CONDENSATE TRAYS & PIPELINES

Maintenance Frequency
Description Comment Daily Monthly Quarterly H Yearly Yearly
1. Isolate electrically and x
System. hydraulically.

2. Loose Remove using wet and dry x


debris. vacuum cleaner.

3. a) Check condition and x


Condens repaint as necessary
ate Tray. b) Close condensate trap and
fill tray to maximum with
4. Disinfect tray and trap with x
clean fresh water.
Disinfecti addition of sodium
on. hypochlorite solution to
achieve free residual chlorine
reserve of 15 mg/litre.

5. Return Drain and thoroughly flush x


to tray and trap until no water
service. remains in condensate tray.
Refill trap with fresh water.
NOTES
Isolation of electrical
supply should be in
accordance with
HASAWA
requirements.
Ensure that adequate
air-break exists between
condensate trap and
drain to prevent
siphoning.

Note: Free chlorine


reserve should be
maintained at a level of
15 mg/litre for four
hours.