PackagedChillerReport:DoNotEdit
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard
550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Unit Performance
Percent Full Load Capacity, % 100 75 50 25
Percent Full Load Power, % 100.0 62.9 34.9 15.5
Unloading Sequence A A A A
Cooling Capacity, kW 1317.1 987.8 658.5 329.3
Unit Power Input, kW 414.5 260.7 144.5 64.4
Efficiency, kW/kW 3.18 3.79 4.56 5.11
Evaporator Data
Fluid Entering Temperature, C 12.0 10.4 9.2 7.9
Fluid Leaving Temperature, C 7.0 7.0 7.0 7.0
Fluid Flow Rate, l/s 62.96 62.96 62.96 62.96
Fouling Factor, (sqm-K)/kW 0.0176 0.0176 0.0176 0.0176
Condenser Data
Entering Air Temperature, C 35.0 27.0 19.0 13.0
Values given are interpolated and are not directly measurable under laboratory conditions.
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard
550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.