governor model is included.
The results described in this paper have been obtained APPENDIX 3. Load data
within the SINTEF-project "ETEST mobile short-circuit
laboratory" supported by The Research Council of NAME Pload Qload
Norway. [MW@ [MVAr@
Load 1 20 7.5
Load 2 16 4
Thanks also to Lars Lindquist in SIMPOW-team,
Vsters, Sweden, for giving advice in connection with APPENDIX 4. DG model parameters
simulations.
Parameter DG model
Xd [pu] 2.04
REFERENCES Xd' [pu] 0.238
Xd [pu] 0.143
Xq [pu] 1.16
[1] Statnett, 2008, Veileder for Funksjonskrav i Xq " [pu] 0.137
kraftsystemet, FIKS, Statnett SF, Oslo, Norway, 79 ra [pu] 0.00219
Xl [pu] 0.13
pages. (Norwegian grid codes for the transmission Td0' [s] 2.38
system). Td0" [s] 0.0117
Tq0" [s] 0.11
[2] BDEW, June 2008, Technical Guideline Generating H [s] 1.0
PlantsConnected to the medium-Voltage Network, V1D [pu] 1.0
BDEW, Berlin, Germany, 130 pages. SE1D [pu] 0.1
V2D [pu] 1.2
[3] Svenska Kraftnt, December 2005, Affrsverket SE2D [pu] 0.3
svenska kraftnts freskrifter och allmnna rd om
drfitskerhetsteknisk utforming av APPENDIX 5. Voltage regulator data
produkstionsanlggningar. AcKFS 2005:2. Svenska
Kraftnt, Vllingby, Sweden, 20 pages. Parameter Description
[4] ENTSO-E. ENTSO-E AISBL, 2012, ENTSO-E Draft KP [pu] 120.5 PID proportional gain
KI [pu] 165.5 PID integral gain
Network Code for Requirements for Grid Connection TI [s] 1 PID integral time constant
applicable to all Generators, Brussels, Belgium. KD [pu] 25 PID derivative gain
TD [s] 0.01 PID derivative time constant
[5] IEC 61400-21, 2008, Wind turbines. Part 21: KA [pu] 1 Voltage regulator gain
Measurement and assessment of power quality TA [s] 0 Regulator time constant
VRmax [pu] 35 Maximum regulator output
characteristics of grid connected wind turbines.IEC, VRmin [pu] 0 Minimum regulator output
Geneva, Switzerland. KE [pu] 1 Exciter constant
[6] IEEE Std 421.5, 2005, IEEE Recommended practice TE [s] 0.5 Exciter time constant
SE1 [pu] 1.346 Saturation curve value at point 1
for Excitation System Models for Power System E1 [pu] 2.222 Voltage value at point 1
Stability Studies, IEEE, New York, USA. SE2 [pu] 1.9 Saturation curve value at point 2
E2 [pu] 2.962 Voltage value at point 2
[7] STRI AB, 2004, SIMPOW User Manual 11.0,
Copyright STRI AB 2004, revision date 2010-09-24.
STRI AB, Vsters, Sweden.