Note: Consult with power team (NCELL/HW) if MCCB rating is 3 phase 20A or below.
7. Change Battery Capacity Default Value: 490AH
Setting Value: as per installed battery
(340 AH (=2x170AH) if only 2 battery bank and 680AH (4x170AH)
if 4 battery bank)
Note: Total Capacity of Battery e.g. If there is 4 banks of 140AH North Star Blue battery,
Setting will 560AH (140 * 4).
8. Relate Bus Bar Under Voltage in 6 number Port Relay.
[Alarm configuration Site Summary Bas Bar undervoltage
from N/A to 6]
9. Relate HEX Fault in 1 number Port Relay.
[Alarm configuration HEX HEX Fault from 6 to 1]
10. Alarm Information of ICC500(FCB)
Port
Port
CARD ICC310 Alarm Description Voltage Sevarity
BTS *
End
BTS/SMPS/PIU alarms
EMUB S3- DO_3 COM PSU Fault(Rectifier) PSU Fault(Rectifier) Low Minor
EMUB S4- DO_4 COM Fuse Fault Fuse Fault Low Critical
EMUB S8- DO_8 COM SPD Fault SPD Fault Low Major
Port BTS will depend of BTS vendor type. If Huawei port will be as
per above and if ZTE as per below
Color
Old name New name
code
Main power
white-
supply has a Mains Failure
blue
fault alarm
Rectifier white-
Rectifier Failure
module alarm orange
white-
Flood alarm Temperature Alarm
green
white-
Battery alarm Battery alarm
brown
white-
Smog alarm Load on DG
grey
Door alarm Red-blue
Over-voltage
red-
alarm of main Over Voltage Alarm
orange
power input
Battery low- red-
Battery Discharge Alarm
voltage alarm green
11. Change Site name /Date/ Time and Set Actual Time, Date and
Site [Site Config System Date Time and Site Information]
For any kind of doubt during installation and commissioning Please
contact with Power team of HW Subash C Adhikari 9851156083,
Firoj Khan 9802055452,Ncell Krishna Manandhar-
9802100232,Ncell Dipendra Shah- 9802100171