(Secl-r0-Hv-CA-tbb-0001 - Rev - 1) (Hvac & Plumbing Calculation For Gis Substation)
(Secl-r0-Hv-CA-tbb-0001 - Rev - 1) (Hvac & Plumbing Calculation For Gis Substation)
SECL DISTRIBUTION
PROJECT V
CIVIL V
ARCH. V
ELEC. V
INST.&CONT. V
FIRE FIGHTING V
HVAC O
MECH. V
PIPING V
PROCESS V
VIBRATION V
NOISE V
MATERIAL V
PERPORMANCE
V
GROUP
PROCURE. V
CONST. V
QA/QC V
HSE V
PRECOMM.-
V
COMM.
CONTENTS
1. GENERAL ..................................................................................................................................... 4
1.1. SCOPE.................................................................................................................................... 4
7. APPENDICES ............................................................................................................................. 27
1. GENERAL
1.1. SCOPE
This calculation defines the requirements for detail design and construction of Heating,
Ventilating and Air Conditioning (hereinafter referred to as HVAC) system and plumbing
system, which shall be applied to GIS Substation for Saudi Aramco Third Party
Cogeneration Project in the Ras Tanura, Kingdom of Saudi Arabia(Red Sea).
1.2. OBJECTIVE
To determine the cooling and heating loads in GIS Substaion and to size HVAC
equipment to provide the suitable environmental conditions for personnel and
equipments
1.3. REFERENCES
This calculation is performed in accordance with the following codes, standards and
project specifications. Their latest editions at time of contract award shall be applied
Language : English
Unit : S.I Unit
2. DESIGN CONDITIONS
Note ; 1) Selection for Air Cooled Condensing Units (ACCU) and Split System Air
Conditioning Units (SAC) shall be as per 106 F (41 C) DB.
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBB-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
1) HVAC System load calculation shall be done in accordance with ASHRAE handbook
methods and computer generated using Carrier E20-II used calculation software. A
psychometric analysis shall be provided for each system with cooling and/or heating
load calculations. A 10% safety margin shall be applied for HVAC load calculation.
This analysis shall be include but not limited to:
A. Mixing temperature of outside and return air
B. Entering air temperature and enthalpy at coil
C. Leaving air temperature and enthalpy at coil
D. Outside air design condition
E. Building R and U values
F. Internal heat gains for installed equipment
G. Internal heat gain basis for Lighting and other miscellaneous equipment
H. Supply air volumes
I. Ventilation air volumes
2) Heat load calculation shall be carried out in accordance with good engineering
practice and Carrier E20-II, HAP ver. 4.4.
Minimum ventilation rates shall be as per table below or latest issue of ASHRAE 62 and
SBC-501.
Ventilation and Exhaust Rates
Application Minimum Air Flow Rate
Toilets 72 cfm (36 l/s) per water closet/urinal
Shower Rooms 48 cfm (24 l/s) per shower head
Locker rooms, Pantry,
Ablution, Janitor Room,
Normal storage areas,
0.5 cfm r ft2 (2.6 l/s per m2) floor area
Dressing room, Lunch room,
Water heater rooms, Fire
truck bay
Trash Storage, Workshop,
1.5 cfm per ft2 (7.5 l/s per m2) floor area
Chemical Storage
Office areas and similar 20 cfm (10 l/s) per person
rooms
Kitchen (General Area) 0.7 cfm per ft2 (3.5 l/s per m2) floor area
Minimum ventilation for Battery Rooms shall be 10 air changes per hour.
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBB-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
Heat Emission
Typical Application Remarks
(Watts/ m2)
Based on ASHRAE Fundamentals
Office 12 Handbook 2013
Chapter 18 Table 2
Electrical / Mechanical 16
Laboratory 15
Restroom 10
Corridor 5
Workshop 20
Warehouse 15
Conference / Meeting /
15
Training
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBB-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
3.3. HEAT DISSIPATION FROM CONTROL & ELECTRICAL PANEL AND EQUIPMENTS
G03 Protection
4450 Watts - -
Panel Room
G04 SA Room 5900 Watts - -
Notes : 1) Heat Emission from Electrical Panel and Equipment are informed from Electric
division.
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBB-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)
Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)
Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)
d/ 0.54
U (W / m2K) 1.852
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBB-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
4.4. FLOOR
Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)
d/ 0.493
U (W / m2K) 2.028
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBB-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
Total(b) 831
Total (a)+(b) 1436 1450
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBB-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
Refer to Appendix 1
Cooling capacity Sensible capacity : 71.2 kW
Air System Size 1
(qCA) Total Capacity : 104.9 kW
Summary
Cooling Coil
Type : Direct expansion
(qCA)
1
Sensible capacity : 71.2 kW
Total Capacity : 104.9 kW
Entering Air Temperature : 32.1 DB, 21.9 WB
Leaving Air Temperature : 11.9 DB, 11.5 WB
Total Input
50.5 kW
Power for unit
Ventilation 1) Ventilation Fan volume by room sensible heat load (QS) A : Area of the
Airflow Ventilation Fan volume for this room by sensible related room,
Rate (Q) heat load [Unit : m2]
a) Heat emission (qs)
Safety Factor: 10 %
- Electrical Heat emission (qe) : 10800 W(10.8 kW)
- Fabric and Solar (qf) : 4077 W (4.1 kW) Specific heat (Cp)
: 1005 J/kg.C
- Total : qs = qe+qf
= 10.8 + 4.1 = 14.9 kW Air density (p)
: 0.0011 kg/liter
b) Outside Air Temperature (To) : 41.0 CDB (Density of air at 41 C)
c) Room Temperature (Tr1) : 46.0 CDB
qe : Refer to 3.3
d) Electrical Room Temperature (Tr2) : 27.0 CDB Heat Dissipation
e) Temperature difference (dT= Tr1 - Tr2) : 19.0 CDB from Control &
Q s = qs/(Cp x x dT) x S.F Electrical Panel and
Equipments
= 14.9 x 1000 / ( 1005 x 0.0011 x 19.0 ) x 1.1
qf : Refer to
= 780 L/s 780 L/s
APPENDIX 2.
2) Therefore, ventilation airflow rate (Q) : 780 L/s Space Design Load
Pressure Drop Part Pressure Drop Summary
Static Part Name
(Pa/Part) Qty (Pa)
Pressure BPD : Blast Protection
(SP) Air device 30 2 60 Damper
Damper 30 2 60
Duct 1.0 35 35
Fitting - - 26
Fan
Specificatio Equip. No. : R0TBB-JE001
ns Quantity : 1 Set
Location : B01-Cable Room
Type : Centrifugal, Duct In-Line
Capacity : 780 L/s 200 Pa x 0.55 kW
1
7. APPENDICES
GIS SUBSTATION
APPENDIX 1
HVAC LOAD CALCULATION OUTPUT DATA (E20-II)
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS
GIS SUBSTATION
GIS SUBSTATION
(R0TBB-JA001A/B)
Air System Sizing Summary for GIS BUILDING
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
GIS SUBSTATION
Zone L/s ................................Sum of space airflow rates Calculation Months ........................................... Jan to Dec
Space L/s ............................Individual peak space loads Sizing Data ....................................................... Calculated
Total coil load ............................................................ 104.9 kW Load occurs at ...................................................... Jul 1500
Sensible coil load ........................................................ 71.2 kW OA DB / WB ...................................................... 41.0 / 27.0 C
Coil L/s at Jul 1500 ..................................................... 2650 L/s Entering DB / WB .............................................. 32.1 / 21.9 C
Max block L/s ............................................................. 2790 L/s Leaving DB / WB ............................................... 11.9 / 11.5 C
Sum of peak zone L/s ................................................ 2790 L/s Coil ADP ...................................................................... 10.1 C
Sensible heat ratio .................................................... 0.678 Bypass Factor ........................................................... 0.100
m/kW ............................................................................ 4.3 Resulting RH .................................................................. 41 %
W/m .......................................................................... 232.6 Design supply temp. .................................................... 12.0 C
Water flow @ 5.6 K rise .............................................. N/A Zone T-stat Check ..................................................... 2 of 2 OK
Max zone temperature deviation ................................... 0.0 K
Max coil load ............................................................... 25.5 kW Load occurs at ...................................................... Des Htg
Coil L/s at Des Htg ..................................................... 1813 L/s W/m ............................................................................ 56.5
Max coil L/s ................................................................ 1813 L/s Ent. DB / Lvg DB ............................................... 15.6 / 27.3 C
Water flow @ 11.1 K drop........................................... N/A
Actual max L/s ............................................................ 2790 L/s Fan motor BHP............................................................ 7.48 BHP
Standard L/s ............................................................... 2784 L/s Fan motor kW ................................................................ 7.5 kW
Actual max L/(s-m) ..................................................... 6.19 L/(s-m) Fan static .................................................................... 1450 Pa
1. Summary
Ventilation Sizing Method ........................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ....................................................................... 1327 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GIS-G02-HVAC ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.8 C / 26.9 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 123 m 888 - 123 m 596 -
Roof Transmission 88 m 464 - 88 m 249 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 6 m 134 - 6 m 118 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 1521 W 1521 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1320 W 1320 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 1089 1415 - 1135 -35
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 542 141 10% 210 -4
>> Total Zone Loads - 5957 1556 - 2308 -39
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GIS-G02-HVAC ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 38 0.439 - 283 - 186
NE EXPOSURE
WALL 53 0.439 - 397 - 255
NW EXPOSURE
WALL 32 0.439 - 209 - 155
DOOR 6 1.703 - 134 - 118
H EXPOSURE
ROOF 88 0.257 - 464 - 249
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' GIS-G03-PROTECTION RM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1900 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.3 C / 26.4 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 37 m 288 - 37 m 180 -
Roof Transmission 50 m 293 - 50 m 140 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 6 m 112 - 6 m 112 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 855 W 855 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4450 W 4450 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 600 0 10% 43 0
>> Total Zone Loads - 6599 0 - 475 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' GIS-G03-PROTECTION RM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 22 0.439 - 161 - 104
NW EXPOSURE
WALL 16 0.439 - 127 - 75
DOOR 6 1.703 - 112 - 112
H EXPOSURE
ROOF 50 0.257 - 293 - 140
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' GIS-G01-GIS ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.2 C / 26.8 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 541 m 3979 - 541 m 2613 -
Roof Transmission 215 m 1150 - 215 m 606 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 24 m 507 - 24 m 457 -
Floor Transmission 215 m 5307 - 215 m 4785 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 3707 W 3706 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3315 W 3315 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1796 0 10% 846 0
>> Total Zone Loads - 19760 0 - 9308 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' GIS-G01-GIS ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 218 0.439 - 1718 - 1055
DOOR 2 1.703 - 46 - 41
SW EXPOSURE
WALL 124 0.439 - 950 - 601
NW EXPOSURE
WALL 100 0.439 - 664 - 485
DOOR 20 1.703 - 416 - 375
NW EXPOSURE
WALL 98 0.439 - 647 - 473
DOOR 2 1.703 - 46 - 41
H EXPOSURE
ROOF 215 0.257 - 1150 - 606
TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' GIS-G04-SA ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.3 C / 26.6 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 80 m 784 - 80 m 459 -
Roof Transmission 99 m 698 - 99 m 331 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 6 m 170 - 6 m 133 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 106 m 867 - 106 m 391 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 1711 W 1711 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5900 W 5900 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1013 0 10% 131 0
>> Total Zone Loads - 11142 0 - 1445 0
TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' GIS-G04-SA ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 43 0.439 - 417 - 247
NW EXPOSURE
WALL 37 0.439 - 367 - 212
DOOR 6 1.703 - 170 - 133
H EXPOSURE
ROOF 99 0.257 - 698 - 331
GIS SUBSTATION
B01-CABLE ROOM
(Space Design Load Summary)
Space Design Load Summary for GIS-Cable Room
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
GIS SUBSTATION
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GIS-B01-CABLE ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 26.9 C / 20.3 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 48.5 C OCCUPIED T-STAT 6.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 0 m 0 - 0 m 0 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 3707 W 3706 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 371 0 10% 0 0
>> Total Zone Loads - 4077 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GIS-B01-CABLE ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
GIS SUBSTATION
APPENDIX 2
PRESSURIZATION AIR VOLUME CALCULATION
CALCULATION EXAMPLE OF FLOW RATE OF SUPPLY AIR FOR PRESSURIZATION
(Based on ASHRAE Application, Chapter 53, Equation 8 & 9, edition on 2011)
The air flow rate, through a construction crack, door gap, or other flow path is proportional to the pressure
difference across that path raised to the power n.
For a flow path of fixed geometry, n is theoretically in the range of 0.5 to 1.
However, for all flow paths, except extremely narrow cracks, n = 0.5, and the flow can be expressed as ;
Q = CA(2p/)
where,
Q = volumetric air flow rate
C = flow coefficient
A = flow area (called leakage area)
p = pressure difference across the flow path
= density of air entering the flow path
The flow coefficient depends on the geometry of the flow path, as well as on turbulence and friction.
In the present context, the flow coefficient is generally in the range of 0.6 to 0.7.
For = 1.2 kg/, and C = 0.65, the flow equation above can be expressed as ;
Q = 0.8392 Ap
where,
Q = volumetric air flow rate (/s)
A = flow area (called leakage area) ()
p = pressure difference across the flow path (Pa)
Total leakage area should be summed with data of each architectural component as below ;
Room name : G01-GIS ROOM (GIS BUILDING_RTR) Room pressure (Pa) : 25
1. Calculation leakage air flows thru structure
Best Leak area
Component Units Quantity
estimate (cm2)
General cm2/m2 1.80
Ceiling
Drop cm2/m2 0.19 214.5 40.8
Cast-in-place concrete cm2/m2 0.50 605.7 302.9
Clay brick cavity wall, finished cm2/m2 0.68
Walls (exterior) Pre-cast concrete panel cm2/m2 1.20
Low-density concrete block, unfinished cm2/m2 3.50
Low-density concrete block,painted or stucco cm2/m2 1.10
Floor Concrete slab cm2/m2 0.40 214.5 85.8
Masonry, not caulked cm2/m2 6.50
Masonry, caulked cm2/m2 1.30
Window frame
Wood, not caulked cm2/m2 1.70
Wood, caulked cm2/m2 0.30
Double horizontal slider, not weatherstripped cm2/lmc 1.10
Double horizontal slider, wood weatherstripped cm2/lmc 0.55
Double horizontal slider, aluminum weather stripped cm2/lmc 0.72
Double hung, not weatherstripped cm2/lmc 2.50
Double hung, weatherstripped cm2/lmc 0.65
Windows
Single horizontal slider, weatherstripped cm2/lmc 0.67
Single horizontal slider, aluminum cm2/lmc 0.80
Single horizontal slider, wood cm2/lmc 0.44
Single horizontal slider, wood clad cm2/lmc 0.64
Single-hung, weatherstripped cm2/lmc 0.87
Total Area 429.4
Leakage air volume to be maintain 25Pa (m /hr) 770.0
Abbreviations
= gross area in square meters, ea = each, lmc = linear meter of crack, lms = linear meter of sash
The data of other component not defined above will be referred in ASHRAE Fundamentals 2001, chapter 26, table 1
GIS SUBSTATION
APPENDIX 3
PSYCHROMETRIC CHART
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS
GIS SUBSTATION
GIS SUBSTATION
(R0TBB-JA001A/B)