Professional Documents
Culture Documents
Jeneratör Montaj El Ki̇tabi
Jeneratör Montaj El Ki̇tabi
MONTAJ TAVSYELER
EL KTABI
Bu Kullanma ve Bakm El kitab sizlere Aksa jeneratr sistemini tantmak amacyla hazrlanm ve gelitirilmitir.
Ayrca alm olduunuz jeneratrle ilgili genel bilgiler, tablolar ve emalarda verilmitir.
Genel emniyet tedbirlerini almadan jeneratrnz asla altrmaynz, bakm ve onarmn yapmaynz.
Aksa nceden haber vermeden kullanm kitabnda yapaca deiiklik hakkn sakl tutar.
1. GR............................................................................................................................................ 1
2. EMNYET.................................................................................................................................... 1
2.1. Genel............................................................................................................................................................................ 1
2.2. Yerleim, Tama ve ekme............................................................................................................................ 1
2.3. Yangn ve patlama................................................................................................................................................. 2
2.4. Mekanik....................................................................................................................................................................... 2
2.5. Kimyasal....................................................................................................................................................................... 2
2.6. Grlt........................................................................................................................................................................ 3
2.7. Elektriksel.................................................................................................................................................................... 3
2.8. Elektriksel arpmalara kar ilk yardm........................................................................................................ 3
3. ODA BOYUTLANDIRMASI, YERLETRME, KALDIRMA............................................ 4
3.1. Genel............................................................................................................................................................................ 4
3.2. Kabin............................................................................................................................................................................. 4
3.3. Jeneratrn tanmas.......................................................................................................................................... 4
3.4. Jeneratr yerinin seimi...................................................................................................................................... 5
3.5. Kabinli Jeneratr Grubunun Ak Sahada Yerletirilmesi ve Kurulumu................................... 5
3.6. Jeneratr Temeli ve taban................................................................................................................................ 6
3.7. Oda dizayn klavuz notlar................................................................................................................................ 7
4. YAKIT SSTEM.........................................................................................................................12
4.1. Genel............................................................................................................................................................................ 12
4.2. Dizel yaktn zellii............................................................................................................................................... 12
4.3. Dizel yakt zellik tanmlar............................................................................................................................... 13
4.4. ase - depo yakt tank........................................................................................................................................ 13
4.5. Ara tanksz yakt sistemi..................................................................................................................................... 13
4.6. Ara tankl yakt sistemi........................................................................................................................................ 13
4.7. Gnlk servis yakt tank..................................................................................................................................... 14
4.8. Byk hacimli depolama tanklar................................................................................................................... 14
4.9. Yakt hatt tanmlamas........................................................................................................................................ 14
4.10. Yakt geri dn hatlar....................................................................................................................................... 16
4.11. Elektrikli yakt transfer pompalar.................................................................................................................. 16
5. EGZOZ SSTEM.......................................................................................................................17
5.1. Egzoz sisteminde olmas gerekenler ve dikkat edilmesi gereken hususlar............................. 18
5.2. Egzoz boru tesisat dizayn................................................................................................................................ 19
6. SOUTMA SSTEM................................................................................................................24
6.1. Genel............................................................................................................................................................................ 24
6.2 Radyatr soutmal gruplar.............................................................................................................................. 24
6.3. Uzak radyatrle soutulmu sistemler....................................................................................................... 24
6.4. Havalandrma........................................................................................................................................................... 25
6.5. Soutma suyu ve ileme tabii tutulmas.................................................................................................... 28
6.6. Motoru stma.......................................................................................................................................................... 29
6.7. Yanma havas............................................................................................................................................................ 29
7. YALAMA YAI...................................................................................................................... 29
7.1. Ya performans zelikleri.................................................................................................................................. 29
7.2 Cummins motorlar iin ya tavsiyesi.......................................................................................................... 29
7.3 John Deere dizel motorlar iin ya tavsiyesi........................................................................................... 29
7.4 Doosan dizel motorlar iin ya tavsiyesi................................................................................................... 30
7.5 Mitsubishi dizel motorlar iin ya tavsiyesi.............................................................................................. 30
8. ELEKTRKL START SSTEMLER......................................................................................... 30
8.1. Ak sistemleri.......................................................................................................................................................... 30
9. EBEKE VEYA JENERATRN YKE TRANSFER....................................................... 30
9.1. OTS panosu ve panonun yeri, yerleimi.................................................................................................. 30
9.2. OTS standartlar..................................................................................................................................................... 31
9.3. OTS G anahtarlama eleman..................................................................................................................... 31
10. ELEKTRK TESSATI VE KABLO.......................................................................................... 31
10.1. Genel............................................................................................................................................................................ 31
10.2. Kablo kesiti seimi................................................................................................................................................. 32
10.3 Kablolarn montaj metotlar............................................................................................................................. 32
10.4. Kablo kanallar.......................................................................................................................................................... 32
10.5. Koruma........................................................................................................................................................................ 32
10.6. Ykleme...................................................................................................................................................................... 32
10.7. G faktr............................................................................................................................................................... 33
10.8. Paralel alma.......................................................................................................................................................... 33
10.9. Topraklama............................................................................................................................................................... 33
11. SES ZALASYONU................................................................................................................... 35
11.1 Susturucular.............................................................................................................................................................. 35
11.2 Kabinler........................................................................................................................................................................ 35
11.3 Dier ses drcler......................................................................................................................................... 35
12. SALIK VE EMNYET............................................................................................................. 36
12.1 Yangndan korunma............................................................................................................................................. 36
12.2 Egzoz gazlar.............................................................................................................................................................. 36
12.3 Hareketli paralar................................................................................................................................................... 37
12.4 Tehlikeli voltaj.......................................................................................................................................................... 37
12.5 Su.................................................................................................................................................................................... 37
12.6 Soutma svs ve yakt......................................................................................................................................... 37
13. YK KARAKTERSTKLER................................................................................................... 37
13.1. Genel............................................................................................................................................................................ 37
13.2 Yk karakteristikleri............................................................................................................................................... 37
13.3. Motora yol verme................................................................................................................................................. 37
13.4. Olaan d ykler.................................................................................................................................................. 38
13.5. Dengesiz ykler......................................................................................................................................................... 39
13.6. Alternatr balants................................................................................................................................................ 39
13.7. zolasyon testi............................................................................................................................................................. 39
14. RMORKLU JENERATRLERN EKLMES....................................................................... 39
15. MTERNN SORUMLULUKLARI.......................................................................................... 40
1. GR 2. EMNYET
Aksa Jeneratr; soutma suyu ve antifrizi, yakt, yalama 2.1 Genel
ya ve arjl aknn salanmas durumunda, gtrl- Jeneratr doru kullanlmas halinde tamamen gvenli
d yerde hemen devreye verilecek ekilde tasarlan- olacak ekilde tasarlanmtr. Bununla birlikte gvenlik
mtr. sorumluluu jeneratr kuran, ileten ve bakmn ya-
Uzun yllarn verdii deneyim ile AKSA, verimli, gveni- pan kiilere aittir. Eer belirtilen gvenlik nlemleri uy-
lir ve kaliteli jeneratrler retir. gulanm ise kaza ihtimali ok azdr. Herhangi bir teknik
Bu Montaj El Kitab, kullancnn jeneratr kolayca operasyon veya ilem yapmadan nce gerekli emniyeti
montaj yapmasna yardm amacyla hazrlanmtr, ona- salamak operasyon veya ilemi yapan kiiye aittir. Je-
rm kitab deildir. Bu kitapta verilen tavsiye ve kural- neratr yalnzca yetkili ve eitimli kiiler tarafndan a-
lara uyulmas halinde jeneratr uzun sre maksimum ltrlabilir.
performans ve verimde alacaktr. Bu nedenle aada
yazl tavsiyelere uyulmas uygun olacaktr. Uyarlar
1) Kirli ve tozlu ortamda jeneratrn dzenli alma- ! Jeneratre bakm yapmadan veya jeneratr altr-
sn salamak amacyla daha sk bakm yapmaya dikkat madan nce kitaptaki tm uyarlar okuyunuz ve an-
edilmelidir. laynz.
2) Her zaman ayarlar ve onarmlar, bu ii yapmak iin ! Bu kitaptaki prosedr, talimat ve gvenlik nlemleri-
yetkili ve eitimli bir kii tarafndan yaplmaldr. ne uyulmamas halinde kaza ve yaralanmalarn artmas
3) Her jeneratr, asesi zerine yaptrlm etiket ze- muhtemeldir.
rinde gsterilen bir model ve seri numarasna sahiptir. ! Bilinen emniyetsiz bir durumda jeneratr asla al-
Ayrca bu etiket zerinde jeneratrn imalat tarihi, geri- trmaynz.
limi, akm, kVA cinsinden gc, frekans, g faktr ve ! Eer jeneratrde emniyetsiz bir durum var ise, tehlike
arl verilmitir. Bu etiket bilgileri yedek para siparii, uyars koyunuz ve aknn negatif (-) kutbunun ba-
garantinin ilemesi veya servis salanmas iin gereklidir. lantsn keserek bu olumsuz durum dzeltilene kadar
4) Tavsiye edilen yalama ya, soutma suyu ve yaktn jeneratrn almasn engelleyiniz.
kullanlmas. ! Jeneratre bakm veya temizlik yapmadan nce ak-
5) Orijinal motor jeneratr paralarnn kullanlmas nn negatif (-) kutbunun balantsn kesiniz.
6) Aksa yetkili servislerinin kullanlmas ! Jeneratr standartlara uygun ekilde kurulmal ve a-
7) Tavsiye edilen emniyet ve montajla ilgili tedbirlerin ltrlmaldr.
alnmas
2.2 Yerleim, Tama ve ekme
Kitapta 3. ve 13. Blm jeneratrn yerletirilmesi,
tanmas ve ekilmesi konularn kapsamaktadr. Jene-
ratr tamadan, kaldrmadan, yerletirmeden veya
rmorklu jeneratr ekmeden nce bu blm oku-
yunuz. Aadaki emniyet tedbirlerini dikkate alnz.
Uyarlar
! Elektriksel balantlar, ilgili standartlara uygun ekilde
yapnz. Bu standartlara topraklama ve toprak hatalar
dahildir.
! Jeneratrler iin yaplan yakt depolama sistemlerinin
ilgili kodlara, standartlara ve dier gereklere uygun e-
ekil 1.1. AKSA Jeneratr Grup Etiketi kilde kurulduundan emin olunuz.
! Motor egzoz gazlar personel iin tehlikelidir. Kapal
Herhangi bir ihtiya durumunda Aksa Servis ve Yedek mahallerde bulunan btn jeneratrlerin egzoz gaz-
para Sirketini veya yetkili bayisini araynz. lar ilgili standartlara uygun szdrmaz siyah borular ile
darya atlmaldr. Scak egzoz susturucusu ve egzoz
borular yanabilecek maddelerin temas ve personelin
1
dokunmasna kar korunmaldr. Egzoz gaznn tehlike- den uzak tutunuz. Kvlcm veya ark, yakt tututurabilir.
siz olarak dar atlmasn salaynz ! Motor alyor iken yakt tankn doldurmaktan ka-
! Jeneratr, alternatr ve motor kaldr- nnz.
ma halkalarn kullanarak kaldrmaynz. ! Yakt sisteminde yakt sznts varsa jeneratr al-
Jeneratr kaldrmak iin asede bulunan trmaynz.
kaldrma noktalarn kullannz. Kabinli je- ! Herhangi bir yangn annda personelin kolay k iin
neratrlerde kabinin st ksmnda bulu- acil k kaps olmaldr.
nan kaldrma noktalar da kullanlabilir.
! Kaldrma aralar ve destek yaplarnn salam ve je- 2.4 Mekanik
neratr tayabilecek kapasitede olduundan emin Jeneratr, hareketli paralardan
olunuz. korunmak iin muhafazalaryla bir-
! Jeneratr kaldrld zaman, tm personel jeneratr likte tasarlanmtr. Buna ramen
etrafndan uzak tutulmaldr. jeneratr mahallinde alrken
! Rmorklu jeneratr ekerken tm trafik kurallar- dier mekanik tehlikelerden personeli ve cihazlar ko-
na, standartlara ve dier dzenlemelere dikkat ediniz. rumak iin nlem alnmaldr.
Bunlarn iinde ynetmeliklerde aka belirtilen gerekli
donanmlar ve hz snrlar da vardr. Uyarlar
! Personelin mobil jeneratr zerinde seyahat etmesi- ! Emniyet muhafazalar karlm halde jeneratr a-
ne izin vermeyiniz. Personelin, ekme demiri zerinde ltrmaynz. Jeneratr alyorken bakm yapmak veya
veya mobil jeneratr ile ekici ara arasnda durmasna baka bir sebepten dolay emniyet muhafazasnn yan-
izin vermeyiniz. na veya altna ulamaya almaynz.
! zel olarak tasarlanmadka jeneratr tehlikeli ola- ! El, kol, uzun salar, sarkan elbise paralar ve taklar
rak snflandrlan bir evrede kurmaynz ve altrma- hareketli paralardan uzak tutunuz.
ynz. Dikkat: Baz hareketli paralar ak
bir ekilde grlmemektedir.
2.3 Yangn ve Patlama ! Jeneratr odas var ise kapsn ka-
Jeneratrn bir paras olan yakt tutuabilir ve patlaya- pal ve kilitli tutunuz
bilir. Bu maddelerin depolanmasnda uygun nlemlerin ! Scak yakt, scak soutma suyu,
alnmas, yangn ve patlama riskini azaltr. BC ve ABC scak egzoz duman, scak yzeyler ve keskin kelere
snf yangn sndrcler el altnda bulundurulmaldr. temastan kannz.
Personel bunlarn nasl kullanldn bilmelidir. ! Jeneratr mahallinde alrken eldiven, apka ve koru-
yucu elbise giyiniz.
Uyarlar ! Soutma suyu souyana kadar radyatr dolum kapa-
! Jeneratr odasn uygun ekilde havalandrnz. n amaynz. Radyatr kapan tamamen amadan
! Jeneratr, jeneratr odas ve zeminini temiz tutunuz. nce yksek buhar basncnn azalmas iin kapa yava
Yakt, ya, ak elektroliti veya soutma su- yava gevetiniz
yunun etrafa dklmesi durumunda, dk-
len yeri derhal temizleyiniz. 2.5 Kimyasal
! Yanc svlar motorun yaknnda bulundurmaynz. Jeneratrde kullanlan yalar, yaktlar,
! Yaktn etrafnda alev, kvlcm, sigara imek gibi yanma- soutma sular ve ak elektrolitleri
ya sebebiyet verebilecek olaylara izin vermeyiniz. Ak endstriyel tiptir. Uygun kullanlmaz-
balantsn yapmadan veya ak balantsn skmeden larsa personele zarar verebilirler.
nce ak arj cihaznn beslemesini kesiniz.
! Ark olayndan kanmak iin topraklanm iletken nes- Uyarlar
neleri terminaller gibi elektrie maruz kalan blgeler- ! Yakt, ya, soutma suyunu ve ak elektrolitini deri ile
2
temas ettirmeyiniz ve skldkten sonra alternatr terminal kapagn yerine
yutmaynz. Eer kazayla yutulur ise tbbi tedavi iin taknz. Kapak emniyetli bir sekilde yerine taklmadka
derhal yardm isteyiniz. Eer yakt yutulmu ise kustur- jeneratr alstrmaynz.
maynz. Deri ile temas halinde temas blgesini sabunlu ! Jeneratr gcune ve elektrik karakteristiklerine uygun
su ile ykaynz. yklere ve elektrik sistemlerine baglaynz.
! Yakt veya ya bulam elbise giymeyiniz ! Tm elektrikli ekipmanlar temiz ve kuru tutunuz. Izo-
! Aky hazrlarken aside dayankl bir nlk, yz mas- lasyonun asndg, atladg ve krldg yerlerdeki
kesi ve koruyucu gzlk taknz. Deriye veya elbiseye elektrik tertibatn yenileyiniz. Asnms, paslanms ve
ak elektrolitinin dklmesi durumunda dklen yeri rengi gitmis olan terminalleri yenileyiniz. Terminalleri
bol miktarda basnl su ile hemen temizleyiniz. temiz ve baglantlar sk tutunuz.
! Tm baglantlar ve bostaki kablolar izole ediniz.
2.6 Grlt ! Elektrik yangnlarnda BC veya ABC snf yangn sn-
Ses izolasyon kabini ile donatlmam drcler kullannz.
jeneratrlerin ses iddeti 105 dBA
dan fazladr. 85 dBA dan fazla ses 2.8. Elektriksel arpmalara kar ilk yardm
iddetine uzun sreli maruz kalma, Uyarlar
iitme iin tehlikelidir. ! Elektrie maruz kalm kiiye, elektrik
Uyarlar kaynan kapatmadan nce plak elle
! Jeneratr mahallinde alrken kulaklk taknz. dokunmaynz.
! Eer mmknse elektrik kaynan
2.7 Elektriksel devre d ediniz.
Elektrikli cihazlarn etkili ve emniyetli ! Bu mmkn deil ise elektrik fiini ekiniz veya elektrik
almas, bu cihazlarn doru bir ekil- kablosunu elektrie maruz
de yerletirilmesi, kullanlmas ve bak- kalan kiiden uzaklatrnz.
mnn yaplmas ile salanr. ! Eer bunlar da mmkn deil ise, kuru yaltkan madde
Uyarlar zerinde durunuz ve tercihen kuru tahta gibi yaltkan
! Jeneratrn yke balants, bu konuda eitimli ve ka- bir madde kullanarak, elektrie maruz kalan kiiyi ilet-
lifiye olan yetkili bir elektriki tarafndan, ilgili elektrik kenden uzaklatrnz.
kodlarna ve standartlarna uygun bir ekilde yaplma- ! Eer kazazede nefes alyor ise, kazazedeyi aada ta-
ldr. nmland gibi iyileme pozisyonuna getiriniz.
! Jeneratr altrmadan nce (buna mobil jeneratr- ! Eer elektrie maruz kalan kii bilincini kaybetmi ise,
ler de dahil) jeneratrn ayltmak iin aadaki ilemleri uygulaynz:
topraklamasnn yapldndan emin olunuz.
! Jeneratre yk balants yapmadan veya jeneratrden 2.8.1. Solunum Yolunu Amak
yk balantsn skmeden nce jeneratrn almasn Kazazedenin ban geriye doru ei-
durdurunuz ve ak negatif (-) terminalinin balantsn niz ve enesini yukar kaldrnz.
kesiniz. Kazazedenin azna veya boazna
! Islak veya sulu bir zeminde duruyor iken yk baglant- kam olabilecek takma di, sakz, si-
sn yapmaya veya yk baglantsn kesmeye gara gibi nesneleri karnz.
kalksmaynz.
! Jeneratr zerindeki iletkenlere, baglant kablolarna 2.8.2. Nefes alma
ve elektrikli paralara vcudunuzun herhangi bir ksm Kazazedenin nefes alp almadn, g-
ile veya izole edilmemis herhangi bir nesne ile temas rerek, dinleyerek ve hissederek kont-
etmeyiniz. rol ediniz.
! Yk baglants yapldktan sonra veya yk baglants
3
2.8.3. Kan Dolam Kazazedenin ne veya arkaya doru yuvarlanmama-
Kazazedenin boynundan nabzn kontrol ediniz. sn salaynz.
Nefes alp vermesini ve nabzn dzenli bir ekilde
2.8.4. Eer Nefes Alamyor fakat Nabz Varise kontrol ediniz. Eer ikisinden biri durursa yukardaki i-
Kazazedenin burnunu skca kapat- lemleri tekrarlaynz.
nz.
Derin nefes alarak dudaklarnz ka- Uyarlar
zazedenin dudaklar ile birletiriniz. Kazazedenin bilinci tekrar yerine gelene kadar, su gibi
Gs kafesinin ykseldiini gzle- svlar vermeyiniz
yerek azndan yavaa fleyiniz. Son-
ra flemeyi brakarak gs kafesinin 3. ODA BOYUTLANDIRMASI, YERLETRME,
tamamen inmesine izin veriniz. Kaza- KALDIRMA
zedeye dakikada ortalama 10 defa nefes veriniz. 3.1. Genel
Eer yardm armak iin kazazede yalnz braklacak- Jeneratrn boyutlarnn bilinmesinden sonra jenerat-
sa, 10 defa nefes vererek ksa rn yerletirilmesi iin planlar hazrlanabilir. Bu blm
zamanda geri dnnz ve nefes verme ilemine devam jeneratrn etkin ve emniyetli yerletirilmesi iin gerekli
ediniz. nemli faktrleri iermektedir.
Her 10 nefes verme ileminden sonra nabz kontrol
ediniz. 3.2. Kabin
Nefes alp vermeye balad anda kazazedeyi iyileme Jeneratr, bir kabin iine konduunda tama ve yer-
pozisyonuna getiriniz. letirme byk lde kolaylaacaktr. Kabin, jenerat-
2.8.5. Nefes Alamyor ve Nabz Yok ise r yetkisiz kiilerin kullanmasna ve d etkenlere kar
Tbbi yardm isteyin veya en yakn korur.
salk kuruluunu araynz.
Kazazedeye iki defa nefes verin ve 3.3. Jeneratrn Tanmas
aadaki gibi kalp masajna balayn. Jeneratr asesi, zellikle jeneratrn tanmasn kolay-
Gs kafesinin birleme yerinden 2 latrmak iin dizayn edilmitir. Jeneratrn yanl kald-
parmak yukarya avu iini yerletiriniz. rlmas paralarda ciddi hasarlara yol aabilir.
Dier elinizi de parmaklarnz kilitle- Jeneratr, forklift kullanlarak kaldrlabilir, dikkatli bir
yerek yerletiriniz. ekilde asesinden itilebilir veya asesinden ekilebilir.
Kollarnz dik tutarak, dakikada 15 defa 4-5 cm aa
doru bastrnz.
Tbbi yardm gelene kadar 2 nefes verme ve 15 kalp
masaj ilemini tekrar ediniz.
Eer kazazedenin durumunda dzelme grlrse, nab-
zn kontrol ederek nefes vermeye devam ediniz. Her
10 nefes verme ileminden sonra nabzn kontrol edi-
niz.
Nefes alp vermeye balad anda kazazedeyi, iyile-
me pozisyonuna getiriniz. ekil 3.1. Jeneratrn vin ile kaldrlmas
Uyarlar:
2.8.6. yileme Pozisyonu ! Jeneratr motor veya alternatr kaldrma halkalarn
Kazazedeyi yan yatrnz. kullanarak kaldrmaynz.
Solunum yolunun ak olmasn salamak iin enesi ! Forklift ile itme esnasnda dorudan aseyi itmeyiniz ve
ileriye doru bakacak ekilde ban eik tutunuz. oluabilecek hasar nlemek iin mutlaka ase ile forklift
4
arasna tahta koyunuz Ayrca jeneratrn geici olarak binann iinde veya d-
! Jeneratrn arlna uygun kaldrma tehizat kulla- nda altrlmasnda kabin kullanlmas faydaldr.
nnz. - Dahili topraklama durumunu kontrol ediniz
! Jenenatr askda iken tm personeli jeneratrden - Topraklama ubuunu jeneratre en yakn noktaya
uzak tutunuz. monte edin, yaylma direncini (maks.1k) ln, kon-
! Kabinli veya kabinsiz jeneratr kaldrlrken ase veya tak voltaj 25 Volt, 30 mA kaak akmdan daha yksek
kabin zerindeki kaldrma halkalar kullanlmaldr. olmamal.
3.4. Jeneratr Yerinin Seimi 3.5 Kabinli Jeneratr Grubunun Ak Sahada Yerle-
Jeneratrn konaca yerin seimi yaplrken aadaki tirilmesi ve Kurulumu
faktrler gz nne alnmaldr: Jeneratr ak sahada, darda kurarken aadaki ko-
- Toplam alan ve alan ierisindeki snrlamalar nulara dikkat edilmesi gerekir;
- Jeneratr mahalline giri, balangta jeneratrn oda- Egzoz gazlarnn birikebilecei bir yere jeneratr kur-
ya getirilmesi, yerleim durumu, montaj tasarmlar, son- maynz. Egzoz gazlarnn kapal bir alanda toplanmasn
raki yakt ve servis yapabilme durumlarnn gz nne nlemek iin egzoz gaznn pencere, kap veya hava-
alnmas landrma kanallarnn giriinden veya dier aklklardan
- Zemin durumu, seviyesi ve meyil durumu gz nne uzak tutunuz.
alnmaldr Egzoz ve soutma havas ak binalara ve insanlara
-Ses ile ilgili kstlamalar varm (ofis ,yerleim yeri vb.) potansiyel tehlike oluturmayacak ekilde konumland-
- Jeneratr iin oda ierisinde cebri havalandrmaya ih- rlmal.
tiya duyulacandan yeterli soutma havas ve yanma Jeneratr konumlandrrken hakim rzgrlar ve hava
havas oda ierisine alternatr n arkasndan girecek ve akmlar gz nne alnmaldr,
motorun n tarafndan scak hava dearj edilecektir. niteyi daha nceden hazrlanm, su drenaj artlarn
Binann durumuna gre , gerekli olan hava miktarnn saylayan bir yere yerletiriniz.
salanabilmesi iin ek hava kanallar yaplmasna ihtiya Drenaj pompasnn boaltma alan , yamur oluu,
duyulabilir. at oluu, arazi sulamas veya su fskiyesi gibi niteyi su
-Yamur, kar, sulusepken, sel suyu, direk gn , don- basaca veya muhafazaya su pskrtecei ve hava giri
durucu souk ve ar scaklk gibi unsurlara kar koru- ve k aklklarna girecei yeri semeyiniz.
mal olmaldr. Yamur, kar, sulu sepken, sel suyu, direkt gn ,
- Andran veya iletkenlik salayan toz, iplik, duman, ya dondurucu souk ve ar scaklk gibi unsurlara kar
duman, buhar ve motor egzoz duman gibi havadan korumal olmaldr,
tanan zararl maddelere kar korumal olmaldr. Andran veya iletkenlik salayan toz, iplik, duman,
- Aa veya direk gibi devrilebilecek nesnelerin ve mo- ya duman, buhar ve motor egzoz duman gibi hava-
torlu aralarn arpmasna kar korumal olmaldr. dan tanan maddelere kar korumal olmaldr,
- Jeneratrn soutulmas ve servis ve bakm yaplabil- Telefon, elektrik, yakt, klima, sulama gibi hizmetlerin
mesi iin jeneratr etrafnda en az 1 metre ve jeneratr etkilenmedii bir yere jeneratr kurunuz,
zerinde en az 2 metre boluk olmaldr. Jeneratr , emi ve atlarnn , yaprak , ot , kar gibi
- Jeneratr odaya tayabilmek iin jeneratrn ge- doal yollardan kapanmamasn salayacak bir yere
ebilecei uygun bir geit olmaldr.Hava giri ve k monte ediniz. Hkm sren rzgrlar jeneratrn emi
havalandrmalar ,Jeneratr odasna giri-k noktas ve atn etkiliyecek ynde olursa, niteyi korumak iin
salamas dnlrse sklebilir yaplabilir. rzgar kran ina edilmesi gerekir,
- Yetkisiz kiilerin jeneratr mahalline girileri nlenme- Jeneratrn konulaca zemin dzgn yzeyli ve kuru
lidir. olmal, zamanla batma ve eilme durumu olmama-
- Eer jeneratr binann dna koymak gerekiyor ise, l, Jeneratrn slak arln tayabilmeli. Bu nedenle
jeneratr bir kabin veya bir oda ierisine konmaldr. jeneratrn montaj iin dzgn yzeyli beton kaide
5
gereklidir. Kablo ve yakt hatlar iin ayr ayr kanallar ve zerine kurulmas tavsiye edilir, Beton kaidede tercihen
kanal kapaklar hazrlanm olmaldr, 0,50 lik eim kabul edilebilir.
Jeneratrn devreye alnmas ve yerleimi iin yeter-
li alan olmal. Ayrca bakm yapabilmek iin jeneratre Temel ;
eriim olana salanmal. Glendirilmi bir beton kaide kmeyi ve titreimi n-
Egzoz sisteminde herhangi bir kaak ve hasar olup ol- lemek iin salam bir destek salar.Genel olarak jenera-
madn ,scak egzoz sisteminin herhangi yanc madde trn kurulaca beton kaide 150-200 mm derinliinde
veya atklarla temas etmediini kontrol ediniz, olmal , Beton kaidesinin eni ve boyu , jeneratr ase-
Egzoz borusunun knda herhangi bir engel ya da sinin her yanndan 150 mm boluk brakacak ekilde
kstlayc unsur olup olmadn kontrol edin, uzun olmaldr.Betton kaidenin altndaki zemin uygun bi
Dzenli temizlik ve bakm iin kabin evresinde yeteri ekilde hazrlanmal ve hem jeneratr hemde beton
kadar akln bulunmas, kabin kapaklarnn tamamen kaideyi tayacak kapasitede olmaldr. (eer jeneratr
alabilecei alann salanmas gerekir. zemine monte ediledekse, zeminin Jeneratr ve ak-
Jeneratr yanc madde ve duvarlardan en az 1,5m sesuarlarn kaldrabilecek kapasitede olmaldr.).Eer
uzaa kurunuz. zemin zamanla slanacak ise beton kaidenin zeminden
Dizel jeneratr grubu kabini koruma snf IP 23 zel- yukarda yaplmasnda fayda vardr.Bu hem Jeneratr
liindedir, iin hemde jeneratre servise gelecek kiiler iin kuru
Enerji tamayan tm metal aksamn topraklanm ol- bir ortam hazrlayacak, ayrca beton kaideyi korozyona
mas gerekir, karda koruyacaktr. Bu nedenle Beton kaidesi , grubun
Kabinli jeneratr mmkn olduu kadar yk sistemi- yerletirildii odann zemininden en az 150 mm yuka-
ne yakn konumlandrlmaldr. rda olmaldr. Beton kaide altndaki kum tabaka en az
200 mm yksekliinde olmaldr.
3.6. Jeneratr Temeli ve taban :
Not: zel kaide beton gerekli deildir, jeneratr slak
arln tayacak dzgn beton zemin yeterlidir.
Bu tip alma (sismik tanmlama dahil) kaide betonun
dizayn, inaat veya yap mhendisi sorumluluunda ya-
placaktr.
Kaide betonun temel fonksiyonlar:
- Jeneratr toplam arln tamak
-Jeneratr grubunun meydana getirdii vibrasyonu ya-
pdan izole etmek
Yap tasarm iin inaat mhendisi aadaki detaylara
ihtiya duyacaktr.
- Jeneratr odas alma ss (makineden ktleye veri-
len s transferi tanmlanmam gerilim stresi
oluturabilir )
- nerilen kaide beton ktlesinin tm boyutlar
- Jeneratr asesinin tespit noktalar ve montaj
Beton Kaide:
Beton kaidenin dklmesi ile jeneratrn kaideye otur-
tulmas arasnda betonun sertlemesini salayabilmesi
iin en az yedi gn gemesi gerekecektir. Beton kai-
denin mmkn olduunca dz olmas ve yeni toprak
6
Aadaki forml minimum beton derinlii hesabnda Titreimin Yaltm:
kullanlabilir. Her bir jeneratr tek modl olarak motor ve alternatr
k kaplin ile birbirine balanr ve grup esnek lastik izolatr-
t = ------------------- lerle aseye monte edilir.
dxwxl
Normal olarak ar bir beton kaidenin, motorun tit-
t = Betonun kalnl metre (feet)
reimini snmlemek iin kullanlmas gerekli deildir.
k = Jeneratrn net arl kg (lbs)
Jeneratr arln tayabilecek dzgn beton zemin
d = Betonun younluu (2322 kg/m3) 145lbs/ft3
yeterlidir.
w = Betonun genilii metre (feet)
l = Kaide betonunun uzunluu metre (feet)
Not: ase ile grup arasnda titreim takozu mevcut
Jeneratrn konulaca betonun tama gc beton ise tekrar ase altna titreim takozu koymak isterseniz
ierisinde kullanlan malzemelere , temelin yerletirildii AKSA yetkili servisine dannz.
topran tama kapasitesine bal olarak deiiklik gs-
terebilir , bundan dolay beton kaide ve temelde Balantlar:
glendirilmi elik hasr alar , ubuklar veya bunlara Tm boru sistemleri ve elektriksel balantlar jenerat-
edeer malzemeler kullanlmas gerekebilir. Dzgn re esnek balantlar ile balanmaldr. Yakt ve su hatt
olmayan ve zayf olan beton kaide istenmeyen titreime devreleri, egzoz borular uzun mesafelere titreimi ta-
sebep olabilir. yabilir.
Toprak Tama Yk:
Jeneratrn toplam arl (soutma suyu , ya , yakt 3.7. Oda Dizayn Klavuz Notlar
tankndaki mazot dahil) ile jeneratr beton kaidesinin 3.7.1.Oda boyutu tolerans:
topraa uygulad yk , genelde birok topran tama deal olarak jeneratr evresinde kolay bakm ve dola-
yknn (yaklak olarak 2000 lbs/ft2 9800 ma alan iin yakt tank ve panodan minimum 1 metre
kg/m2) altnda olmasna ramen kontrol etmekte her mesafe verilmi olmas gerekir. Personel giri kaps giri
zaman fayda vardr. ve ka, ses kes bariyerlerinin ve dier aksesuarlarn
giriine uygun, yeterlikte olmal.
Hesaplanmas :
k=toplam arlk (jeneratr slak arlk + beton kaide
3.7.2. Giri ve k ses kesme bariyerleri ile panjurlar:
arl) kg (lbs)
Giri ve k ses kesme bariyerleri 100 mm lik tahta
w=beton kaide genilii metre (feet)
ereveye monte edilmeli. Bariyer nne monte edi-
l=beton kaide uzunluu metre (feet)
len panjurlar hava giriinde dk direnci salamak iin
k panjur tasarmna dikkat edilmeli, minimum 50% alan
TTY = ------------------- (psi)
144 x w x l salanmaldr.
Panjurlarn i ksmna ku ve kk canllarn girmesine
k kar tel kafes olmas gerekir. Kafes tellerinin aklklar
TTY = ------------------- (kg/m2)
wxl hava akn engelleyecek aralkta olmamas gerekir.
k bariyeri radyatr davlumbaz flanna s ve yaa
rnek Ugulama : kar direnli esnek branda balantsyla balanr.
400 kVA jeneratr gurubu , toplam arl 4500 kg (s-
lak arlk , soutma suyu , ya dahil) , beton kaide 3.7.3. Yanma Havas Girii
4 m uzunluunda , 1.5 m geniliinde ve 350 mm yk- Motor yanma havas mmkn olduunca temiz ve
sekliinde , dolaysyla topraa uygulad yk ; souk olmaldr. Yanma havas jeneratrn bulunduu
Beton kaide arl = 2322x4x1,5x0,35 =4876 kg ortamdan motora monte edilen hava filtresi vastasyla
k=4500+4876=9376 kg ekilir.
Fakat bazen toz, pislik ve scaklk gibi koullardan do-
9376
TTY = ---------------------- (kg/m2) ; THY = 1562 kg/m2 lay jeneratr etrafndaki hava uygun olmayabilir. Bu
1,5 x 4
7
durumlarda bir hava giri kanal balanabilir. Bu kanal
motor zerindeki hava filtresine temiz havay d or-
tamdan veya baka bir odadan salar. Hava flitresini -
karmaynz veya onu motordan uzaa monte etmeyiniz
aksi takdirde hava kanalnda meydana gelebilecek ka-
aklardan giren yada kanalda biriken toz direk motorun
iine gidebilir.
ekil 3.3 Zayf havalandrma tertibat atlan havann
3.7.4. Egzoz Sistemleri ynlendirilmesi
Egzoz sistemi , izim plannda grld gibi oda tava- Odaya hava giriinin ve odadan hava knn kolay ol-
nna sabitlenmelidir. Eer binann tavan egzoz sistemi mas iin hava giri ve k pencerelerinin yeterince
arln tayamayacak durumda ise oda zemininden byk olmas gerekir. Kaba bir hesapla hava giri ve k
pencereleri radyatr alannn en az 1.5 kat
demir konstrksiyon ile egzoz sisteminin tanmas ge-
byklnde olmaldr.
rekir. Egzoz sistemi kaza ile dokunmalara kar zemin-
den 2 3 metre yukarda yaplmas gerekir. Paslanmaz
elik kompensatr sabit egzoz sistemi ile motor egzoz
manifoldu arasna monte edilmesi gerekir.
Egzoz sisteminin jeneratr odasndaki blmnn yk-
sek younluklu , yksek scaa dayankl izalosyon ile
sarldktan sonra izolasyon zeri alminyum yastk ile
kaplanmas iyi olacaktr. Dolays ile operatr yaralan-
mas ve jeneratr odasnda meydana gelecek s yk-
selmesi azalacaktr.
ekil 3.4 Hava Giri k Alan
3.7.5. Soutma ve Havalandrma
Motor, alternatr ve egzoz borular s yayarak ortam Jeneratrn hava artlarndan etkilenmemesi iin giri
ve k pencerelerinin panjurlar olmaldr.
scaklnn artmasna sebep olurlar. Scakln artmas
Bu panjurlar sabit olabilir ancak souk iklimler iin hare-
ise jeneratrn almasn olumsuz ynde etkiler. Bu ketli olmas tercih edilmelidir. Jeneratr altrlmadn-
nedenle motor ve alternatrn souk tutulmas iin da panjurlar kapatlabilir. Bylece ilk altrma ve yke
yeterli havalandrmann salanmas gerekir. Hava ak- vermeyi kolaylatran scak hava odada kalr. Otomatik
nn ekil 3.5 de grld gibi olmas gerekir. Hava kontrol sistemli bir jeneratr odasnda eer panjurlar
alternatr tarafndan jeneratr odasna girmeli, motor hareketli ise bunlar otomatik olarak hareket ettirilebilir.
zerinden ve radyatr ierisinden geerek adr bezin- Yani motorun almaya balamasyla birlikte panjurlarn
hemen almas ve motorun durmasyla da panjurlarn
den krk tipinde esnek bir branda yardmyla odadan
kapanmas salanabilir.
kmaldr. Eer scak havann odann dna atlmas iin
bir branda kullanlmaz ise fan, scak havay jeneratr
odasna yayarak soutmann etkinliini azaltr.
ekil 3.2. Saptrma kanallar ile radyatrden ekil 3.5. Tipik Jeneratr grubu bodrum yerleim plan
8
3.7.6. Kablo Sistemleri fer panolar duvara montaj yaplan tiptir. Maksimum de-
Byk gteki jeneratr transfer panosu jeneratr oda- rinlii 370 mm dir. Zemin tipi panolar 600 Amper ile
snn dna ve datm panosu odasna monte edilir. balar. Zemin tipi panonun arkasndan minimum 800
zel proje uygulamalarnda bu sistem deiiklie u- mm alan braklm olmal.
rayabilir. Alternatr k terminallerinden kacak g
kablolar esnek yapda H07RN-F tipi kablolarla montaj 3.7.8. Jeneratr Gruplar
yaplmal. 800kVA gcundeki jeneratrlere kadar yakt tank
Esnek g kablolar kablo kanal/ merdiveni vastasyla
tanr. Kablolar doru bir eklide desteklenmi , ve or- grubun asesindedir. Ayr yakt tank salanmas mm-
tam ve montaj koullarna gre seilmi olmaldr.Esnek kndr; ancak jeneratr odasnda ilaveten bir alann
tek damar g kablolar herhangi bir panoya veya ci- olmas gerekir. Radyatr ile hava k kanal arasnda
haza girite demir olmayan metal levha malzemeden minimum 300 mm branda bezi monte edilmi olmal.
geirilmelidir.
3.7.9. Kaplar
3.7.7. Transfer Panosu Jeneratr odas kaplar her zaman dar almal, ift
Kk gteki jeneratrler iin transfer panosu jenera- kap kullanlmas durumunda jeneratr hareket ettir-
tr odasna montaj yaplabilir. 600 Ampere kadar trans- mede kolaylk salayacaktr
9
Radyatr Scak Hava
Jeneratr Grubu, 50 Hz, 400 V Oda Boyutu Oda kap
Hava k giri Egzoz
boyutu
Boyutlar Penceresi pencere
Standby m si
Cummins m
G m m toplam
Motor Model ap P
Modeli kVA alan
Yksek- A B C
Boy En
lik Boy En Ykseklik D E K m2 L M inch m
S3.8-G6 AC 55 55 1,78 0,95 1,25 3,5 3 2,5 0,7 0,65 0,5 0,6 1,5 2 3 2
S3.8-G7 AC 66 66 2,15 1,05 1,45 3,5 3 2,5 0,7 0,7 0,55 0,65 1,5 2 3 2
6BTA5.9-G5 AC 110 110 2,2 1,05 1,6 4 3 2,5 1 1,1 0,42 1,4 1,5 2 3 2
6BTAA5.9-G5 AC 175 175 2,32 1,15 1,67 4 3,3 2,5 1 1,1 0,55 1,4 1,5 2,2 3 2
6CTA8.3-G2 AC 200 200 2,3 1,15 1,6 4 3,3 2,5 1 1 0,55 1,3 1,5 2,2 5 2
6CTAA8.3-G2 AC 250 250 2,6 1,15 1,75 4,5 3,3 2,5 1 1,25 0,4 1,6 1,5 2,2 5 2
QSL9-G5 AC 350 350 3 1,15 1,9 5 3,3 3 1,2 1,4 0,35 2,1 1,5 2,5 4 2,5
NTA 855-G4 AC 400 400 3,23 1,16 2 5 3,3 3,2 1,25 1,9 0,45 3 1,5 2,5 6 2,5
QSX15-G6 AC 500 500 3,56 1,36 2,1 6 3,5 3,2 1,5 1,45 0,45 3 1,7 2,6 8 2,5
QSX15-G8 AC 550 550 3,56 1,36 2,1 6 3,5 3,2 1,5 1,45 0,45 3 1,7 2,6 8 2,5
VTA28-G5 AC 703 700 4 1,4 2,16 6,5 4 3,5 1,6 1,4 0,6 3 2 2,6 2x6 2,6
VTA28-G6 AC 825 825 4 1,4 2,16 6,5 4 3,5 1,6 1,4 0,6 3 2 2,6 2x6 2,6
QSK23-G3 AC 880 880 4 1,71 2,26 6,5 4 4 2 2 0,25 5 2,4 2,7 8 2,7
QST30-G4 AC 1100 1100 4,4 1,78 2,35 7 4,5 4 2,1 2 0,3 5,3 2,5 3 2x6 3,1
KTA38G5 AC 1100K 1100 4,4 1,78 2,37 7 4,5 4 2,1 2,1 0,3 5,3 2,5 3 2x6 3,1
KTA50-G3 AC 1410 1410 4,95 2,1 2,47 8 4,5 4 2,3 2,1 0,25 6 2,7 3 2x8 3,1
KTA50-G8 (GS8) AC 1675 1675 5,5 2,15 2,6 8 4,5 4 2,3 2,3 0,2 7 2,7 3,5 2x8 3,6
QSK60-G4 ACQ 2250 2250 5,9 2,3 3 9 5 5 2,7 2,6 0,3 9 3,1 4 2x10 4
*ase ile zemin ayn hizada (bu deere beton kaide pay eklenmelidir)
Tablo 3.1. Tek grup olarak alacak Cummins dizel motorlu ak tip dizel jeneratr boyutlar, oda boyutlar, hava
giri ve k pencerelerinin boyutlar ve egzoz borusu ap lleri. Boyutlara akustik elemanlar dahil edilmemitir.
3029TF120 AJD45 45 1,78 0,95 1,15 3 3 2,5 0,7 0,7 0,4 0,6 1,5 2 3 1,9
4045TF120 AJD75 75 2,15 1,05 1,46 4 3 2,5 0,9 1,0 0,42 1,2 1,5 2 3 1,9
4045TF220 AJD90 90 2,15 1,05 1,46 4 3 2,5 0,9 1,0 0,42 1,2 1,5 2 3 2
4045HF120 AJD 110 110 2,15 1,05 1,46 4 3 2,5 0,9 1,0 0,42 1,2 1,5 2 4 2
6068TF220 AJD 132 132 2,3 1,15 1,55 4 3 2,5 0,9 1 0,5 1,2 1,5 2,3 4 2
6068HF120 AJD 170 170 2,4 1,15 1,55 4 3 2,5 1 1 0,52 1,25 1,5 2,3 4 2
6068HF120 AJD 200 200 2,4 1,15 1,55 4 3 2,5 1 1 0,52 1,25 1,5 2,3 4 2
6068HFG55 AJD 275 275 2,75 1,3 1,35 4,5 3,5 2,5 1,15 1,35 0,35 1,9 1,5 2 4 2
Tablo 3.2. Tek grup olarak alacak John Deere dizel motorlu ak tip dizel jeneratr boyutlar, oda boyutlar, hava
giri ve k pencerelerinin boyutlar ve egzoz borusu ap lleri. Boyutlara akustik elemanlar dahil edilmemitir.
10
Radyatr Scak Hava
Jeneratr Grubu, 50 Hz, 400 V Oda Boyutu Hava k Oda kap
giri Egzoz
Penceresi pencere boyutu
Boyutlar m
Doosan Standby si
Motor Model G m m toplam m
alan ap P
Modeli kVA Yksek- A B C
Boy En lik Boy En Ykseklik D E K m 2 L M inch m
P08TI AD 220 220 2,68 1,15 1,63 4,5 3,3 3 1 1,2 0,45 1,5 1,5 2,2 3 2
P126TI AD 275 275 2,85 1,3 1,65 5 3,3 3 1,2 1,25 0,4 1,9 1,7 2,4 3 2,4
P126TI-II AD 330 330 2,85 1,3 1,65 5 3,3 3 1,2 1,25 0,4 1,9 1,7 2,4 3 2,4
P158LE-1 AD 410 410 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2X3 2,6
P158LE AD 490 485 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2X3 2,6
P180LE AD 550 550 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2X3 2,6
P180LE AD 600 600 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2x3 2,6
P222LE AD 660 660 3,7 1,4 2,1 5,5 3,5 3,3 17 1,6 0,45 3,4 2,1 3 2X3 2,6
P222LE-S AD 700 700 3,7 1,4 2,2 5,5 3,5 3,3 17 1,7 0,4 3,6 2,1 3 2X3 2,6
P222LE-II AD 770 770 3,7 1,4 2,2 5,5 3,5 3,3 1,7 1,7 0,4 3,6 2,1 3 2X3 2,6
Tablo 3.3. Tek grup olarak alacak Doosan dizel motorlu ak tip dizel jeneratr boyutlar, oda boyutlar, hava
giri ve k pencerelerinin boyutlar ve egzoz borusu ap lleri. Boyutlara akustik elemanlar dahil edilmemitir.
Radyatr Scak
Jeneratr Grubu, 50 Hz, 400 V Oda Boyutu Hava k
Hava
Oda kap
giri Egzoz
Penceresi pencere boyutu
Boyutlar m
Mitsubishi Standby si
Motor Model G m m toplam m
alan ap P
Modeli kVA Yksek- A B C
Boy En lik Boy En Ykseklik D E K m 2 L M inch m
S3L2 AMT11 11 1,25 0,85 0,95 2,5 3 2,5 0,55 0,5 0,4 0,35 1,5 2 2 1,5
S4L2 AMT16 16 1,35 0,85 0,95 2,5 3 2,5 0,55 0,5 0,4 0,35 1,5 2 2 1,5
S4Q2 AMT22 22 1,38 0,85 1,0 2,5 3 2,5 0,55 0,5 0,4 0,35 1,5 2 2 1,5
S4S AMT33 33 1,5 0,9 1,15 2,5 3 2,5 0,7 0,65 0,4 0,6 1,5 2 2 1,5
S6R2-PTAA APD825M 825 4,1 1,83 2,11 6,5 4 4 1,8 1,96 0,4 3,5 2,5 3 8-10 3
S12H-PTA APD1100M 1100 4,37 2,1 2,21 7 4,5 4 1,9 2,1 0,35 4 2,5 3 8-10 3
S12R-PTA APD1425M 1425 4,43 2,04 2,22 7 4,5 4 2,2 2,1 0,2 4,6 2,5 3 12 3
S12R-PTAA2 APD1650M 1650 4,95 2,2 3,08 8 4,5 5 2,5 3 0,3 7,5 3 4 12 4
S16R-PTA APD1915M 1915 5,16 2,25 2,6 8 4,5 5 2,6 2,3 0,3 6 3 3,5 14-16 4
S16R-PTA2 APD2100M 2100 5,23 2,52 2,96 8 5 5 2,9 2,8 0,2 8 3 4 14-16 4
S16R-PTAA2 APD2250M 2250 5,7 2,21 3,4 9 5 5,5 2,9 3,3 0,15 9,5 3 4,5 14-16 4
S16R2-PTAW APD2500M 2500 6,15 2,38 3,4 9 5 5,5 2,7 3,3 0,3 9 3 4,5 14-16 4
Tablo 3.4. Tek grup olarak alacak Mitsubishi dizel motorlu ak tip dizel jeneratr boyutlar, oda boyutlar, hava
giri ve k pencerelerinin boyutlar ve egzoz borusu ap lleri. Boyutlara akustik elemanlar dahil edilmemitir.
11
EGZOZ HAVASI
Jeneratr gurubundan atlan scak hava, opsiyonel kanal
vastasyla duvarda alan pencereden odann dna
HAVA GR
atlr. Duvarda alan pencere kanal boyutu ile ayn
Taze hava giri panjuru duvara veya kap zerine montaj yaplr.
olmal. Kanal ile pencere arasna suni kauuk veya
HAVA GR YZEY
snger kullanlarak hava kaana kar conta yaplr.
en az = egzoz havas alan x 2
Oda duvarnda alan egzoz hava penceresi dndan
tel kafes ile yapanc malzemelere kar korunmal.
Egzoz borusu scak hava kanalna baldr.
ELEKTRK KABLOLARI
JENERATR ASEYE
MONTAJLIDIR
TOPRAKLAMA
ekil 3.7. Kabinli jeneratrn oda yerleimi 3- Jeneratrn monte edildii zeminden en az 500 mm
yksekte konumlandrlm olan ana yakt tankndan
4. YAKIT SSTEM direkt olarak
4.1. Genel Motor iin en nemli zelliklerden birisi temiz ve su
Dizel motora yakt beslemesi aadaki ekillerde sa- karmam yaktn kullanlmasdr. Yakt ierisindeki
lanm olabilir. pislik enjektr klarn tkayabilir ,ve yakt sisteminde
1- Direkt olarak asesinde bulunan yakt tankndan bulunan paralarda hasara sebep olabilir. Yakt
2- Jeneratr odas veya muhafazas ierisinde ana yakt ierisindeki su , yakt sistemindeki paralarn korozyo-
tankndan otomatik dolum yapabilen gnlk servis nunu hzlandrr.
tankndan 4.2. Dizel Yakt zellii
12
4.3. Dizel Yakt zellik Tanmlar de yakt balantlar yaplm ve almaya hazr vaziyet-
Kl: Yakt ierisindeki mineral kalntsdr. Yksek kl tedirler. Yakt transferi, el operasyonlu pompalar veya
miktar silindirlerde ve enjektrlerde ar elektrik motorlu nitelerle yakt dolumu ile salanabilir.
oksitlenmeye sebep olur (Test Yntemi : ASTM D482,
ISO 6245) 4.5. Ara Tanksz Yakt Sistemi
Bu en basit dzenleme ile ana yakt tankndan direkt
Setan says: Dizel yaktn yanma kalitesinin bir ls- olarak motora yakt beslemesi yaplm olacaktr. Bu sis-
dr.Souk havalarda ve srekli dk ykte altrlacak temde yakt dn hatt bu tanka direk baldr.ekil 4.1
motorlarda yaktn setan numarasnn yksek olmas is- de tipik bir uygulamasn grebilirsiniz.
tenir.(Test Yntemi :ASTM D613 ; ISO 5165) Bu dzenlemenin snr kurallar aadadr:
1- Byk hacimli ana yakt tankndan karak motoru
Sislenme ve Akma noktas: Akma noktas , yaktn aka- doal ak ile besleyen yakt hatt jeneratrn kaide be-
mayaca en son scaklk deeridir.Yakta , ilk parafin tonu seviyesinin minimum 500 mm zerinde olmaldr.
mumu kristallerinin olutuu scaklk deeri ise sislenme 2- Yakt dn hattnn basn dm motor teknik
noktasdr. Akma noktas ,jeneratr grubunun alaca verilerinde ifade edilen deeri amamaldr. (max. Allo-
en dk ortam scaklnn 6C altnda olmas istenir. wable head on injector return line)
Sislenme noktas ise akma noktasndan en ok 6C 3- Ana yakt tankndan motora ekilen yakt besleme
zerinde olmas gerekir. Bylece yaktta kristalleme borusu motora gerekli yaktn toplam hacmini (tketi-
olmayacak ve filtreleme sistemi tkanmayacaktr. (Test len yakt ve geri dnen yakt miktar) karlayacak apta
Yntemi : ASTM D97, ISO 3015) Yaz tipi No.2 Diesel olmal.
in sislenme noktas yaklak 4,4C , akma noktas ise
-12,2 ila -6,6C dir.
13
4.8. Byk Hacimli Depolama Tanklar
Yakt besleme sisteminin amac tasarlanm sistem iin
uygulamaya ynelik yaktn yeterli miktarda depolan-
masdr. Dolaysyla ana yakt tanklar bu ihtiyaca uygun
hacimde olmaldr.
Tanklarn doldurulmas; tanker tarafndan kolay giri
yapmasna izin verecek ekilde ve kabine yerletirilmi
kilitlenebilir yakt doldurma balants olacaktr. Bu ka-
binde ayn zamanda yakt miktarn gsteren bir gs-
terge ve ar dolma alarm iin seviye sivici ve tankn
zerinde menhol bulunmas gerekir.
ekil 4.2. Ara tankl yakt sistemi Ana yakt tank aadaki zellikleri kapsamaldr;
- Temizleme veya onarm esnasnda yaltm koulu
4.7. Gnlk Servis Yakt Tank (oklu tanklar monte edildii yerlerde)
Jeneratr gruplar iin 1000-1500-2000 litrelik harici - Doldurma balants
yakt tanklar grup la beraber temin edilebilir. Ayrca - Hava k iin boru veya nefeslik
manel veya otomatik yakt transfer sistemi salanabilir. - Ara yakt tankndan ana yakt tankna tama hatt ba-
Dizel yakt inkoyla reaksiyona girdiinden yakt tanklar lants
galvaniz kapl sacdan yaplm olmamaldr. - Gzlem yapma veya manhole kapa, yaklak 18 inch
Yakt tank havalandrma borusu monte edilen yakt ( 457 mm) apnda.
sisteminin en yksek noktasna uzatlm olmaldr.Boru -Tankn en alt noktasnda boaltma balants
ap en az yakt giri ap kadar olmal ve ierisine toz - Seviye gstergesi (tank doldurma noktasna transfer
kir girmesini engelleyecek ekilde montajnn yaplm edilen gsterge)
olmas gerekmektedir. - Yakt besleme balants amur boaltma balants zt
Ara tank olarak kullanlacak gnlk servis tankna ar noktasnda
yakt transferi olmas durumuna kar aadaki tedbirle- - (htiya olunan yerde) yakt szgeci ve vana
rin alnm olmas gerekir. -Zemine monte edilen yakt tanklar iin yakt tama
1- Ana yakt tankna direkt geri dn (tant) boru tavas salanm olmaldr
tesisat yaplm olmal -Yeteri kadar geni ve yakt tank kapasitesinin %10
2- Gnlk tankn altnda toplama kab ierisine seviye daha fazlasn kapsayacak boyutta bir yer yaplmal
alarm sistemi dzenlenmi olmal. Seviye aldnda - Zemin, sv geirmez, bir tarafa dklme olacak ve
yakt transfer pompasnn enerjisini kesecek ekilde d- eim verilmi ekilde
zenleme yaplm olmal. yatrlm olacaktr.
3- Toplama kabna tama devresi boru tesisat yaplm - Tankn her tarafndan balant donanmlarna erimek
olmal. mmkn olabilmeli
Tank zerindeki dizel motora besleme hatt balants - Sv toplama ukurunu boaltmak iin el veya elektrikli
jeneratrn zemine oturduu seviyeden 600 mm yuka- pompalama sistemi kurulu olmaldr.
rda olmal ve bu durumda yakt pozitif basnla motoru - Tm metal aksam yerel standartlara gre topraklan-
besleyecektir. Yakt besleme hattndaki basn kayb, m olmaldr.
motorun yakt besleme pompas iin msaade edilen Yeraltna yerletirilecek tanklar iin yaplacak kaznn
maksimum basn kaybndan fazla olmamaldr (motor boyutu kolay montaj yapabilmeye izin verecek yeter-
teknik zellik sayfasna baknz) (maximum inlet restric- likte olmaldr. ukur yeteri kadar geni olmal tankn
tion at lift pump or inlet connection). d ksm ile hava aral en az 1 metre olmal. Tank des-
Yakt geri dn hatt basn kayb , izin verilen mak- tekler zerinde indirilirken tankn koruyucu kaplamas
simum deerden yksek olmamaldr. (motor teknik zarar grmemeli.
zellik sayfasna baknz) (maximum allowable head on
injector return line). 4.9. Yakt Hatt Tanmlamas
Ara tank ana yakt tankndan daha aa seviyeye yer- Yakt pompas giriinin ap vastasyla minimum boru
letirildii zaman transfer hatt zerine motorlu vana aplar tanmlanmtr. Boru i ap en az transfer pom-
yerletirilmi olmal. pas girii kadar olmal. Eer boru sistemi yakt uzun
Yakt tankndan motora doru yaplan tm boru tesisat mesafeye tayacaksa boru ap artrlm
balantlarn sonunda borulara vibrasyonun transferini olmal. Boru tesisat ierisinde yksek emme basncn
nlemek iin esnek hortum balants kullanlmaldr. nlemek iin tankn knda yardmc transfer pompa-
14
sna ihtiya duyulabilir. Her ne olursa olsun yakt hatt iin kontrol edilmi olmal. Yakt borularndan motorun
ar emme basnc nlenmi olmal. Yksek emme ba- ierisine pisliin girmesi ve ekilmesini nlemek iin ilk
sncnda boru ierisinde yakt buharlaacak ve motora start tan nce yakt tank ve tm borular bol yaktla
yakt beslemesi dm olacaktr. temizlenerek flalama ileminden geirilmesi gerekir.
Her zaman iin boru tesisat boyutlandrlmas yap- Montaj yapldktan sonra yakt sistemindeki havann bo-
lrken filtreler, tesisat elemanlar ve vanalarda basn altlmas gerekir. Sistemden havay almak iin st nok-
dmesini hesaba katmak gerekir. Yakt boru tesisatn tada kk vana olmaldr. Boru tesisatnda dnler
jeneratr titreiminden izole etmek iin esnek balan- yaplrken dirsek yerine T balant kullann, kullanlan bu
t kullanlmaldr. Bu titreim izole edilmemi ise boru T lerdeki tapalarn sklmesiyle hatlarda fla ile temizlik
tesisat kopabilir veya yakt sznts meydana gelebilir. yaplmas kolaylaacaktr. Tm dili boru ve elemanlar-
Esnek balant hortumu mmkn olduu kadar ksa ve da uygun sv conta kullanlarak szdrmazlk salanm
motora yakn olmal. olmaldr.
Boru tesisatnn geni alana yaylmas durumunda uygun Yakt emi ve dn hatt 250 psi (1,7mPa) pik basnca,
desteklerin monte edilmesi gerekir. Sistemden titreimi 20 in Hg(68 kPa) vakum basncna ve - 40 C (-40 F)
izole etmek iin boru asklar kullannz. (ok souk iklimlerde) ile 93 C (200 F) aras scakla
Scak su borular, elektrik kablolar, egzoz borular ile dayankl olmaldr.
yakt boru tesisat birlikte ekilmemelidir. Yukardaki
boru tesisat evresi scaktr. Her hangi s yklemesi Dikkat: Yakt hatt boru ve elamanlarn contalamada
durumunu ortadan kaldrmak iin yakt tesisatnn izole teflon bant kullanmaynz. Bant paralar enjektrler
edilerek korunmas gerekir. Tm borular monte edil- veya pompa ierisinde tkama meydana getirebilir
meden nce temizlik durumu, sznt ve genel durumu
Maksimum Yakt
Boru ap DN Boru ap
Debisi *
(in) (mm)
GPH (L/h)
80 (303) den az 1/2 15
81-100 (304-378) 1/2 15
101-160 (379-604) 3/4 20
161-230 (605-869) 3/4 20
231-310 (870-1170) 1 25
311-410 (1171-1550) 11/4 32
411-610 (1551-2309) 11/2 40
611-920 (2310-3480) 11/2 40
15
4.10. Yakt Geri Dn Hatlar
Yakt dn hattndaki yakt scak olduundan ,dn zin verilen maksimum yakt dn hatt direnci :
hatt , ya gnlk tanka veya ana yakt tankna balanma- 6,5 in Hg
ldr , bu sayede snan yakt scakln tankn ierisine Yakt dn hattnn ana yakt tankna baland yer ile
datlarak souyacaktr. enjektrler arasndaki kot fark 5 ft (1,5 m)
Statik ykseklikten doan basn kayb =
Dikkat: 1-Yakt geri dn hattn direk olarak yakt 12 in 1 in Hg
emme hattna balamaynz. Balanmas durumunda 5ft (fuel) x -------- x -------------- = 3,7 in Hg
jeneratrn g kaybna ve motorun dzgn alma- ft 16,3 in Fuel
masna sebebiyet verecektir.(Baz elektronik motorlar Dolaysyla srtnmeden doan maksimum basn
yksek yakt scakl korumas olduundan jeneratr kayb = 6,5-3,7 = 2,8 in Hg dan az olmaldr.
grubu stop edebilir.).
2-Yakt geri dn balants , yakt tanknn en st nok- 4.11. Elektrikli Yakt Transfer Pompalar
tasna balanmaldr. Ana yakt tankndan jeneratr grubu gnlk tankna,
3-Yakt geri dn hatt yakt besleme hattndan bir yakt transfer edilmek istendiinde yakt pompasna ih-
boru boyundan daha fazla kk apta olmamaldr. tiya duyulur.
4-oklu jeneratr sistemlerinde her bir jeneratr iin AC pompalar 230 Volt AC besleme elektrii ile al-
ayr dn hatt yaplmaldr. rlar. Transfer pompalar genellikle jeneratr ana akt
tankna yakn yerde monte edilir, yakt seviye anahtarlar
Yakt emi-dn hatt diren hesab; ise gnlk tank ierisine montaj yaplr. Kontrol rleleri,
Yakt emi - dn hattnn basn kayb motor data ve- anahtarlar, lambalar kontrol panosundadr
rilerinde bulunan maksimum deeri amamaldr (Maxi- Ana yakt yanknda yakt yok iken veya k vanas kapal
mum allowable Head on injector return line). iken pompa altrlmamal, altrlr ise pompa hasar
Yakt dn hatt toplam direnci = Yakt dn hattnn grr
statik yksekliinden kaynaklanan basn kayb + sr-
tnmelerden doan basn kayb
rnek ,
MADDE TANIMLAR
1 KRESEL VANA
2 FLTRE
3 EK VALF
4 MEKANK YANGIN VANASI
5 SELENOD VANA
6 YAKIT POMPASI
7 KRESEL VANA
8 2KRESEL VANA
9 AMUR BOALTMA VANASI
1 TAINTI HATTI
VE HAVALIK
HAVALIK
2 DOLDURMA MOTORDAN
BORUSU MENHOL GER DN
YAKIT SEVYE ST
4 5 6
GSTERGES NOT:
TANK KADES ANA TANK YER YAKIT SELENOID KORUMALI YAKIT FLTRES
9 EM
HACMNDEN %10 BYK
OLMALIDIR
ekil 4.3. Jeneratr grubu gnlk servis yakt tank ve ana yakt tank iin tipik balant tesisat
16
ekil 4.4. Ana yakt tankndan, ase- depo gnlk yakt tankna tipik yakt boru tesisat montaj
1. Dolum kabini ile ar dolum alarm ve yakt gstergesi
2. Ana yakt tankna dolum hatt
3. Havalk
4. Yakt gstergesi
5. Ana yakt tank
6. Boaltma vanas
7. Yakt-sv toplama tank
8. k vanas
9. Gnlk yakt tankna giden besleme hatt
10. Elektrikli yakt transfer pompas
11. Elektrikli yakt kesme vanas
12. Yakt-sv toplama tank
13. Gnlk yakt tank (ase ierisinde)
14. Yakt seviye kontrol anahtarlar
15. Manel dolum ve havalk
16. Yakt seviye gstergesi
17. Boaltma vanas
18. Yakt sznt alarm (opsiyon)
19. Motor yakt filtresi
20. Motor yakt pompas
Uyarlar:
! Jeneratrlerin yakt depolama sistemleri standartlara edilmelidir.
uygun olmaldr. ! Ana yakt tankndan gnlk yakt tankna balant boru-
! Yaktn etrafnda alev, kvlcm, sigara imek gibi yanma- su, gnlk tank besleme borusundan byk
ya sebebiyet verebilecek veya eit olmaldr.
olaylara izin vermeyiniz. ! Yakt sistemi hattnda su ayrc n filtre kullanlmas
! Yakt borular , siyah elikten olmal , galvaniz kapl enjektrleri ve yakt pompasn koruyacak ve
olmamaldr.. onlar ar artlarda almalarna yardmc olacaktr.
! Yakt tanklarn tamamen doldurmaynz. Yksek or- ! Yakt temiz ve sudan arndrlm olmaldr.
tam scaklklarnda yaktn genleebilmesi iin yakt
tank kapasitesinin %6s kadar bir boluk braknz. 5. EGZOZ SSTEM
! Motor durduunda yakt borularndan motora doru Egzoz sisteminin amac ; motordan kan egzoz duma-
yerekiminden dolay tabii ak olmamaldr. nn emniyetli bir ekilde bina dna
! Motorun dzgn almas iin yakt scakl kritik bir tanmas ve egzozun meydana getirdii kurum , ses ,
faktrdr.Her bir motor iin azami yakt emi duman gibi kt etkilerin insanlardan ve
scakl bulunmaktadr , bu deerin salanmasna dikkat binalardan uzak yerlere datlmasdr.
17
ekil 5.1. Tipik Egzoz Sistemi
18
mansn drr ve egzoz gaz ssn artrarak sktrma dolay hasar grmesine neden olabilir.
verimine negatif etki ederek motorda hasar olumasna Motor turbo sarjn ve egzoz manifoldunu sarmaynz,
neden olabilir. bu paralar ar sndndan motor ve paralar zerin-
Geri basn limiti bir ok Cummins motorda normal deki termal gerilimi arttracak ve motora yahut parala-
olarak 3 inHg (76 mm Hg) fakat en son motorlarda, rna zarar verecektir.
motor teknik verilerinde maksimum gaz ak 2inHg (50 Eer motorun 2 ayr egzoz k varsa (V tipi motor-
mmHg) esas alnm olabilir.(zin verilen maksimum eg- lar) bu teke indirilip egzoz sistemi bu ekilde devam
zoz geri basnc iin motor veri sayfalarna baknz) ettirilebilir.
oklu jeneratr gruplar iin tek egzoz kanal kullanl-
mas sakncaldr , alan motordan ve dier egzoz kay- 5.2 Egzoz Boru Tesisat Dizayn
naklarndan verilen karbon ve basnl gaz almayan lk olarak sistemin maksimum egzoz geri tepki basnc
motorlarda byk risk ve hasar meydana getirebilir. motor verilerinden renilmelidir.
almayan motor zerindeki turbo arj dier kaynak- Aada rnek olarak verilen sistemin geri tepki basnc
lardan verilen egzoz gaznn ak basnc ile dndrlebi- teorik olarak u ekilde hesaplanr.
lir ve buda turbo arjn rulmannn yasz almasndan
19
1-) lk olarak susturucun neden olduu geri basnc buluruz.Susturucun daha net geri basnc
bulunmak isteniyorsa retici firma ile grlebilir.
a ) Susturucunun i alann buluruz , bunun iin Tablo 5.1 kullanlabilir.
2-) Tm dirsek ve sspanslarn edeer dz boru boylar bulunur. Bunun iin Tablo 5.2 kullanlr.
3-) Egzoz debisi ve boru apna gre Tablo 5.4 den faydalanlarak dz boru boyunun meydana getirdii egzoz geri
tepki basn katsays bulunur .
8 boru ve 4605 cfm iin geri tepki basnc katsays = 0,098 in H2O / feet
4-) Son olarak egzoz siteminde kullanlan elemanlarn meydana getirdii toplam egzoz geri tepki basnc bulunur.
Bu deer , motor veri sayfasnda verilen maksimum egzoz geri tepki basncndan kkse , Egzoz sistemi uygundur
denir.
20
Susturucu ap (in) Susturucu Alan (ft2) Susturucu ap (in) Susturucu i Alan (ft2)
2 0.0218 8 0.3491
2.5 0.0341 10 0.5454
3 0.0491 12 0.7854
3.5 0.0668 14 1.069
4 0.0873 16 1.396
5 0.1363 18 1.767
6 0.1963
21
26
(660)
24
(610)
22
(560)
Egzoz geri tepki basnc in H2O (mm H2O)
16
(406) Meskun Mahal Tip Susturucu
14
(356)
10
(254)
8
(203)
6
(152)
4
(102)
2
(51)
2,000
(610)
4,000
(1219)
6,000
(1829)
8,000
(2438)
10,000
(3048)
12,000
(3658)
14,000
(4267)
16,000
0
22
1.00
(25.4) 2.5 (65) 3.5 (90) 5 (125) 8 (200)
0.50
(12.7)
0.40
(10.1)
10 (250)
0.30
(7.6)
Egzoz geri tepki basnc in H2O/feet (mm H2O/feet)
0.20
(5.1)
12 (300)
0.10
(2.5)
14 (350)
0.05
(1.3)
0.04
(1.0)
0.03
(0.76)
16 (400)
0.02
(0.51)
0.01
200
(5.66)
300
(8.50)
400
(11.33)
500
(14.16)
1,000
(28.3)
2,000
(56.6)
3,000
(85.0)
4,000
(113)
5,000
(142)
10,000
(283)
20,000
(566)
(0.25)
100
(2.83)
23
6. SOUTMA SSTEM maldr.
6.1. Genel Souk evre ssnda jeneratr odas lk tutulmaldr.
Su soutmal motorlar, motordan tahrikli su pompas- Hava girii ve radyatr k grup kullanlmad zaman-
nn soutma suyunu motor blounda bulunan su kanal- larda ayarlanabilen panjurlarla kapatlm olabilir. Ayrca
larndan geirilmesiyle soutulur.Her bir motor kendine termostat kontroll blok suyu stclar da kullanlabilir.
has aada belirtilen soutma sistemlerinden herhangi
birine sahiptirler. 6.3. Uzaa Montajl Radyatrle Soutulmu Sistemler
-Son soutucusuz Uzaa Montajl Radyatr (istee bal)
-Son soutuculu (JWAC) Jeneratrn montaj edildii yerde ses seviyesinin dk
-Hava-hava soutuculu (ATA yada CAC) olmas istenebilir yada jeneratrn montaj edildii yer
-Tek pompa ift devre (1P2L) dar olabilir veyahut jeneratre ulam kstl olabilir , bu
-Cift pompa ift devre (2P2L) ve buna benzer durumlarda uzaa montajl radyatr
Deiik Jeneratr soutma sistemleri vardr ve aada sistemi tercih edilebilir.Radyatrn uzaa konmasyla
verilen sistemlerden biri kullanlm olabilir. jeneratr odasnda grlt seviyesi der. Uzaa radya-
- Motora monteli radyatr tr montaj yapldnda donmaya kar komple sistem
- Uzaa monteli radyatr korunmu olmal.
- Is deitirici ile soutma Soutma sistemini sv ile doldurmadan nce tm te-
sisatn emniyetli olup olmadn kontrol ediniz. Bunlar
6.2. Radyatr Soutmal Gruplar hortum kelepeleri, vidalar, tesisat elemanlar ve ba-
lantlardr. Motor ile uzaa montajl radyatr arasnda
esnek balant elemanlar kullannz.
24
odas havalandrma fan seimi yaplmaldr. Is deitirici ile genleme (header tank) tank jeneratr
Not: Uzaa monteli radyatr sistemlerinde, radyatrn odasna yerletirilmi olmal, genleme tank motorun
ve radyatr ile motor arasndaki borularn toplam ba- ve s deitiricinin zerinde bir seviyeye monte edilme-
sn kayb motor veri sayfalarnda yazan basn kaybn- li. Devir-daim pompas, sistem ierisinde dk seviye-
dan yksek olursa veya radyatr ile motor ye yerletirilmi olmal.
arasndaki kot fark ok fazla olursa (Cummins motorlar Is deitirici boru tesisatnda elik, demir, suni kauuk,
iin genelde 18 m), s deitiricili (Esanjrl) alminyum, bakr veya galvanize elik malzeme kullanl-
soutma sistemine gemek gerekir. mas tavsiye edilmitir.
Is Deitirici (Esanjr) Motora olan tm balantlar esnek borularla olmal, tit-
Sabit souk su kaynann rnein, rezerv su veya ne- reimin transferi nlenmeli.
hir suyu bulunduu yerlerde veya ok uzak mesafelere Is deitirici ve jeneratrden ortama yaylacak s gz
konulan radyatrle motoru soutmak gerekirse s de- nne alnarak jeneratr odas havalandrma fan sei-
itirici motora monte edilebilir. miyaplmaldr.
MAX.YATAY UZUNLUK M
MAX.YKSEKLIK M
6.4. Havalandrma
Yanma havasnn salanmas ve motor, alternatr ve odas havalandrmas genellikle yeterlidir. Oda hava ss
dier kaynaklardan yaylan snn ortadan kaldrlmas iin ykselmesini karlamak iin gerekli hava ihtiyac iin r-
jeneratr odasnn havalandrlmas gerekir. nek hesaplamaya baknz.
- Radyatr fan nemsiz miktarda jeneratr odasnda
Motora monteli radyatrle havalandrma; negatif basnca sebep olacaktr. Boyler tipi stma cihaz-
Bu konfigrasyonda hava jeneratr grubu zerinden larnn jeneratr ile ayn odaya yerletirilmi olmamas
geirilerek radyatr vastasyla odann dna atlr. gerekir.(Byle bir durumda ekstra byk odaya, giri
Aada verilenleri gz nnde bulundurun; penceresi ve /veya kanallar, fanlar gerekir)
- zellikle havalandrma havas uzun kanallar, direnli - Daha souk iklimler iin jeneratr almad zaman
zgaralar ve panjurlardan dar atld zaman, hava ak jeneratr odasn lk tutmak iin hava giri ve k ak-
direnci sistem devreye verilmeden nce llm ol- lklarn kapatmak iin otomatik panjurlar kullanlm ol-
mal ve sistemde ar diren olmamal. maldr. Jeneratr alt zaman termostatik kontroll
- Radyatr fan vastasyla meydana getirilen jeneratr panjurlar kullanlarak radyatr dearj havas oda ierisi-
25
ne dndrlerek jeneratrn ok ksa srede snmasn bedilen s her dakikada 132 BTU dur ve susturucudan
salayacak ve yakt scakln sislenme noktasnn ze- 2500 BTU/dak
rinde kalmas salanacaktr.. Bu giri ve k panjurlar Jeneratrden yaylan s ---------------------- 4100 Btu/dk
jeneratr almadnda tamamen kapal , alt anda Egzoz borusundan 10 x 132----------------- 1320 Btu/dk
yanma havasn salayacak kadar biraz ak , oda scak- Susturucudan yaylan s ----------------------- 2500Btu/dk
-------------------
l belli bir deer ulanca ise tamamen ak olmaldr.
Eer jeneratr acil durum jeneratr ise bu panjurlar Toplam odaya yaylan s --------------------- 7920 Btu/dk
jeneratr altnda tamamen ak vaziyete gelmelidir.
- Hava girileri ,Jeneratr alrken jeneratr odasna 2- Jeneratr odas iin gerekli hava ak miktar; toplam
yamur suyu ve karn girmesini engellemek iin , giri s giriinin msaade edilen oda havasnn scaklk yksel-
hava hznn (150-220 metre/dak) (500-700 feet/dak) mesine blnmesiyle orantldr.
gemeyecek ekilde dizayn edilmelidir.
- Radyatr soutmal gruplarda ,Jeneratrn meydana 55 x Toplam Is (Btu/dk)
getirdii grlt, titreim ve hareketin transferini n- Gerekli hava ak = -----------------------------------
Is ykselmesi (F)
lemek iin radyatre esnek kanal balants salanm
olmal. 55 x 7920
= ------------------------- = 14520 cfm
- Jeneratr odasnda tm cihazlardan yaylan snn , mo- 3
tor, alternatr, egzoz borular ve susturucular, toplam
kW (H) oluturur. Boru ap Borudan Yaylan Is Susturucudan
Yaylan Is
INCHES BTU/dk - foot
- Havalandrma sistemi tam yk altnda jeneratr odas BTU/dk - foot
(mm) (kJ/dk - metre) (kJ/dk - metre)
10 15 C arasnda s ykselmesine msaade edilecek
1.5 (38) 47 (62) 297 (313)
ekilde dizayn edilmi olmaldr. Jeneratr odas ieri-
2 (51) 57 (197) 490 (525)
sinde meydana gelen s 40 C yi aar ise aspirasyon 2.5 (64) 70 (242) 785 (828)
havas motora atmosferden direkt kanal ile salanm 3 (76) 84 (291) 1,100 (1.160)
olmaldr. 3.5 (98) 96 (332) 1,408 (1,485)
Jeneratr odas havalandrmas aadaki formllerle 4 (102) 108 (374) 1,767 (1,864)
H
6 (152) 156 (540) 3,550 (3,745)
V (cfm) = -------------------------- + Motor Yanma Havas 8 (203) 200 (692) 5,467 (5,768)
4100 BTU/dak (72 kW) , 5 -inch (127mm) ve 10 feet QST30G3 137 152
QST30G4 152 N/A
(305 cm) egzoz borusu ve bir adet susturucu ve jene- KTA50G3 176 229
ratr odasna monte edilmitir. Jeneratr odas ierisin- KTA50G8 236 N/A
26
ekil 6.4. Tekli Jeneratr Oda Havalandrmas
27
ekil 6.5. oklu Jeneratr Oda Havalandrmas
28
Dikkat: Radyatr kapan amadan nce soutma sis- korumak iin soutma suyuna antifriz konmu olmaldr.
teminin soumu olduuna emin olunuz. 50% antifriz, 50% su karm tavsiye edilmitir. nk
2 - Gerekli miktarda antifrizi ilave ediniz. DCA4 konsantrasyonu antifrizin miktarna baldr. So-
3 - Radyatr kapan yerinden aln ve hazrladnz sv- utma svsna antifriz konmam ise DCA4 n dozaj
y soutma sistemine koyunuz. daha yksek konsantrasyona ykseltilmi olmaldr. D-
k silisli antifriz tavsiye edilmitir.
Souk havadan korunma
Suyun donmasndan dolay motora gelecek hasara kar
Karm Oran (%)
KARIIM
0/100 30/70 40/60 50/50 60/40 95/5
32F 4F -10F -34F -65F 8F
Donma Noktas
(0C) (-16C) (-23C) (-36C) (-54C) (-13C)
Etilen Glikol
212F 220F 222F 226F 230F 345F
Kaynama Noktas
(100C) (104C) (106C) (108C) (110C) (174C)
32 F 10F -6F -27F -56F -70 F
Donma Noktas
(0C) (-12C) (-21C) (-33C) (-49C) (-57C)
Propilen Glikol
212F 216F 219F 222F 225F 320F
Kaynama Noktas
(100C) (102C (104C) (106C) (107C) (160C)
29
saatlik kullanm iin zel rodaj ya (John Deere ENGI- evre Iss F
NE BREAK-IN OIL) kullanlmaldr. Rodaj ya sevkiyat -40 -20 0 20 40 60 80 100 120 140
srasnda motorunuza Aksa tarafndan konulmutur.
Bu yan bulunmad durumlarda ilk 100 saatlik kulla-
nmda aada belirtilen zellikte yalar kullanlmaldr. 5W40-15W40
CI-4-10W30
API CE
10W30
ACEA E1 (6081 motorlar hari)
CCMC D4 5W30
0W30
Bu sre sonunda John Deere, motorlarnda aadaki
yalarn kullanlmasn tavsiye etmitir. -40 -30 -20 -10 0 10 20 30 40 50 60
John Deere PLUS-50 evre Iss C
John Deere TORQ-GARD SUPREME
John Deere UNI-GARD Tablo 7.1. Tavsiye edilen yalama ya SAE viskozite
dereceleri
Yukardaki yalarn bulunmad durumlarda aadaki
multigrade zellikte yalarn kullanlmasn tavsiye eder. 8. ELEKTRKL START SSTEMLER
Elektrikli start sistemleri genellikle tm jeneratrler
API CG-4
zerinde kullanlmtr. Elektrikli start sistemleri bir Mar
API CF-4
motoru ,ak ve kontrol panosunu ihtiva eder.Daha
ACEA E3
byk motorlarda ift mar motoru dzenlemesi kul-
ACEA E2
lanlm olabilir.
CCMC D5
Elektrikli start sistemleri iin g kayna 12 veya 24 V
CCMC D4
dc. ak grubudur. Start voltaj motor boyutuna gre
belirlenmitir. Daha byk motorlarda kablo apn
Ayrca motorun bulunduu ortama gre aada ki
ve start akmn drmek iin 24 V dc. kullanlr. Mar
tablodan yararlanarak uygun zellikte yalarn seilme-
motoru, jeneratr kontrol modl tarafndan kontrol
si gerekmektedir. (6081 motorlar iin ya viskozitesi
edilir.
15W-40 olan yalar tercih edilmelidir.)
8.1. Ak Sistemleri
7.4. Dosan Dizel Motorlar iin Yalama ya Tavsi-
Kullanlan aklerin tipleri;
yeleri:
Akler kurun asit ve NiCad olarak iki tip dir. Genellik-
Balang da API CH-4 motor ya sevkiyat srasnda
le fiyat uygun olduu iin kurun asitli akler kullanlr.
motorunuza Aksa tarafndan konulmutur. Motordan
NiCad. akler uzun mr gereken yerlerde kullanlr.
en iyi verimi almak ve motorun uzun mrl olmas
Aklerle ilgili daha detayl bilgileri , jeneratrle beraber
iin tavsiye edilen zellikte motor ya kullanlmas uy-
verilen motor bakm ve kullanm klavuzlarndan re-
gun olacaktr. Bilinen marka ya kutularnn zerinde
nebilirsiniz.
bulunan etiket de API CH-4 kalitede ve SAE 15W-40
viskozite motor ya kullannz. evre scaklna ba-
9.EBEKE veya JENERATR n YK e TRANSFER
l olarak viskozite derecesinin aada verilen tabloya
9.1. Otomatik Transfer Panosu ve Panonun yeri ve
gre ayarlanmas uygun olacaktr
Yerleimi
Otomatik Transfer Sisteminde (OTS); ebeke besle-
7.5. Mitsubishi Dizel Motorlar iin Yalama ya Tav-
mesinin arzalanmas/kesilmesi durumunda, acil standby
siyeleri:
jeneratr grubunun anahtarlama tertibi ile yke trans-
Mitsubishi dizel motorlarda API CD veya CF kalitesin-
fer edilmesidir. Otomatik transfer sistemi:
de ya kullanlmas tavsiye edilmitir. Bu yalar turbo
- ebeke beslemesinin arza durumunu izler
arjl ve yksek seviyeli yk uygulamalar iin uygundur.
- Ykn ebeke beslenmesinden, yedek jeneratr sis-
Aada verilen tablodan evre scaklna bal olarak
temine kontrol cihaz tarafndan devreye verilmesini
yan viskozitesi seilebilir. rnein; SAE 15W-40 n
gerekletirir.
anlam; 15W derecesi dk scakl ve 40 derece yk-
OTS de g anahtarlama eleman ve kontrol elaman
sek scakl (W harfi yan souk evre scaklklar iin
vardr. Kontrol eleman jeneratr grubu kontrol mo-
uygun olduunu gsterir)
dl kapsamnda olabilmekte veya daha byk sistem-
30
lerde bina merkezi otomasyon sistemi ierisinde ola-
bilmektedir.
OTS genellikle duvar tipi veya zemin tip pano ierisine
monte edilmitir
Transfer anahtar yerleiminde gz nne alnacak nok-
talar unlardr:
Transfer anahtarn, mmkn olduu kadar datm/
yk panosuna yakn yerletiriniz.
Transfer anahtar; temiz, kuru, havalandrmas iyi ve
ar sdan uzak ortamlarda olmaldr. Ortam ss 40C
zerine kt zaman sigortalar ve alterler daha abuk
ama yapacaktr. Transfer panosu etrafnda yeteri kadar
alma alan bulunmaldr.
Jeneratrden ekilen akmlarn deeri mmkn oldu-
u kadar faza eit datlmaldr. Bir fazdan ekilecek
akmn deeri nominal akm deerini kesinlikle ama-
maldr.
Jeneratr iin kullanlacak kuvvet kablolarnn akm ta- ekil 9.1. Tipik acil g sistemi yerleimi
ma kapasiteleri Tablo10.1de verilmitir.
Transfer paneli ile jeneratr arasnda alter opsiyo- 10 ELEKTRK TESSATI VE KABLO
neldir. 10.1. Genel
Transfer panosu jeneratrden ayr ise mmkn oldu- Elektrik balantlar ve bakm tamamen kalifiye ve tec-
unca datm panosu yanna yerletirilir. Bu durumda rbeli elektrik teknisyenleri tarafndan yaplmaldr.
jeneratrden, ebeke panosundan ve acil yk panosun-
dan transfer panosuna kuvvet kablolar ekilir. Ayrca Uyar
jeneratr kontrol panosundan transfer panosuna 8x2.5 ! Elektrik balantlarn ilgili elektrik kodlarna ve stan-
mm2 kumanda kablosu ekilmelidir. dartlara uygun yapnz.
Transfer panosu jeneratr zerine monte edilmi ise
mteri panosundan ebeke ve yk kablosu olarak iki 10.1.1.Kablolama
adet kuvvet kablosu ekilmesi gerekir. Tipik acil g sis- Jeneratr montajnda kullanlan kablolar; ok nveli (da-
temi tek hat emasndan incelenebilir. ekil 9.1 marl) ve tek nveli olarak deiirler. Kablolar deiik
yollarla denerek montaj yaplr.
9.2. OTS Standartlar - Yap yzeyinde duvarlar, kiriler ve kolonlarda direkt
Avrupa da kullanlan OTS lerde yerel ve uluslararas olarak akta denen kablolar.
standartlar; IEC-947-4 AC1, IEC-158-1, VDE0106, BS - Zeminde kablo kanal ierisinde ak veya kapal olarak
4794 Kuzey Amerika da kullanlan OTS iin UL stan- - Metal veya plastik kablo kanallar veya merdivenler ile
dard geerlidir. - Yer alt kanallar ile
Kablolar mmkn olduu kadar ksa mesafede olacak
9.3. OTS G Anahtarlama Eleman ekilde jeneratr, transfer panosu ve kontrol panosu
Transfer anahtarlar veya drt kutuplu anahtarlama arasnda denirler.
mekanizmalar ve deitirici kontaktr elemanlarndan letken kesitinin seimine etki eden faktrler:
meydana gelirler. Birok OTS sistemleri 1050 Amperin - Is
altnda elektriksel kilitli ve istee bal olarak mekanik - Ykleme ekli (srekli aralkl vb
kilit sistemli iki kontaktrden meydana gelir. 1050 Am- - Ar yke kar yeterli gte korumann yapld tip
perin zerinde devre kesici alter elaman kullanlr. - Kablonun tipi
- Nominal alma voltaj
- Akm tama kapasitesi
- Tanmlanan voltaj dmesi
- Deme tipi ve dier kablolara yaknl
Tesisin planlama safhasnda harmoniklerin retilmesi ve
miktarlar nceden tahmin edilmesi mmkn olmad-
ndan Ntr iletkenleri yksek deerlerde boyutlandrl-
mal ve ntr iletkeninin kesiti en az faz iletkeni kesitinde
olmaldr.
31
Kablo seimi srasnda dikkat edilmesi gereken bir hu- 10.4. Kablo Kanallar
susta ykle jeneratr arasndaki mesafe ile birlikte de- Kablo tesisinde en ok kullanlan metot perfore edilmi
marajl yklerin ( elektrik motoru gibi) olup olmaddr. kanallarn kullanlmasdr.
Eer mesafe ok uzun ise demaraj annda gerilim d- Kanallar galvanize yaplm yada pas nleyici madde kul-
m ok artacandan dolay yk tarafnda voltaj, isten- lanlm olmal. Kelepeler veya klipsler galvanize elik
meyen seviyelere debilir. Bunu nlemek iin aada veya pirin den yaplm olmal. Kablolar dz formda
verilen forml yardm ile daha uygun kesitli yk kablosu yatrlm olmal. Kablo ba kullanmak iin bo alan ol-
seilebilir. mal. Kanal destekleri arasnda yaklak 1200 mm aralk
braklm olmal. Tesis edilen destekler ve kanallar ye-
e = 3 x I x L x (R.Cos + X.Sin ) / 1000 terli mukavemet ve boyutta olmal gelecekte %20 daha
e = gerilim dm ( V ) fazla kablo denecei planlanm olmal
I = Hat akm ( A )
L = Hattn uzunluu (m) 10.5. Koruma
R = Kablonun direnci (ohm/km ) Emniyet nedeninden dolay her bir yk devresinde dev-
X = Kablonun reaktans (ohm/km) re kesici alter veya kontaktr olmas gerekir. Datm
sistemi ile jeneratre balanan kablolar ar yk veya
Bununla beraber kablolar TSE ve VDE standartlarna ksa devre durumunda balanty otomatik olarak kese-
uygun seilmelidir. cek devre kesici ile korunmas gerekir.
Alternatr terminallerine balant yaparken esnek kab-
lo kullanlmas vibrasyon asndan uygun olacaktr. Las- 0,6/1 kV, NYY tip Kablo Akm Tama
tik klfl, esnek iletkenlerden oluan alak gerilim iin, Kapasitesi
Kesit
H07 RN-F tipi kullanlmas uygun olacaktr. 25oC 40oC
Toprakta
Transfer panosu uzakta ise tesisatn tamamnda esnek mm2 Havada Havada
ok ok ok Tek
kablo kullanlmas pahal olacaktr. Esnek kablo kullan- Damarl Damarl Damarl Damarl
H07RN-F
mn minimize etmek iin ara kablo balant ek kutusu
2,5 36 25 22 25 21
kullanlabilir.
4 46 34 30 33 28
Tm montajlarda; ebeke beslemesi girii ve jeneratr
kontrol panosu giri terminalleri arasna kontrol pa- 6 58 44 38 42 36
nosunda bakm yaplabilmesine izin verecek sigortalar 10 77 60 53 57 50
monte edilmesi uygun olacaktr. 16 100 80 71 76 67
25 130 105 94 101 88
10.2. Kablo kesiti Seimi
35 155 130 114 123 110
Kablolar, onlarn akm tama kapasitelerine gre se-
50 185 160 138 155 138
ilmi olmaldr Tam yk akmndan az olmayan akm
tamal. Kablonun kesiti seilirken montajla durumlar 70 230 200 176 191 170
gz nne alnmal. 95 275 245 212 228 205
120 315 285 248 267 245
Akm tama kapasitesine etki eden faktrler: 150 355 325 283 305 271
- leten malzemesi, bakr veya alminyum 185 400 370 322 347 310
- zolasyon malzemesi
240 465 435 380 .... ....
- Kablonun koruma tipi: zrh, klf, yatak
- Montaj ortam ss
- Montaj metodu; ak hava, kanal, dier devrelerin kab- Tablo 10.1. PVC izoleli YVV (NYY) 0.6/1 KV VDE
lolar ile grup yaplm normlarna ve TSEye uygun kablolarn akm kapasite-
lerine gre kablo kesitleri.
10.3. Kablo Montaj Metotlar
Kablo muhafaza kanal 10.6. Ykleme
- Kanallar topraklanm olmal Elektrik datm panosu planlanrken jeneratre dengeli
- Kanallar kablolar denmeden nce montaj yaplm yk verilmesini salamak olduka nemlidir. Eer bir
olmal fazdaki yk dier fazlardaki yklerden ok ise, bu durum
- Bo yer salanm olmal alternatr sarglarnn ar snmasna, fazlar aras k
- Kanal sistemi su ve toz giriine kar korunmal voltajnn dengesiz olmasna ve sisteme bal olan has-
sas 3 fazl cihazlarn hasar grmesine sebep olur. Hibir
32
faz akm jeneratrn nominal akmn amamaldr. Bu Topraklama hatt
ykleme artlarnn yerine getirilmesini salamak iin Topraklama hatt; Topraklama elektrotuna balant
mevcut datm sistemi tekrar dzenlenebilir yapmak iin uygun kesitte bakr iletkendir. Topraklama
iletkeni standartlar karlamal ve en azndan tam yk
10.7. G Faktr akmn tayabilecek kapasitede olmaldr. Topraklama
Jeneratre balanacak olan ykn G faktr (Cos ) hatt iletkeninin topraklama ubuu /ubuklar na ba-
belirlenmelidir. (Cos ) 0,8 in altndaki ykler jenerat- lant noktas kaza ile oluacak tehlikeye kar korunmu
rn ar yklemesine sebebiyet verecektir.Ykn g olmal, fakat inceleme yapmaya uygun olmal.
faktrnn 0.8 ile 1.0 arasnda olmas durumunda jene-
ratr, belirtilmi olan gc verir ve uygun bir ekilde a- Topraklama terminali
lr. Eer ykn g faktr 0.8 in altnda ise jeneratr Topraklama terminali jeneratr devre kesici alterine
ar olarak yklenir. Bu ileri g faktrnn nlenmesi yakn yerletirilir. Topraklama sreklilik iletkeni tm
iin kondansatrler gibi g faktr dzeltme eleman- akm tamayan metallerle; kabin ve jeneratr asesi ile
lar kullanlabilir. temas salanr. Mteri iletme topraklamas terminali
Ancak bu gibi durumlarda jeneratr yke verildiinde, ile balant yaplm olunacaktr.
g faktr dzeltme elemanlar devre d braklma- Topraklama ubuklar
ldr ubuklarn says topraklama direncine bal olarak ye-
terli topraklama elektrotu dzenlemesi gereklidir.
10.8. Paralel alma
Standart bir jeneratr dier jeneratrler ile veya e- 10.9.2. Empedans ( Diren veya Reaktans) Toprak-
beke ile paralel altrmak iin ekstra tehizatlar ba- lama
lanmaldr. Topraklama hatas snrlandrma direnci jeneratr ntr
noktasnn topraklama elektrotuna kalc olarak monte
10.9. Topraklama edilir. Kullanlm olan fazl kablolu sistemlerde,
Jeneratr asesi topraklanmaldr.Jeneratr , titreim gcn sreklilii ile toprak hatas olan yerlerde gerekir.
takozlar zerine monte edildiinden , topraklama ba- 600 volt ve aas olan sistemler.
lantsda esnek olmaldr.Topraklama kablo boyutu tam
yk akm ekebilecek kapasitede ve gerekli standartlar Topraklanmam
salyor olmaldr. AC jeneratr sistemi ve toprak arasnda dahili balant
Jeneratr grubu ve ilikide olduu tm cihazlar, kontrol yaplmamtr. Kullanlm olan fazl kablolu sistem-
ve transfer anahtar panolar jeneratr devreye veril- lerde, gcn sreklilii ile toprak hatas olan yerlerde
meden nce topraklanm olmal. Topraklama sistem gerekir. 600 volt ve aas olan sistemler.
voltaj iin referans salar.
- Yzen voltajlardan saknma 10.9.3. Korumalar
- zolasyon stresini nler Snrlanmam Toprak Kaa
- Bitiik elemanlarda voltajlara dokunmay nler Ntr toprak hatt zerine monte edilmi bir akm trafo-
Deiik topraklama sistemleri vardr. su, akm izleme rlesi ile topraklama noktasna herhangi
bir akm akmasn izleyerek tm sistemi korur. Snrlan-
10.9.1.Kat maddeye topraklama mam (unrestricted) toprak hatas avantajlar:
Sistem, bir topraklama elektrotu vastasyla topraa - Jeneratr, devre kesici ve sistem zerinde tm toprak
gre empedanssz olarak direkt balant ile topraklama hatalar iin koruma salar.
yaplr. Bu metot 600 volt ve daha dk voltajlardaki - yi seviyede personel korumas salar
sistemler iin topraklama elektrotu ile topraklama yap-
lr. Topraklama sistemi aadaki ekilde yaplr; Snrlanm Toprak Kaa
Akm trafolar sistemin tm fazlarna ve ntre balan-
Topraklama Elektrotu mtr. Koruma, toprak noktasna akan akm izleyen
Topraklama elektrotu; bir veya daha fazla bakr kapl akm izleme rlesi, sadece koruma blgesinde ala-
elik ubuklar toprak ierisine aklmtr. Herhangi bir caktr. Blge, jeneratre ve akm trafolarna gre nt-
nokta arasnda tehlikeli voltajn meydana gelmesini n- rn pozisyonu snrlanm olur. Snrlanm toprak kaa
lemek iin yaplan topraklama dk diren deerine korumasnn avantajlar:
sahip olmaldr. - Koruma blgesi dnda meydana gelecek arzalar etki
etmez.
- Ama problemindeki risk seviyesi dktr.
33
- Arza olaynda kablolar ve alternatre etki edecek sna ou kez uygun deerde diren yerletirilir.
hasar drmede koruma rlesi dk seviyelere ayar
edilebilir. 10.9.7. Tipik Topraklama Dzenlemeleri
- Mmkn olan dokunma voltajnn drlmesinde, Yedek jeneratr grubu ile 3 ve 4 kutuplu Otomatik
koruma rlesi ani almalar iin ayarlanabilir. Transfer Anahtar (OTS) topraklamas. izimlerde N
notu Ntr, E notu Toprak olarak belirtilmitir.
Topraklama
letken topraklamas; metal iletkenlerin topraa balan- UTILITY SUPPLY GENERATOR SET
3-POLE AUTOMATIC
masdr (iletken elektriinin topraklanmasdr). Bunun TRANSFER SWITCH
amac:
- Topraklamadan dolay sistemin voltaj dengesi salanr.
- nsan hayat iin tehlike durumu azalr.
- Ntr noktas potansiyeli, referans olarak dzensiz de-
imez.
- Herhangi faz ile toprak arasndaki voltaj sistemin faz
voltajn normalde amamas gerekir. 3 3 WIRES & GROUND
TO LOAD
- Herhangi faz ile toprak arasnda arza akm korumas-
nn yerine getirilmesine izin verilir.
ekil 10.1. 3 Faz 3 Hat Sistem Topraklama balants
10.9.4. Alak Gerilim kl Tek alan Jeneratr
Grubu Topraklamas UTILITY SUPPLY GENERATOR SET
Alak gerilim kl sistemlerde (600 V altnda) alld- 3-POLE AUTOMATIC
TRANSFER SWITCH
gibi ntr iletkeni direkt olarak topraa balanr. Bu
balant alternatrn ntr noktas ve alternatr gvdesi
arasnda birletirme kablosu veya bakr bara ile yaplr.
Alternatr gvdesi, yerel kurallara gre yaplan bina ana
topraklamasna grup halinde bir araya getirilen iletken-
lerin toprakland noktaya balanr.Pratik olarak ntr
ile toprak arasndaki yolun direnci iyi bir toprakta 1
3 4 WIRES & GROUND
dan dk ve yksek direnli toprakta 5 dan dk TO LOAD
olmaldr. ( Maksimum 20 )
Ntr ve toprak arasndaki akan akmn alglanmas ntr ekil 10.2. 3 Faz 4 Hat Sistem Topraklama balants
toprak balantsyla izlenebilir. Fazlarn biri ve toprak 3 kutuplu anahtarlama yaplmaktadr.
arasnda gvdede kontak olmas durumunda bu iki ilet-
ken arasnda akm akacaktr. Topraa direkt olarak UTILITY GENERATOR SET
kontan devam etmesi durumunda alternatr sonsuz 4-POLE AUTOMATIC
TRANSFER SWITCH
ykle karlam olacandan bu durum sarglarn yan-
masna sebep olacaktr.
10.9.6. Yksek Gerim kl Jeneratr Gruplarnn ekil 10.3. 3 Faz 4 Hat Sistem Topraklama balants
Topraklamas 4 kutuplu anahtarlama yaplmaktadr
Yksek gerilimli sistemlerin gvdesinde akm arzas du-
rumunda, topraa kontak yapan fazn birinden topraa 10.9.8. Toprak Hata Koruma emas
akan akm, alak gerilim sistemlerine gre daha yksek Jeneratr sistemleri iin toprak hatas koruma emalar
seviyede ak olacaktr. Bu akmn seviyesini snrlamak alternatr korumak iin tasarlanr.
iin yksek gerilim sistemlerinde fark izleme ve akm Baka trl ifadeler yoksa toprak hatas korumas maki-
trafolarnn alglama yapabilmesi iin toprak ve ntr ara- ne korumas iindir.
34
Jeneratr gruplar iin toprak hatas korumas aada iki rn ses seviyesinin drlmesinde kullanlrlar .
ana kategoride ifade edilmitir.
Snrlanm 11.2. Kabinler:
Snrlanm toprak hatas korumas, sadece bir koruma Ses Kes Kabinleri Jeneratr ses seviyesinin drlme-
blgesine tesir eder. Snrlanm toprak hatas korumas sinde aktif rol oynarlar.
yk zerinde deil, jeneratr grubu sistemi koruma bl-
gesinde toprak hatas olaynda ama olaynn salanmas 11.3. Dier Ses Drcler:
iin kullanlm olmal. Bina iine yaplan yerleimlerde, duvarlara ses kesici ya-
Snrlanmam ltm yaplmas , emi panjurlarna ses kes bariyerlerinin
Snrlanmam toprak hatas korumas, besleme hatt konulmas ,fan susturucular gibi bir ok uygulama Jene-
zerine balanm tm yke tesir eder.Koruma blge- ratr sesinin azaltlmasnda kullanlabilir.
si jeneratr grubuna balanm yklerin tamamna etki
edecektir. Operatr gvenlii iin 30 mA snrlanmam Farkl Ses Seviyelerinin Toplanmas;
koruma kullanlr. Topraklama noktasna 30 mA akm Eer bir yerde 2 yada daha fazla ses kayna mevcut ise,
akmas durumu algland zaman, koruma alr bunlarn meydana getirecei toplam grlt seviyesini
bilmek isteyebilirsiniz, bunun iinde ses seviyelerinin
ZONE OF
belirtilen ynteme gre toplanmas gerekir. Fakat ,ses
PROTECTION seviyesi logaritmik bir deer olduundan basit bir topla-
UTILITY GENERATOR SET ma ilemiyle bu i zlemez.
4-POLE AUTOMATIC
TRANSFER SWITCH 2 ses kaynann meydana getirdii toplam ses seviyesi-
ni bulmak iin Tablo 11-1 kullanlr ;
1. Ses seviyelerini tespit edin (Lp1 , Lp2).
2. Ses seviyeleri arasndaki fark bulun.
3. Tablo 11-1 de hesapladnz fark bulun ve yatay ek-
sen de bu deeri belirleyin
4 WIRES & GROUND
4. Eride bu farka denk gelen ses art miktarn bulun
TO LOAD ve bu deeri en yksek ses seviyesine ekleyin.
3
5. Eer birden ok ses kayna var ise ayn yntemi tek-
rarlayarak toplam ses seviyesini bulun.
ekil10.4. Snrlanm, Toprak hata koruma emas
L+
dB
35
110
100
Ses Seviyesi dB(A)
90
80
70
60
50
7 10 20 50 100 200
(23) (33) (66) (164) (330) (660)
Grlt Kaynandan Olan Uzaklk
ekil 11.2. Ses seviyesinin mesafeye gre dm (Bo Arazi)
36
12.3. Hareketli Paralar elektriksel ok ve flalamay artrr, bu da cihazn hasar
- Dnen fan, kay zerindeki muhafazalar, kelepeler grmesine ve ciddi ekilde personelin yaralanmasna
ve desteklerin balantlar iyi sklm olmal veya lmesine sebep olur. Jeneratrn ii ve d kuru
- Taklarnz, giysinizi ve ellerinizi hareketli paralardan deilse kullanmaynz.
koruyunuz, uzakta tutunuz.
- Eer Jeneratr alr vaziyette ayar yaplmas mecburi 12.6. Soutma svs ve Yakt
ise , scak egzost manifolduna ,dnen paralara vs. aza- Soutma sistemi boken veya motor alyorken su s-
mi dikkat gsteriniz. tcsn altrmaynz , aksi taktirde stcnz zarar gre-
cektir. Soutma svs basn altnda sudan daha yksek
12.4. Tehlikeli Voltaj kaynama noktasna sahiptir.
Elektriksel g retilmesi, aktarlmas ve datm sistem- Motor alyorken radyatr, s deitirici eanjr basn
lerinde uygun olmayan kablo tesisat kullanm yangn kapan amaynz. Jeneratr grubunun soumasna ve
veya elektro ok a sebep olabilir. sistem basncnn normal duruma gelesine izin veriniz.
Elektriksel almalarda personelin korunmas iin kuru Yakt tanklar veya donanmlar, yakt hatlarnda bakr
tahta platformu veya lastik izoleli paspasn zerinde veya galvanize edilmi metal kullanmaynz. Tanklarda
durmal, elbise ve ayakkablar kuru olmal, ellerde bu- ve yakt hatlarnda yakt ierisindeki kkrtten dolay
lunan metal taklar kartlm olmal ve izoleli takmlar slfrik asit meydana gelecektir. Bakr veya galvanize
kullanlmal. hatlar veya tanklarda molekler yapdan dolay yakt ve
- Jeneratr odas zeminine kablolar serili brakmaynz. asit reaksiyona girer.
- Elektrik kablolar ve yakt veya su borular iin ayn
kanal veya boruyu kullanmaynz. 13. YK KARAKTERSTKLER VE UYGULAMALAR
- AC ve DC kablolarn ayn boru ierisinde ekmeyiniz. 13.1. Genel
- Cihaz topraklamasnn doru yapldna emin olun. Jeneratr gruplar ana grev iin kullanlrlar:
Tm metalik paralar anormal durum meydana geldi- 1- Prime veya Srekli ykte kullanma
inde enerjilenebilir. Bu nedenle uygun bir ekilde top- 2- ebeke enerjisiyle birlikte snrl g ihtiyacnda kul-
raklanm olmal. lanma
- zellikle ebeke arasnda otomatik olarak alan je- 3- ebeke enerjisine yedek (Standby) g kayna ola-
neratr her zaman iin bakm, servis yaplaca zaman rak kullanma
jeneratrn almamas iin ak ve ak arj balantla-
rn devre d braknz.. Ak kablolarn skmeden nce 13.2. Yk Karakteristikleri
ak arj cihaznn AC beslemesini kesiniz. Jeneratr Yk karakteristiinin ayrntlarna gre deerlendirilmesi
zerinde alma yaparken jeneratrn kaza ile al- gereklidir. Bu yzden yklerin karakterleri ve doas ge-
mas personel yaralanmasna veya lme sebep olur. rei analiz edilmi, veri tarznda desteklenmi olmaldr.
- Elektriksel kilitlemeleri zmeyiniz. Monte edilmi cihazlar listelenmi ve alma durumu
- Elektriksel balantlar, montajlar yeterli, ehliyetli tek- bilinmelidir.
nisyenler tarafndan yaplmaldr. Deiik g faktr olan ykler olduu yerde aktif ve
- Jeneratr direkt olarak bina elektrik sistemine ba- reaktif ykler gz nne alnmal ve ayr tutulmu ol-
lamaynz. maldr. Daha sonra yk analizine ilave edilmi olmaldr.
- Yksek gerilim jeneratr gruplar alak gerilimlilerden Her ikisi aktif ve reaktif gle zerinde diversite faktr
farkldr. Yksek gerilimli cihazlarla alabilmek iin zel uygulanarak daha hassas tahminler yaplm olabilir.
cihaz ve eitim gerekir. Bu cihazlar zerinde yeterli ei- Jeneratrden alacak motorlarn alma pozisyonu
tim alm personel alma ve bakm yapmaldr.Uygun saptanm olmal. Jeneratr kapasitesi demeraj g ta-
olmayan kullanm ve uygulamalar personel yaralanmas- lebini karlayacak yeterlikte olmaldr. Gelecekte yk
na hatta lmlere sebebiyet verebilir. art ve enerji ihtiyac artabileceinden jeneratr gc
- Enerji bulunan cihaz zerinde alma yapmaynz. genellikle ihtiya kapasitesinin ve demaraj talebinin %20
Yetkisiz personelin elektrikli cihazlara mdahale etme- zerinde karlayabilmesi gerekir. Jeneratr, daha son-
sine msaade etmeyiniz. Yksek voltajl elektrik cihaz- raki ihtiya iin pay ve jeneratrn alaca mahalde
larnda g kaynandan balant kesildikten sonra da meydana gelecek yksek evre scakl ve ykseklie
kalc indklenmi voltaj olur, cihaz emniyetli ekilde bal dk atmosfer basncna bal olarak g d-
topraklanm ve enerjisi boaltlm olmal. mn karlamaya yeterli olmaldr.
37
bulunan elektrik motorlarnn says, deiken ykler, Alternatr gc (kVA veya akm)
farkl tipteki yol verme metotlar ve reziztif (diren) C : ---------------------------------------------------
yklerin karm durumu gz nne alnr. Motorlarn Etki eden yk ( kVA veya akm)
yol alma etkisi ve yol alma sras, alan yklerle birle-
me durumu belirtilmi olmal. Yk profili karlatrmas Voltaj kmesinin Snrlanmas
yaplarak jeneratrn asgari gc seilebilir. Optimum Makine zerinde meydana gelecek voltaj kmesini s-
zmde bulunmada motor ve alternatrn farkl e- nrlamann yollar:
lemesi (uygunsuz birleme) daha iyi olabilir. 1. Tesis edilen ykn en byk paras olan motorlarn
saylar iersinde, yke etki edecek motorlarn yol ver-
Boyutlandrma me sralamasnn snrlanmasyla mmkn olabilir.
Muhakkak ki en byk motor yk zerinde en byk 2. En byk gteki motorlara ilk nce yol verilmelidir.
etkiye sahip olmayabilir. Etki, yol verme metodu tara- 3. Dk transient reaktansl alternatr kullanlabilir, bu
fndan belirlenir. da byk gte alternatrn seilmesi ile olur.
Deiik yol alma metotlar, genel yol verme karakteris-
tikleri ile aada verilmitir. 13.4. Olaand Ykler
13.4.1. Non-lineer Ykler
a) Direkt yol verme : 7 x tya. 0,35 g.f. G elektronii devrelerinde kullanlan tristrler ve tri-
b) Yldz gen yol verme : 2,5 x tya. 0,4 g.f. yaklar, besleme kayna zerinde harmonik bozulmas-
c) Oto trafo yol verme : 4 x tya. 0,4 g.f. na sebep olan byk kaynaklardr. Lineer olmayan yk
d) Elektronik Yumuak yol verme : 3 x tya. 0,35 g.f. akmlar dk empedansl ebeke beslemesi zerinde
e) nverter src ile yol verme : 1,25 x tya. 0,8 g.f. kabul edilebilir snrlar ierisinde olabilir fakat monte
edilen lineer olmayan ykler ierisinde konvertr kulla-
tya: Tam yk akm nlm ise daha nemli durum olacaktr. Meydana gelen
g.f.: G Faktr harmonik akmlar kullanlan konvertr n tipine bal
olacaktr.
zellikle dikkat edilecek hususlar: Harmonik bozulmasn bastrmak iin aadaki metot-
1. Motor yeterli kilo-watt gc verecek gte seilmeli. lar kullanlm olabilir:
2. Alternatr yeterli kVA gc verecek gte seilmeli. Filtre bankalar: Fitre bankalarnn tasarmnda ykn
3. Tanmlanan deiik ykler verildii zaman frekans ve alma sresi gz nne alnr ve empedans bilgisi ge-
voltaj kmesi kabul edilebilir snrlar ierisinde olmal. rekir.
Mteri ve danman bir araya gelip, yk profili hakkn- Tek nite eklinde konvertr gruplar yaplmas
da grp, zellikle en kt ykleme durumuna gre Faz deitirme; retilmi olan harmonikler zel do-
tm dier ykler balyken en ar etki yapacak ykn rultucu trafolar kullanarak, ikinci sarg veya as dei-
yol verilmesi gz nne alnarak ekonomik zm bu- tirilir.
lunmas tavsiye edilmitir. Besleme sisteminin empedansnn drlmesi: Alter-
natr gc artrlarak veya zel dizayn edilmi dk
Voltaj kmesi reaktansl makine kullanlmasyla besleme sisteminin
Jeneratr tarafndan mevcut pasif yk tanyorken ve empedans drlr.
herhangi elektrik motoru alrsa sistem zerinde hz
deiimi meydana gelecek ve daha fazla akm ekilmesi- 13.4.2. Floresan Lambalar
ne sebep olacaktr. Yol verilen motor voltaj kmesine Floresan lambalar saf kapasitif ykler gibi yksek tran-
sebep olacaktr. Ykn anahtarlanmasn (transferi) m- siyentli terminal voltajlar retir. Tesis edilen floresan
teakip alternatr terminallerinde meydana gelen voltaj lambalarn g faktr dzeltici kondansatrleri, frasz
kmesinin bykl makinenin subtransient ve tran- alternatrn dner diyotlar zerinde zorlayc yksek
sient reaktansnn direkt fonksiyonudur. trasient meydana getirir. Ana sarg ile paralel endktif
olmayan uygun diren problemin zm iin kullan-
kme, V = X du ( Xdu + C) labilir.
38
motor gibi davranmasna ve dizel motoru dndrme lak, anma, ar yrtk, gibi durumlar iin kontrol edil-
ynnde etki etmesine sebep olacaktr. Jeneratr hz melidir.
artacak ve dizel motor yakt governr yakt beslemesi- Tm lastiklerin durumlarn kontrol ediniz. Tm sinyal
ni drecektir. Ters gcn tamam mekanik kayplar ve lambalar ve farlarn altn kontrol ediniz.
alternatr elektrik kayplar tarafndan emilmi olmaldr.
Bu nedenle alternatre balanan dier yklerin tamam 14.2. ekme:
re-jeneratif gcn seviyesine eit olmal. Re-jeneratif Rmorklu jeneratr ekerken rmorkun arlnn
gc emmek iin rezistif yk bankas srekli olarak je- manevra ve durma mesafesini etkileyeceini unutma-
neratre balanmas gerekebilir. ynz.
Uyarlar
13.4.4. Kapasitif Ykler ! Rmorklu jeneratr ekerken tm trafik kurallarna,
Kapasitif ykler alternatrn ar ikazlanmasna sebep standartlara ve dier dzenlemelere uyulmaldr. Bunla-
olurlar. Kapasitif yklerin etkisi alternatrn manyetik rn iinde ynetmeliklerde aka belirtilen gerekli do-
doyumu vastas ile snrlanm yksek terminal voltaj nanmlar ve hz snrlar da vardr.
meydana getirir. ! Personelin mobil jeneratr zerinde seyahat etmesine
izin vermeyiniz. Personelin ekme demiri zerinde veya
13.5. Dengesiz Ykler mobil jeneratr ile ekici ara arasnda durmasna izin
Elektrik datm panosu planlanrken jeneratre den- vermeyiniz.
geli yk verilmesini salamak olduka nemlidir. Eer ! Eimli ve yumuak araziden ve ukur, ta gibi engel-
bir fazdaki yk dier fazlardaki yklerden ok ise, bu lerden kannz.
durum alternatr sarglarnn ar snmasna, fazlar aras ! Geriye doru manevra yaparken mobil jeneratrn
k voltajnn dengesiz olmasna ve sisteme bal olan arkasndaki ve altndaki zeminin temiz olduundan emin
hassas trifaze (3 fazl) cihazlarn hasar grmesine se- olunuz.
bep olur. Hibir faz akm jeneratrn nominal akmn
amamaldr. Bu ykleme artlarnn yerine getirilmesini 14.3 Park etme:
salamak iin mevcut datm sistemi tekrar dzenlene- Rmorklu jeneratr arln kaldrabilecek kuru bir
bilir. Kontrol edilemeyen, dengesiz ykten kaynaklana- zemine park ediniz. Eer eimli bir yere park edilecek-
cak arza devre kesici alter veya elektronik ar akm se, aa doru kaymasn nlemek iin yokua apraz
koruyucu cihaz ile nlenebilir. olarak park ediniz. 15 yi aan bir zemine park etme-
yiniz
13.6.Alternatr Balants
Birok alternatre farkl k voltaj verebilecek ekilde SAYIN AKSA JENERATR KULLANICISI;
tekrar balant yaplabilir. Alternatr balantsn dei- Jeneratrnzn sresinden nce garanti d kalmama-
tirerek farkl u gerilimi elde ederken alterler, akm s, sorunsuz almas ve uzun mrl olmas iin aa-
trafolar, kablolar ve l aletleri gibi elemanlarn uy- daki hususlara dikkat ediniz!
gunluu kontrol edilmelidir.
1. Garanti belgesi veya fatura ibraz edilmediinde yap-
13.7. zolasyon Testi lan ilemler garanti kapsamna alnmayacaktr.
Jeneratr altrmadan nce sarglarn yaltm direnci-
ni test ediniz. Bu esnada Otomatik Voltaj Reglatr- 2. Jeneratr grubuna Aksa nn bizzat yetkilendii kiiler
nn (AVR) balantsyla tm kontrol amal balantlar ya da servisler haricinde, 3.ahslarn mdahalesiyle do-
sklmelidir. Dner diyotlar da ksa devre edilmeli veya abilecek arzalar garanti kapsam dndadr.
balants sklmelidir.
500 V luk bir Megger veya benzer bir l aleti kullan- 3. Periyodik bakm izelgesinde belirtilen kontroller ve
labilir. Megger i k terminali ile toprak (ase) arasna bakmlar zamannda ve tam olarak yaplmaldr. Periyo-
balaynz. zolasyon direnci topraa gre 1M dan dik bakm yaplmad iin doacak arzalar garanti kap-
fazla olmaldr. Yaltm direncinin 1M dan az olmas sam dndadr.
durumunda alternatr sarglar kurutulmaldr.
4. Jeneratrn montaj kullanma klavuzunda belirtildii
14.RMORKLU JENERATRLERN EKLMES gibi yaplmaldr. Yaplmad takdirde meydana gelecek
14.1. ekme iin Hazrlk: problemler garanti kapsamna alnmayacaktr.
ekici aracn ve rmorklu jeneratrn zerindeki tm
balant elemanlarn gevek somun, eilmi metal, at- 5. Kirli ve sulu mazot kullanlmas halinde doacak arza-
39
lardan mteri sorumlu olacaktr. 16. Satn alnan jeneratrlerin devreye alma ilemleri,
Aksa Jeneratr Yetkili Servislerince yaplmaldr. M-
6. Motorun ya seimi kullanma klavuzunda belirtildii terinin kendisi veya baka bir servise start ilemi yaptr-
gibi olmaldr. Aksi durumlarda meydana gelecek arza- mas, makinenin garanti kapsam dna kmasna sebep
lar garanti kapsamna girmez. olur.
7. Akler krlma, fazla asit koyma, arjsz brakp sertle- 17. Satn alnan jeneratrlere garanti sresi ierisinde,
tirme durumlarnda garanti d kalr. orijinal ekipmanlar ve projesi haricinde ilave ekipman
ve proje yaplamaz. Yaplmas planlanan ilave almalar
8. Manel jeneratrlerde motor altktan hemen (Jeneratrlerin paralel altrlmas, ilave kontrol nitesi,
sonra mar anahtar braklmaldr. Motor almyorsa pano, transfer pano vs.) Aksa Jeneratrn onay olma-
marlama ilemi 3 defa 10 ar saniyeden fazla yaplma- dan yaplrsa, makine garanti kapsam dna kar.
maldr. Aksi durumlarda mar dilisi krlabilir veya mar
motoru yanabilir. Bu durumlar garanti kapsam dn- 18. Garanti periyodu 2 yl yada 2000 saatdir (hangisi
dadr. nce meydana gelirse) ve jeneratr satn alnd tarihte
balar.
9. Jeneratr yk altnda iken dizel motoru altrma-
ynz ve stop etmeyiniz. altrma ve stop ilemi, yk 15. MTERNN SORUMLULUKLARI;
ayrldktan sonra jeneratr bota iken yaplmaldr. Aksi 1. Makinenin alma artlarnn kontrol edilerek (yer-
halde subaplarda skmalar meydana gelebilir. Gerilim leim, montaj, elektriksel balantlar, kablo kesitleri, ha-
reglatr, trafo ve diyotlarda arzalara yol aar. Bu du- valandrma, egzoz k, yakt yolu vs.) yaplan devreye
rumlar garanti dndadr. alma ilemi, sadece, devreye alma ileminin yapld
mekn ve elektriksel balantlarn yapld nokta iin
10. Otomatik jeneratrlerde kullanlan ebeke kontak- geerlidir. lk start ileminin yapld mekann deitiril-
trnde meydana gelecek ar akm, dk ve yksek mek istenmesi halinde, makinenin evreye bal alma
gerilimden kaynaklanan hasarlardan firmamz sorumlu artlar da deimi olacandan, makinenin salkl a-
deildir. lmasnn ve garanti sresinin devam iin, tekrar Aksa
Jeneratr yetkili servislerince kontrol edilerek iletmeye
11. Jeneratr alyor iken ak kablolarn karmaynz. alnmaldr. Yetkisiz kiilerce yaplacak yer deitirme ve
Ak kablolarnn ok ksa bir sre dahi yerlerinden ka- yeniden devreye alma ilemi, makinenin garanti kapsam
rlmas, arj alternator rlesinin ve elektronik governor dnda kalmasna sebep olacaktr. kinci defa yaplacak
devresinin hasar grmesine sebebiyet verebilir Bu du- devreye alma ileminin cretini mteri karlayacaktr.
rumlar garanti kapsam dndadr.
2. Garanti sresi ierisindeki btn jeneratrlerimizin,
12. Ar veya dengesiz yke bal arzalar (alternator ve periyodik bakm izelgesinde belirtilen tm bakmlar,
kontktr arzalar gibi) garanti kapsam dndadr. Aksa Jeneratrn yetkili servislerine creti karlnda
yaptrlmaldr. Jeneratre ait bakm izelgesi ve bakm
13. Manuel modda motorun alma scaklna gelmesi kitapklar makine ile birlikte mteriye teslim edilmi-
iin jenertr 3-5 dakika bota altrlr , jeneratr dur- tir. Sz konusu bakm kitap ve izelgesinin kaybol-
durulurken ise , ilk nce yk zerinden alnr ve yine mas durumunda mteri, bu kitapklar tekrar temin
motorun soumas iin yksz olarak 3-5 dakikda al- etmekle ykmldr.
trmaya devam edilir.Aksi halde oluacak arzalar garanti
kapsam dndadr. 3. Mteri, imalat hatas dnda ki tm bakm, arza ve
problemlerin giderilmesindeki ucretleri karlayacaktr.
14. Grubun uzun sreli olarak prime gcnn %30 nun
altnda altrlmasndan kaynaklanacak arzalar garanti 4. Kamyon st teslimlerde, nakliye sorumluluu, in-
kapsam dndadr. dirme sorumluluu da dahil olmak zere (kamyon s-
tnde tesliminden sonra, devreye alma (start) ilemine
15. Garanti kapsamndaki btn makinelerimizde, aksa kadar) makinenin uygun artlarda muhafaza edilmesi
jeneratrn orijinal yedek paralar kullanlmaldr. Ori- tamamen mterinin sorumluluu altndadr.
jinal para kullanlmamas durumunda oluacak arzalar
garanti kapsam dndadr. 5. Satn alnan jeneratr 2 ay ierisinde devreye alnma-
yacaksa, sz konusu jeneratre ait depolama koullar
40
salanmak kayd ile bekletilmelidir. Elinizdeki makinenin
depolama koullar ile ilgili gerekli bilgi ve yardm, Aksa
Jeneratr Yetkili Servislerinden temin edebilirsiniz.
41
Jeneratr Grubu, 50 Hz, 400V
sarfiyat tam
Yakt Tank
Kapasitesi
Yalama ya zellii
Kapasitesi
Kapasitesi
ykte
Yakt
Ya
Su
Standby Cummins Not; yan viskozitedeeri Tablo 7.1. den
Modeli
kVA
L/sa Litre Litre Litre
AC 55 55 S3,8-G6 12,8 100 14,5 11
AC 66 66 S3,8-G7 14,7 240 16,5 11
AC 110 110 6BTA 5.9-G5 25 240 19,8 16,4
AC 175 175 6BTAA 5,9-G5 37 380 20,1 16,4
AC 200 200 6CTA 8,3-G2 40 380 27 23,8
AC 250 250 6CTAA 8,3-G2 51,8 470 45 23,8
AC 350 350 QSL9-G5 63 470 28,6 26,5
API CH
AC 400 400 NTA 855-G4 76 700 66 38,6
API CI-4
AC 500 500 QSX 15-G6 95,9 850 66 91
API CF4
AC 550 550 QSX 15-G8 103 850 66 91
AC 703 700 VTA 28-G5 140 1000 170 83
AC 825 825 VTA 28-G6 164 1000 170 83
AC 880 880 QSK 23-G3 161 1500 120 103
AC 1100 1100 QST 30-G4 202 1500 342 154
AC1100K 1100 KTA38G5 209 1500 350 135
AC 1410 1410 KTA 50-G3 261 2000 415 177
AC 1675 1675 KTA 50-G8 289 2000 420 204
AC 2250 2250 QSK 60-G4 394 2000 500 280
Tablo 14.1. Jeneratrlere ait yakt tank(Ak grup), su ve ya kapasiteleri ve tam ykteki yakt sarfiyatlar
Yakt Tank
Kapasitesi
Yalama ya zellii
Kapasitesi
Kapasitesi
ykte
Yakt
Ya
John
Su
kVA Modeli
L/sa Litre Litre Litre
AJD33 33 3029DF128 6,8 70 15,5 6 John Deere PLUS 50
AJD45 45 3029TF120 9,8 100 23 8,5 John Deere TORQ - GARD SUPREME
AJD75 75 4045TF120 16 240 32 13,2 API CG-4
AJD90 90 4045TF220 23 240 32 13,2 API CF-4
Tablo 14.2. Jeneratrlere ait yakt tank, su ve ya kapasiteleri ve tam ykteki yakt sarfiyatlar
42
Jeneratr Grubu, 50 Hz, 400V
sarfiyat tam
Yakt Tank
Kapasitesi
Kapasitesi
Kapasitesi
Yalama ya zellii
ykte
Yakt
Ya
Su
Standby
Model G Doosan
Not; yan viskozitedeeri Tablo 7.1. den
ortam scaklna gre seilmelidir.
kVA
L/sa Litre Litre Litre
AD 220 220 P086TI 43,1 380 46 15,5
AD 275 275 P126TI 53 470 52 23
AD 330 330 P126TI-II 63,1 470 52 23
AD 410 410 P158LE-1 78,7 700 68,5 21
AD 490 485 P158LE 89,3 700 68,5 21 API CH-4
AD 550 550 P180LE 111,6 850 91 35
AD600 600 P180LE 111,6 850 91 35
AD 660 660 P222LE 134 1000 114,2 40
AD 700 700 P222LE-S 130 1000 114,2 40
AD 770 770 P222LE-II 147 1000 110 40
Tablo 14.3. Jeneratrlere ait yakt tank(Ak grup), su ve ya kapasiteleri ve tam ykteki yakt sarfiyatlar
Yakt Tank
Kapasitesi
Kapasitesi
Kapasitesi
Yalama ya zellii
ykte
Yakt
Ya
Su
Standby Mitsubishi
G Motor Not; yan viskozitedeeri Tablo 7.1. den
Model
ortam scaklna gre seilmelidir.
Modeli
kVA
L/sa Litre Litre Litre
AMT11 11 S3L2 3,3 50 6,5 4,2
AMT16 16 S4L2 4,9 50 7,5 6
AMT22 22 S4Q2 6,3 50 12 6,5
AMT33 33 S4S 8,8 70 21 10
APD825M 825 S6R2-PTAA 157 1300 132 94
APD1100M 1100 S12H-PTA 216 1000 244 200 API CD
APD1425M 1425 S12R-PTA 261 2000 335 180 API CF-4
APD1650M 1650 S12R-PTAA2 317 2000 TBD 180
APD1915M 1915 S16R-PTA 348 2000 350 230
APD2100M 2100 S16R-PTA2 399 2000 445 230
APD2250M 2250 S16R-PTAA2 404 2000 413 230
APD2500M 2500 S16R2-PTAW 478 2000 TBD 290
Tablo 14.4. Jeneratrlere ait yakt tank(Ak grup), su ve ya kapasiteleri ve tam ykteki yakt sarfiyatlar
43
Jeneratr Grubu, 400V, 50 Hz Tek damarl kablonun Tek damarl
akm tama kapasitesi kablo kesiti
Standby G Tam yk akm NYY
Cos: 0,8 (40C evre (YVV)
Model scaklnda) Her bir faz iin
kVA
A A mm2
AC 55 55 79 101 25
AC 66 66 95 123 35
AC 110 110 159 191 70
AC 175 175 252 305 150
AC 200 200 288 382 2 x 70
AC 250 250 360 456 2 x 95
AC 350 350 505 610 2 x 150
AC 400 400 577 684 3 x 95
AC 500 500 721 915 3 x 150
AC 550 550 794 915 3 x 150
AC 700 700 1010 1220 4 x 150
AC 825 825 1190 1335 5 x 120
AC 880 880 1270 1525 5 x 150
AC 1100 - 1100K 1100 1587 1830 6 x 150
AC 1410 1410 2035 2440 8 x 150
AC 1675 1675 2417 2745 9 x 150
AC 2250 2250 3248 3660 12 x 150
Tablo 14.5. 40C evre scaklnda tavsiye edilen jeneratr gcne gre tek damar tipinde kablo seim tablosu
Jeneratr Grubu, 400V, 50 Hz Tek damarl kablonun Tek damarl
akm tama kapasitesi kablo kesiti
Standby G Tam yk akm NYY
Cos: 0,8 (40C evre (YVV)
Model scaklnda) Her bir faz iin
kVA A A mm2
AJD33 33 47 57 10
AJD45 45 65 76 16
AJD75 75 108 123 35
AJD90 90 130 155 50
AJD 110 110 158 191 70
AJD 132 132 190 228 95
AJD 170 170 245 305 150
AJD 200 200 288 382 2 x 70
AJD 275 275 397 456 2 x 95
Tablo 14.6. 40C evre scaklnda tavsiye edilen jeneratr gcne gre tek damar tipinde kablo seim tablosu
44
Jeneratr Grubu, 400V, 50 Hz Tek damarl kablonun Tek damarl
akm tama kapasitesi kablo kesiti
Standby G Tam yk akm NYY
Cos: 0,8 (40C evre (YVV)
Model scaklnda) Her bir faz iin
kVA
A A mm2
45
46
DIESEL GENERATING SETS
INSTALLATION RECOMMENDATIONS
First of all, we would like to thank you for your choice of Aksa Generator Set.
It is solid, safe and reliable machine, built according to the latest technology.
This operating and maintenance manual is designed and developed to make you familiar with the generating
system. Please read the following instructions carefully before starting to use your machine.
This manual gives general information about mounting and maintenance of the generator set. Tables and
Never operate, maintain or repair your generator set without taking general safety precautions.
Aksa Jeneratr does not assume responsibility for possible errors. Aksa Jeneratr reserves to make changes
ATTACHMENTS
- CONTROL PANEL WIRING DIAGRAM
- AKSA JENERATR AUTHORIZED SERVICE POINTS
- AKSA JENERATR WHERE TO BUY ABROAD
- CERTIFICATIONS
- WARRANTY CERTIFICATE
1. INTRODUCTION tor set should only be operated by personnel who are
Aksa Generator set is designed to be commissioned, authorized and trained.
when delivered, as soon as the necessary cooling wa-
ter, antifreeze, fuel, lubrication oil and fully charged bat- WARNING
tery are provided. ! Read and understand all safety precautions and warn-
With its long years of experience, Aksa manufactures ings before operating or performing maintenance on
efficient, reliable and quality generator set. the generating set.
This operating and maintenance manual is prepared ! Failure to follow the instructions, procedures, and
to assist the operator in operation and maintenance safety precautions in this manual may increase the pos-
of the generator set. Observing the advices and rules sibility of accidents and injuries.
in this manual will ensure that the generator set op- ! Do not attempt to operate the generating set with a
erates in maximum performance and efficiency for a known unsafe condition.
long time. ! If the generating set is unsafe, put danger notices and
1) Care should be taken to perform more frequent disconnect the battery negative (-) lead so that it can-
maintenance in dirty and dusty environments in order not be started until the condition is corrected.
to keep the generator set in good working condition. ! Disconnect the battery negative (-) lead prior to at-
2) Necessary adjustment and repairs should be made tempting any repairs or cleaning inside the enclosure.
only by authorized and qualified persons. ! Install and operate this generating set only in full com-
3) Each generator set has a model and a serial num- pliance with relevant National, Local or Federal Codes,
ber indicated on a label on the base frame. This plate Standards or other requirements.
also indicates the manufacturing date, voltage, current,
power in kVA and kW, frequency, power factor and 2.2. Installation, Handling and Towing
weight of the generator set. These data are necessary This manual covers procedures for installation, handling
in spare part orders, for warranty validity and for ser- and towing of generating sets. That chapter should be
vice calls. read before installing, moving and lifting the generating
4) Make sure that recommended oil, fuel and coolant set or towing a mobile set. The following safety pre-
are used. cautions should be noted:
5) Use original spare parts for engine and generator.
6) Contact AKSA authorized service in any case. WARNING
7) Take necessary precautions for safety during instal- ! Make electrical connections in compliance with rel-
lation. evant Electrical Codes, Standards or other require-
ments. This includes requirements for grounding and
ground/earth faults.
! For stationary generating sets with remote fuel stor-
age systems, make sure such systems are installed in
compliance with relevant Codes, Standards or other
requirements.
! Engine exhaust emissions are hazardous to personnel.
The engine exhaust for all indoor generating sets must
be piped outdoors via leak-free piping in compliance
with relevant Codes, Standards
and other requirements. Ensure that hot
Figure 1. Aksa Generator Set Dataplate exhaust silencers and piping are clear of
combustible material and are guarded
2. GENERAL SAFETY PRECAUTIONS for personnel protection per safety re-
2.1. General quirements. Ensure that fumes from the
The generator set is designed to be safe when used exhaust outlet will not be a hazard.
in correct manner. However responsibility for safety ! Never lift the generating set by attaching to the en-
rests with the personnel who install, use and maintain gine or alternator lifting lugs, instead use the lifting
the set. If the following safety precautions are followed, points on the base frame or canopy.
the possibility of accidents will be minimized. Before ! Ensure that the lifting rigging and supporting structure
performing any procedure or operating technique, it is in good condition and has a capacity suitable for the
is up to the user to ensure that it is safe. The genera- load.
1
! Keep all personnel away from the generating set WARNING
when it is suspended. ! Do not attempt to operate the
! When mobile generating set, observe all Codes, generating set with the safety
Standards or other regulations and traffic laws.These guards removed. While the gen-
include those regulations specifying required equip- erating set is running do not at-
ment and maximum and minimum speeds. tempt to reach under or around the guards to do
! Do not permit to ride on the mobile generating set, maintenance or for any other reason.
Do not permit personnel to stand or ride on the draw- ! Keep hands, arms, long hair, loose clothing and jewel-
bar or to stand or walk between the generating set and ers away from pulleys, belts and other moving parts.
towing vehicle,
! Do not install and operate a GenSet in an area that Attention: Some moving parts cannot be seen clearly
is classified as dangerous , if necessary precautions are when the set is running.
not taken ! If equipped keep access doors on enclosures closed
and locked when not required to be open.
2.3. Fire and Explosion ! Avoid contact with hot oil, hot coolant, hot exhaust
Fuel and fumes associated with generating sets can gases, hot surfaces and sharp edges
be flammable and potentially explosive. Proper care and corners.
in handling these materials can dramatically limit the ! Wear protective clothing includ-
risk of fire or explosion. However, safety dictates that ing gloves and hat when working
fully charged BC and ABC fire extinguishers are kept around the generating set.
on hand. ! Do not remove the radiator filler cap until the coolant
Personnel must know how to operate them. has cooled. Then loosen the cap slowly to relieve any
excess pressure before removing the cap completely.
WARNING
! Ensure that the generating set room is 2.5. Chemical
properly ventilated. Fuels, oils, coolants, lubricants and battery electrolyte
! Keep the room, the floor and the gen- used in this generating set are typical of the industry.
erating set clean. When spills of fuel, oil, However, they can be hazardous to personnel if not
battery electrolyte or coolant occur, they should be treated properly.
cleaned up immediately.
! Never store flammable liquids near the engine. WARNING
! Do not smoke or allow sparks, flames or other sourc- ! Do not swallow or allow skin contact with fuel, oil,
es of ignition around fuel or batteries. Fuel vapors are coolant, lubricants or battery electrolyte. If swallowed,
explosive. Hydrogen gas generated by charging seek medical treatment immediately.
batteries is also explosive. Do not induce vomiting if fuel is
! Turn off or disconnect the power to the battery swallowed. For skin contact, wash
charger before making or breaking connections with with soap and water.
the battery. ! Do not wear clothing that has been
! To avoiding arcing keep grounded conductive objects contaminated by fuel or lube oil.
(such as tools) a way from exposed live electrical parts ! Wear an acid resistant apron and face shield or gog-
(such as terminals). Sparks and arcing might ignite fuel gles when servicing the battery. If electrolyte is spilled
or vapors. on skin or clothing, flush immediately with large quanti-
! Avoid refilling the fuel tank while the engine is run- ties of water.
ning.
! Do not attempt to operate the generating set with 2.6. Noise
any known leaks in the fuel system. Generator sets that are not equipped
with sound attenuating enclosures
2.4. Mechanical can produce noise levels in excess of
The generating set is designed with guards for protec- 105 dB(A). Prolonged exposure to
tion from moving parts. Care must still be taken to noise levels above 85 dB(A) is haz-
protect personnel and equipment from other mechan- ardous to hearing.
ical hazards when working around the generating set
2
WARNING ! If this is not possible, stand on dry insulating material
Ear protection must be worn when operating or work- and pull the victim clear of the conductor, preferably
ing around an operating generator set. using insulated material such as dry wood.
! If victim is breathing, turn the victim clear of the con-
2.7. Electrical ductor, preferably using insulated material such as dry
Safe and efficient operation of electrical equipment wood.
can be achieved only if the equipments is correctly in- ! If victim is breathing, turn the victim
stalled, operated and maintained. into the recovery position described
below. If victim is unconscious, per-
WARNING form resuscitation as required;
! The generator set must be connected to the load
Open the airway
only by trained and qualified electricians who are au-
Tilt the victims head back and lift the chin upwards.
thorized to do so, and in compliance with relevant
Remove objects from the mouth or throat (including
Electrical Codes, Standards and other regulations.
false teeth, tobacco or chewing gum).
! Ensure that the generating set, including a mobile set
is effectively grounded/earthed in accordance with all Breathing
relevant regulations prior to operation. Check that the victim is
! The generator set should be shutdown with the bat- breathing by looking, listening and
tery negative (-) terminal disconnected prior to at- feeling for the breath.
tempting to connect or disconnect load connections.
! Do not attempt to connect or disconnect load con- Circulation
nections while standing in water or on wet or soggy Check for pulse in the victims neck.
ground.
If no breathing but pulse is present
! Do not touch electrically
Pinch the victims nose firmly.
energized parts of the generator set and/or intercon-
Take a deep breath and seal your
necting cables or conductors with any
lips around the victims lips.
part of the body or with any non in-
Blow slowly into the mouth watching for the chest
sulated conductive object.
to rise. Let the chest fall completely. Give breaths at a
! Replace the generator set terminal
rate of 10 per minute.
box cover as soon as connection or
If the victim must be left to get help, give 10 breaths
disconnection of the load cables is complete. Do not
first and then return quickly and
operate the generator set without the cover securely
continue.
in place.
Check for pulse after every 10 breaths.
! Connect the generator set only to loads and/ or elec-
When breathing restarts, place the
trical systems that are compatible with its electrical
victim into the recovery position de-
characteristics and that are within its rated capacity.
scribed later in this section.
! Keep all electrical equipment clean and dry. Replace
any wiring where the insulation is cracked, cut, abrad- If no breathing and no pulse
ed or otherwise degraded. Replace terminals that are Call or telephone for medical help.
worn, discolored or corroded. Keep terminals clean Give two breaths and start chest compression as
and tight. follows:
! Insulate all connections and disconnected wires. Place heel of hand 2 fingers breadth above ribcage/
! Use only Class BC or Class ABC extinguishers on breastbone junction.
electrical fires. Place other hand on top and interlock fingers.
Keeping arms straight, press down 4-5 cm at a rate
2.8. First Aid for Electric Shock of 15 times per minute.
WARNING Repeat cycle (2 breaths and 15
! Do not touch the victims skin with bare hands un- compressions) until medical helps
til the source of electricity has been takes over.
turned off. If condition improves, confirm pulse and continue
! Switch off power if possible other with breaths. Check for pulse after every 10 breaths.
wise pull the plug or the cable away When breathing restarts, place the victim into the
from the victim. recovery position described below.
3
Recovery position ! If the generating set is going to be lifted, it should be
Turn the victim onto the side. lifted by the lifting points fitted on canopied
Keep the head tilted with the jaw forward to main- sets and most open sets.
tain the open airway.
Make sure the victim cannot roll forwards or back- 3.4. Location
wards. In order to start to consider the possible layouts for
Check for breathing and pulse regu- a site, the following criteria must first be determined:
larly. If either stops, proceed as above. - The total area available and any restrictions within
that area (i.e. buried or overhead services).
WARNING - The access to the site, initially for delivery and installa-
! Do not give liquids until victim is conscious tion purposes, but afterwards for the deliveries of fuel
and servicing vehicles, etc.
3. INSTALLATION, HANDLING AND STORAGE - Ground condition, is it level or sloping?
3.1. General - Any noise constraints. (i.e. the location of offices or
Once the size of the generator set and any associated residential property).
control systems or switchgear have been established, - A forced ventilation system is required for the equip-
plans for installation can be prepared. This section dis- ment, which draws sufficient cooling and aspiration air
cusses factors important in effective and safe installa- into the room at the back of the alternator and dis-
tion of the generator set. charges the air from in front of the engine. Dependent
3.2. Canopies upon the layout of the building, it may be necessary
Installation and handling is simplified when the genera- to install additional ductwork to achieve the airflow
tor set has been equipped with a canopy. The canopy required.
also gives protection from the elements and protec- - Protection from the elements such as rain, snow,
tion from unauthorized access. sleet, wind driven precipitation, flood water, direct
sunlight, freezing temperatures or excessive heat.
3.3. Moving the Generator Set - Protection from exposure to airborne contaminants
The generator set base frame is specifically designed such as abrasive or conductive dust, lint, smoke, oil
for ease of moving the set. Improper handling can se- mist, vapors, engine exhaust fumes or other contami-
riously damage components. Using for a forklift, the nants.
generator set can be lifted or carefully pushed/pulled - Protection from impact from falling objects such as
by the base frame directly with fork. trees or poles, or from motor vehicles or lift trucks.
- Clearance around the generator set for cooling and
access for service: at least 1 meter around the set and
at least 2 meters headroom above the set.
- Access to move the entire generator set into the
room. Air inlet and outlet vents can often be made
removable to provide an access point.
- Limited access to unauthorized personnel.
- If it is necessary to locate the generator set outside of
the building, the generator set should be enclosed in a
canopy. A canopy is also useful for temporary installa-
tions insider or outside the building.
Figure 3.1. Lifting generator set by using a winch - Check the condition of the internal grounding
- Install the grounding bar to the nearest point on the
WARNING generator, propagation resistance (max.1k)
! Never lift the generator set by attaching to the engine Measure the contact voltage of 25 V, 30 mA residual-
or alternator lifting lugs. current should not be higher.
! Always use wood between forks and the base frame
to spread the load and prevent damage. 3.5. Enclosure Generating Set Location
! Ensure the lifting rigging and supporting structure is in Select a position for the enclosure generator that the
good condition and is suitably rated. following conditions are met
! Keep all personnel away from the generator set when Do not install generator where exhaust gas could
it is suspended. accumulate and enter inside or be drawn into a po-
4
tentially occupied building. Ensure exhaust gas is kept The enclosure protection class is IP 23 specifications.
away from any windows, doors, ventilation intakes or All non-current carrying metalwork associated with
other openings that can allow exhaust gas to collect in the equipment must be bonded to a suitable earth
a confined area. connection.
The positioning of the enclosured generator should Select a position for the enclosured generator which
be such that generator exhaust and cooling air flows is as close as possible to the load.
do not create a nuisance or potential source of danger
to personnel or buildings etc. 3.6. Base and Foundation
Prevailing winds and air currents should be taken into Note: Special foundation is unnecessary. A level and
consideration when positioning generator. sufficiently strong concrete floor is adequate.
Place the unit in a prepared location that is flat and The responsibility for the foundation (including seismic
has provisions for water drainage. considerations) should be placed with a civil or struc-
Install the unit in a location where sump pump dis- tural engineer specializing in this type of work.
charge, rain gutter down spouts, roof run-off, land-
scape irrigation or water sprinklers will not flood the Major functions of a foundation are to
unit or spray the enclosure and enter any air inlet our - Support the total weight of the generating set.
outlet openings. - Isolate generator set vibration from surrounding
Protection from the elements such as rain, snow, structures.
sleet, wind driven precipitation, flood water, direct sun-
light, freezing temperatures or excessive heat To support the structural design, the civil engineer will
Protection from exposure to airborne contaminants need the following details:
such as abrasive or conductive dust, lint smoke, oil mist, - the plants operating temperatures
vapors, engine exhaust fumes or other contaminants, - the overall dimensions of the proposed foundation
Protection from impact from falling objects such as mass.
trees or poles or from motor vehicles or lift trucks. - the mounting and fixing arrangements of the genera-
Install the unit where the location of any services tor bed-frame.
such as phone, electrical, fuel, air conditioning, irriga-
tion, including covered, concealed and underground Concrete Plate
services will not be affected or obstructed. The foundation will require at least seven days be-
Install the unit where air inlet and outlet openings tween pouring the concrete and mounting the genera-
will not become obstructed by leaves, grass, snow, etc. tor set to cure. It is also essential that the foundation
If prevailing winds will cause blowing or drifting, you should be level, preferably within 0,5 of any hori-
may need to construct a windbreak to protect the unit, zontal plane and should rest on undisturbed soil.
The ground must be dry, level and firm enough to A reinforced concrete plate provides a rigid support to
support the weight of the enclosure without any sink- prevent deflection and vibration. Typically the founda-
ing with time. A prepared concrete platform with a tion should be 150 mm to 200 mm ( 6 to 8 inches)
smooth surface is necessary to accommodate the gen- deep and its length and wideness should be 150 mm
erating set. Allowance for cable runs and if necessary, more than generator set. The ground or floor below
fuel pipes from a bulk tank must be made into the the concrete plate should be properly prepared and
concrete slab. Check which side of the set fuel lines should be structurally suited to carry the weight of the
and cables originate from. concrete plate and the generator set. (If the generator
There must be adequate access for installation and set is to be installed above the ground floor the build-
commissioning of the generator. Also allowance must ing structure must be able to support the weight of
be made for maintenance. the generator set, fuel storage and accessories). If the
Inspection of exhaust system for leaks and damage floor may be wet from time to time such as in a boiler
and that no materials or debris can come into contact room, the Plate should be raised above the floor. This
with the hot exhaust system, will provide a dry footing for the generator set and for
Inspection of exhaust pipe exit for obstruction. those who connect service or operate it. It will also
There should be enough space around the generator minimize corrosive action on the base-frame. Because
for regular cleaning and maintenance ,and allow the of that concrete plate should be at least 150mm above
canopy doors full open. the floor.The soil depth between concrete Plate and
Do not install the generator closer 1,5m from any floor should be at least 200 mm .
combustibles or structures with combustible walls
5
Calculation
W: Total weight of the Gen.Set. (Including coolant oil,
fuel etc.) I n lbs (kg)
w: Width of the concrete plate in feet (meters)
FLEXIBLE
JOINT l = Length of the concrete plate in feet (meters)
W
SBL = ------------------- (psi)
144 x w x l
W
SBL = ------------------- (kg/m2)
wxl
Sample Calculation
400 kVa Gen.Set, total weight; 4500 kg (wet weight,
coolant, oil etc.). Concrete plate length is 4 m width is
1,5 m and height is 0,35 m.
FERROCONCRETE PLATE
6
3.7.2. Inlet and outlet attenuators with weather lou- comes in at the alternator end of the set, passes over
vers the engine, through the radiator and out of the room
The inlet and outlet attenuators should be installed via a flexible exhaust duct. Without the ducting of the
within a wooden frame and are based on 100 mm. Air- hot air outside the room, the fan will tend to draw that
ways with 200 mm. Acoustic modules. The attenuators hot air around and back through the radiator, reducing
should be fitted with weather louvers with a minimum the cooling effectiveness.
50 % free area, good airflow profile and afford low
restriction airflow access.
The weather louvers should have bird/vermin mesh
screens fitted on the inside, but these screens must
not impede the free flow of cooling and aspiration air.
The outlet attenuator should be connected to the ra-
diator ducting flange with a heat and oil resistant flex-
ible connection Figure 3.2. Directing the air thrown from the radiator
with deviating wings
3.7.3. Combustion Air Inlet
Air for engine combustion must be clean and as cool
as possible. Normally this air can be drawn from the
area surrounding the generating set via the engine
mounted air filter. However, in some cases due to
dust, dirt or heat the air around the set is unsuitable.
In these cases an inlet duct should be fitted. This duct
should run from the source of clean air (outside the
building, another room, etc) to the engine mounted
air filter. Do not remove the air filter and mount it at Figure 3.3. Weak ventilation
a remote location as this can increase the possibility of
dirt leaking through the ductwork and into the engine The air inlet and outlet openings should be large
inlet. enough to ensure free flow of air into and out of the
room. As rough guide the openings should each be at
3.7.4. Exhaust systems least 1,5 times the area of the radiator core.
The exhaust systems shown on the layout drawings
are supported from the ceiling. Should the building
construction be such that the roof supports were
unable to support the exhaust system, a floor stand-
ing steel exhaust stand will be needed. Exhaust pipes
should terminate at least 2-3 m above floor level to
make it reasonable safe for anyone passing or acciden-
tally touching. It is recommended that stainless steel
bellows be fitted to the engine exhaust manifold fol-
lowed by rigid pipe work to the silencer. It is good
installation practice for the exhaust system within the
generator room to be insulated with high density, high
temperature mineral insulation covered by an alumini- Figure 3.4. Air Inlet and Outlet Area
um over clad. This reduced the possibility of operator
burn injury and reduces the heat being radiated to the Both the inlet and outlet openings should have lou-
operating generator room. vers for weather protection. These may be fixed but
preferably should be movable in cold climates so that
3.7.5. Cooling and Ventilation while the generator set is not operating the louvers
The engine, alternator and exhaust piping radiate heat can be closed. This will allow the room to be kept
which can result in a temperature high enough to ad- warm which will assist starting and load acceptance.
versely affect the performance of the generator set. It For automatic starting generator sets. If the louvers are
is therefore important that adequate ventilation is pro- movable they must be automatically operated. They
vided to keep the engine and alternator cool. Proper should be programmed to open immediately upon
air flow, as shown in Figure 3.5. requires that the air starting the engine.
7
Figure 3.5. Air ventilation
8
OPEN TYPE GEN SET INSTALLATION (FOUNDATION SHOULD BE DETERMINED ACCORDING TO GROUND FLOOR)
FLEXIBLE
JOINT
FLEXIBLE
AIR INLET
JOINT
RADIATOR and
EXHAUST OUTLET
DAY NOT
TANK External tanks are used 880 kVA and above.
9
Generating Sets, 50 Hz, 400 V Radiator Hot Air Air Inlet Room's
Room Dimension Outlet Openings Opening Exhaust
Door
Dimensions Louvers s Total Dimensions
Standby m
Cummins Area
Engine Model Power m m Diameter P
Model kVA A B C
Length Width Height Length Width Height D E K m2 L M inch m
S3.8-G6 AC 55 55 1,78 0,95 1,25 3,5 3 2,5 0,7 0,65 0,5 0,6 1,5 2 3 2
S3.8-G7 AC 66 66 2,15 1,05 1,45 3,5 3 2,5 0,7 0,7 0,55 0,65 1,5 2 3 2
6BTA5.9-G5 AC 110 110 2,2 1,05 1,6 4 3 2,5 1 1,1 0,42 1,4 1,5 2 3 2
6BTAA5.9-G5 AC 175 175 2,32 1,15 1,67 4 3,3 2,5 1 1,1 0,55 1,4 1,5 2,2 3 2
6CTA8.3-G2 AC 200 200 2,3 1,15 1,6 4 3,3 2,5 1 1 0,55 1,3 1,5 2,2 5 2
6CTAA8.3-G2 AC 250 250 2,6 1,15 1,75 4,5 3,3 2,5 1 1,25 0,4 1,6 1,5 2,2 5 2
QSL9-G5 AC 350 350 3 1,15 1,9 5 3,3 3 1,2 1,4 0,35 2,1 1,5 2,5 4 2,5
NTA 855-G4 AC 400 400 3,23 1,16 2 5 3,3 3,2 1,25 1,9 0,45 3 1,5 2,5 6 2,5
QSX15-G6 AC 500 500 3,56 1,36 2,1 6 3,5 3,2 1,5 1,45 0,45 3 1,7 2,6 8 2,5
QSX15-G8 AC 550 550 3,56 1,36 2,1 6 3,5 3,2 1,5 1,45 0,45 3 1,7 2,6 8 2,5
VTA28-G5 AC 703 700 4 1,4 2,16 6,5 4 3,5 1,6 1,4 0,6 3 2 2,6 2x6 2,6
VTA28-G6 AC 825 825 4 1,4 2,16 6,5 4 3,5 1,6 1,4 0,6 3 2 2,6 2x6 2,6
QSK23-G3 AC 880 880 4 1,71 2,26 6,5 4 4 2 2 0,25 5 2,4 2,7 8 2,7
QST30-G4 AC 1100 1100 4,4 1,78 2,35 7 4,5 4 2,1 2 0,3 5,3 2,5 3 2x6 3,1
KTA38G5 AC 1100K 1100 4,4 1,78 2,37 7 4,5 4 2,1 2,1 0,3 5,3 2,5 3 2x6 3,1
KTA50-G3 AC 1410 1410 4,95 2,1 2,47 8 4,5 4 2,3 2,1 0,25 6 2,7 3 2x8 3,1
KTA50-G8 (GS8) AC 1675 1675 5,5 2,15 2,6 8 4,5 4 2,3 2,3 0,2 7 2,7 3,5 2x8 3,6
QSK60-G4 ACQ 2250 2250 5,9 2,3 3 9 5 5 2,7 2,6 0,3 9 3,1 4 2x10 4
Table 3.1. Aksa open type 50 Hz Cummins diesel gen-sets dimensions, room sizes, air inlet and outlet openings
dimensions and exhaust pipe dimensions (look figure 3.6. gen-set room) . Without acoustic treatment. Single sets.
10
Radiator Hot Air Air Inlet Rooms
Generating Sets, 60 Hz, 480 V Room Dimension Outlet Openings Door Exhaust
Opening
Dimensions Louvers s Total Dimensions
Cummins Standby m Area
Engine Model Power m m m
Diamet P
Model kWe A B C er
Length Width Height Length Width Height D E K m2 L M inch m
6CTA8.3-G2 AC 182-6 182 2,3 1,15 1,6 4 3,3 2,5 1 1 0,55 1,3 1,5 2,2 5 2
NT855-G6 AC 290-6 290 3,23 1,16 2 5 3,3 3,2 1,25 1,9 0,45 3 1,5 2,5 6 2,5
QSL9-G5 AC 315-6 315 3 1,15 1,9 5 3,3 3 1,2 1,4 0,35 2,1 1,5 2,5 4 2,5
NTA855-G3 AC 355-6 355 3,23 1,16 2 5 3,3 3,2 1,25 1,9 0,45 3 1,5 2,5 6 2,5
QSX15-G6 AC 400-6 400 3,56 1,36 2,1 6 3,5 3,2 1,5 1,45 0,45 3 1,7 2,6 8 2,5
KTA19-G4 AC 496-6 496 3,43 1,32 2,12 6 3,5 3,2 1,5 1,5 0,5 3 1,7 2,6 6 2,5
QSX15-G9 AC 500-6 500 3,56 1,36 2,1 6 3,5 3,2 1,5 1,45 0,45 3 1,7 2,6 8 2,5
QSX15-G9 AC 501-6 501 3,56 1,36 2,1 6 3,5 3,2 1,5 1,45 0,45 3 1,7 2,6 8 2,5
VTA28-G5 AC 600-6 600 4 1,4 2,16 6,5 4 3,5 1,6 1,4 0,6 3 2 2,6 2x6 2,6
QSK23-G3 AC 810-6 810 4 1,71 2,26 6,5 4 4 2 2 0,25 5 2,4 2,7 8 2,7
QSK23-G3 AC 820-6 820 4 1,71 2,26 6,5 4 4 2 2 0,25 5 2,4 2,7 8 2,7
QST30-G3 AC 920-6 910 4,4 1,78 2,35 7 4,5 4 2,1 2 0,3 5,3 2,5 3 2x6 3,1
QST30-G3 AC 921-6 920 4,4 1,78 2,35 7 4,5 4 2,1 2 0,3 5,3 2,5 3 2x6 3,1
QST30-G4 AC 1015-6 1015 4,4 1,78 2,35 7 4,5 4 2,1 2 0,3 5,3 2,5 3 2x6 3,1
QST30-G4 AC 1016-6 1016 4,4 1,78 2,35 7 4,5 4 2,1 2 0,3 5,3 2,5 3 2x6 3,1
KTA50-G3 AC 1275-6 1275 4,95 2,1 2,47 8 4,5 4 2,3 2,1 0,25 6 2,7 3 2x8 3,1
KTA50-G3 AC 1285-6 1285 4,95 2,1 2,47 8 4,5 4 2,3 2,1 0,25 6 2,7 3 2x8 3,1
KTA50-G9 AC 1530-6 1530 5,5 2,15 2,6 8 4,5 4 2,6 2,5 0,3 8,5 2,7 3,4 2x8 3,5
KTA50-G9 AC 1540-6 1540 5,65 2,15 2,6 8 4,5 4 2,6 2,5 0,3 8,5 2,7 3,4 2x8 3,5
QSK60-G7 AC 2000-6 2000 6,0 2,5 3,22 9 5 5 3 3,3 0,3 12 3,1 4 2x12 4
Table 3.2. Aksa open type 60 Hz Cummins diesel gen-sets dimensions, room sizes, air inlet and outlet openings
dimensions and exhaust pipe dimensions. (look figure 3.6. gen-set room) Without acoustic treatment. Single sets.
11
Generating Sets, 50 Hz, 400 V Radiator Hot Air Air Inlet Rooms
Room Dimension Outlet Openings Door
Opening Exhaust
Dimensions Louvers s Total Dimensions
John Deere Standby m Area
Engine Model Power m m m Diamet P
Model kVA A B C er
Length Width Height
Length Width Height D E K m2 L M inch m
3029DF128 AJD33 33 1,5 0,9 1,25 2,8 3 2,5 0,7 0,7 0,4 0,6 1,5 2 2 1/2 1,9
3029TF120 AJD45 45 1,78 0,95 1,15 3 3 2,5 0,7 0,7 0,4 0,6 1,5 2 3 1,9
4045TF120 AJD75 75 2,15 1,05 1,46 4 3 2,5 0,9 1,0 0,42 1,2 1,5 2 3 1,9
4045TF220 AJD90 90 2,15 1,05 1,46 4 3 2,5 0,9 1,0 0,42 1,2 1,5 2 3 2
4045HF120 AJD 110 110 2,15 1,05 1,46 4 3 2,5 0,9 1,0 0,42 1,2 1,5 2 4 2
6068TF220 AJD 132 132 2,3 1,15 1,55 4 3 2,5 0,9 1 0,5 1,2 1,5 2,3 4 2
6068HF120 AJD 170 170 2,4 1,15 1,55 4 3 2,5 1 1 0,52 1,25 1,5 2,3 4 2
6068HF120 AJD 200 200 2,4 1,15 1,55 4 3 2,5 1 1 0,52 1,25 1,5 2,3 4 2
6068HFG55 AJD 275 275 2,75 1,3 1,35 4,5 3,5 2,5 1,15 1,35 0,35 1,9 1,5 2 4 2
Table 3.3. Aksa open type 50 Hz Johndeere diesel gen-sets dimensions, room sizes, air inlet and outlet openings
dimensions and exhaust pipe dimensions (look figure 3.6. gen-set room). Without acoustic treatment. Single sets.
3029TF120 AJD 39-6 39 1,78 0,95 1,15 3 3 2,5 0,7 0,7 0,4 0,6 1,5 2 3 1,9
4045TF120 AJD 68-6 68 2,15 1,05 1,46 4 3 2,5 0,9 1,0 0,42 1,2 1,5 2 3 1,9
4045TF220 AJD 77-6 78 2,15 1,05 1,46 4 3 2,5 0,9 1,0 0,42 1,2 1,5 2 3 2
4045HF120 AJD 96-6 96 2,15 1,05 1,46 4 3 2,5 0,9 1,0 0,42 1,2 1,5 2 4 2
4045HF120 AJD 97-6 97 2,15 1,05 1,46 4 3 2,5 0,9 1,0 0,42 1,2 1,5 2 4 2
6068TF220 AJD 125-6 125 2,3 1,15 1,55 4 3 2,5 0,9 1 0,5 1,2 1,5 2,3 4 2
6068TF220 AJD 126-6 126 2,3 1,15 1,55 4 3 2,5 0,9 1 0,5 1,2 1,5 2,3 4 2
6068HF120 AJD 148-6 148 2,4 1,15 1,55 4 3 2,5 1 1 0,52 1,25 1,5 2,3 4 2
6068HF120 AJD 177-6 177 2,4 1,15 1,55 4 3 2,5 1 1 0,52 1,25 1,5 2,3 4 2
6068HF120 AJD 182-6 182 2,4 1,15 1,55 4 3 2,5 1 1 0,52 1,25 1,5 2,3 4 2
Table 3.4. Aksa open type 60 Hz Johndeere diesel gen-sets dimensions, room sizes, air inlet and outlet openings
dimensions and exhaust pipe dimensions. (look figure 3.6. gen-set room) Without acoustic treatment. Single sets.
12
Generating Sets, 50 Hz, 400 V Radiator Hot Air Air Inlet Rooms
Room Dimension Outlet Openings Door
Opening Exhaust
Dimensions Louvers s Total Dimensions
Doosan Standby m Area
Engine Model Power m m m Diamet P
Model kVA A B C er
Length Width Height
Length Width Height D E K m2 L M inch m
P08TI AD 220 220 2,68 1,15 1,63 4,5 3,3 3 1 1,2 0,45 1,5 1,5 2,2 3 2
P126TI AD 275 275 2,85 1,3 1,65 5 3,3 3 1,2 1,25 0,4 1,9 1,7 2,4 3 2,4
P126TI-II AD 330 330 2,85 1,3 1,65 5 3,3 3 1,2 1,25 0,4 1,9 1,7 2,4 3 2,4
P158LE-1 AD 410 410 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2X3 2,6
P158LE AD 490 485 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2X3 2,6
P180LE AD 550 550 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2X3 2,6
P180LE AD 600 600 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2x3 2,6
P222LE AD 660 660 3,7 1,4 2,1 5,5 3,5 3,3 17 1,6 0,45 3,4 2,1 3 2X3 2,6
P222LE-S AD 700 700 3,7 1,4 2,2 5,5 3,5 3,3 1,7 1,7 0,4 3,6 2,1 3 2X3 2,6
P222LE-II AD 770 770 3,7 1,4 2,2 5,5 3,5 3,3 1,7 1,7 0,4 3,6 2,1 3 2X3 2,6
Table 3.5. Aksa open type 50 Hz Doosan, room sizes, air inlet and outlet openings dimensions and exhaust pipe
dimensions (look figure 3.6. gen-set room) . Without acoustic treatment. Single sets.
Generating Sets, 60 Hz, 480 V Radiator Hot Air Air Inlet Rooms
Room Dimension Outlet Openings Door
Opening Exhaust
Dimensions Louvers s Total Dimensions
Doosan Standby m Area
Engine Model Power m m m Diamet P
Model kWe A B C er
Length Width Height
Length Width Height D E K m 2 L M inch m
P08TI AD200-6 200 2,68 1,15 1,63 4,5 3,3 3 1 1,2 0,45 1,5 1,5 2,2 3 2
P08TI AD201-6 202 2,68 1,15 1,63 4,5 3,3 3 1 1,2 0,45 1,5 1,5 2,2 3 2
P126TI AD265-6 265 2,85 1,3 1,65 5 3,3 3 1,2 1,25 0,4 1,9 1,7 2,4 3 2,4
P126TI AD270-6 270 2,85 1,3 1,65 5 3,3 3 1,2 1,25 0,4 1,9 1,7 2,4 3 2,4
P126TI-II AD 308-6 308 2,85 1,3 1,65 5 3,3 3 1,2 1,25 0,4 1,9 1,7 2,4 3 2,4
P126TI-II AD 310-6 310 2,85 1,3 1,65 5 3,3 3 1,2 1,25 0,4 1,9 1,7 2,4 3 2,4
P158LE-1 AD 355-6 355 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2X3 2,6
P158LE AD 407-6 407 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2X3 2,6
P158LE AD 408-6 408 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2X3 2,6
P180LE AD 486-6 486 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2X3 2,6
P180LE AD 488-6 488 3,36 1,4 2,04 5,5 3,5 3,3 1,5 1,6 0,45 3 2 3 2x3 2,6
P222LE AD 590-6 590 3,7 1,4 2,2 5,5 3,5 3,3 1,7 1,7 0,4 3,6 2,1 3 2X3 2,6
P222LE AD 595-6 595 3,7 1,4 2,2 5,5 3,5 3,3 1,7 1,7 0,4 3,6 2,1 3 2X3 2,6
P222LE-S AD 625-6 625 3,7 1,4 2,2 5,5 3,5 3,3 1,7 1,7 0,4 3,6 2,1 3 2X3 2,6
Table 3.6. Aksa open type 60 Hz Doosan, room sizes, air inlet and outlet openings dimensions and exhaust pipe
dimensions. (look figure 3.6. gen-set room) Without acoustic treatment. Single sets.
13
Generating Sets, 50 Hz, 400 V Radiator Hot Air Air Inlet Rooms
Room Dimension Outlet Openings Door
Opening Exhaust
Dimensions Louvers s Total Dimensions
Mitsubishi Standby m Area
Engine Model Power m m m Diamet P
Model kVA A B C er
Length Width Height
Length Width Height D E K m2 L M inch m
S3L2 AMT11 11 1,25 0,85 0,95 2,5 3 2,5 0,55 0,5 0,4 0,35 1,5 2 2 1,5
S4L2 AMT16 16 1,35 0,85 0,95 2,5 3 2,5 0,55 0,5 0,4 0,35 1,5 2 2 1,5
S4Q2 AMT22 22 1,38 0,85 1,0 2,5 3 2,5 0,55 0,5 0,4 0,35 1,5 2 2 1,5
S4S AMT33 33 1,5 0,9 1,15 2,5 3 2,5 0,7 0,65 0,4 0,6 1,5 2 2 1,5
S6R2-PTAA APD825M 825 4,1 1,83 2,11 6,5 4 4 1,8 1,96 0,4 3,5 2,5 3 8-10 3
S12H-PTA APD1100M 1100 4,37 2,1 2,21 7 4,5 4 1,9 2,1 0,35 4 2,5 3 8-10 3
S12R-PTA APD1425M 1425 4,43 2,04 2,22 7 4,5 4 2,2 2,1 0,2 4,6 2,5 3 12 3
S12R-PTAA2 APD1650M 1650 4,95 2,2 3,08 8 4,5 5 2,5 3 0,3 7,5 3 4 12 4
S16R-PTA APD1915M 1915 5,16 2,25 2,6 8 4,5 5 2,6 2,3 0,3 6 3 3,5 14-16 4
S16R-PTA2 APD2100M 2100 5,23 2,52 2,96 8 5 5 2,9 2,8 0,2 8 3 4 14-16 4
S16R-PTAA2 APD2250M 2250 5,7 2,21 3,4 9 5 5,5 2,9 3,3 0,15 9,5 3 4,5 14-16 4
S16R2-PTAW APD2500M 2500 6,15 2,38 3,4 9 5 5,5 2,7 3,3 0,3 9 3 4,5 14-16 4
Table 3.7. Aksa open type 50 Hz Mitsubishi diesel gen-sets dimensions, room sizes, air inlet and outlet openings
dimensions and exhaust pipe dimensions. (look figure 3.6. gen-set room) Without acoustic treatment. Single sets.
AIR EXHAUST
Hot air from the generating set is discharged from
the room through a hot air duct (optional) fitted in
AIR INLET
an opening in the wall the same size as the duct.
Air inlet louvre on door or Wall.
The hot air discharge opening is protected from
AIR INLET SURFACE
any obstruction, penetration or infitration of
minimum x 2 the air exhaust area.
foreign elements by a metal louvre.
Use a neoprene foam to seal the hot air dischange
duct in the wall. The exhaust pipe is fitted in the
hot air discharge duct. Hot air from the radiator
passes through the canopy roof.
ELECTRIC CABLES
EARTH TERMINAL
14
4. FUEL SYSTEM
4.1. General mounted.
Dependent upon the specific site layout, the fuel can It is very important that the fuel oil purchased for use
be supplied to the engine either from: in any engine be as clean and water-free as possible.
1. Directly from sub-base fuel tank located under the Dirt in fuel the fuel can clog injector outlets and ruin
generating set. the finely machined precision parts in the fuel injection
2. An intermediate daily service tank located within the system. Water in the fuel will accelerate corrosion of
plant room or generator enclosure, which is automati- these parts.
cally refilled from a bulk storage tank
3. Directly from the bulk storage tank, provided that 4.2. Fuel Oil Recommendations
the outlet connection from this tank is at least 500 The following fuel oil specification is typical.
mm higher than the base on which the generator is
15
injector spill directly to this tank. A typical arrangement
for this is shown in Fig. 4.1.
The principle limitations of this method are:
In order to gravity feed the engine, the outlet from
the bulk storage tank must be a minimum of 500 mm
above the generator plinth level;
The pressure drop of the spill return pipe work must
not exceed that detailed in the Engine Data sheet
The supply pipe work from the bulk storage tank to
16
The filling of the tanks will be by means of a fill connec- tion pressure within the piping. In all cases, excessive
tion housed in a suitable lockable cabinet located so as fuel line suction pressures must be avoided. At high
to permit easy access by delivery tanker. This cabinet suction pressures the fuel vaporize in the piping and
may also house a contents gauge and an overfill alarm the fuel supply to the engine will be decreased. When
connected to the float switch inserted into a manhole sizing piping, always remember to account for pres-
on the tank. sure drop across filters, fittings and restriction valves.
Bulk Tank and its Location Specifications, A flex connector must be added to isolate the engine
Isolation conditions during cleaning and repairing.(for vibration from the fuel piping. If this vibration is not
the places that more than one bulk tanks are stored) isolated, the piping could rupture and leak. The flex-
Fuel inlet connection ible connector must be as close to the engine transfer
Ventilation pumps as possible.
Connection between intermediate fuel tank and Bulk Any expanse of exposed piping must be properly sup-
Tank ported to prevent piping ruptures. Use pipe hangers to
Manhole approx.18 isolate vibration from the system.
Drain valve Exposed fuel piping must never run near heating pipes,
Fuel level indicator furnaces, electrical wiring or exhaust manifolds. If the
Fuel supply connection area around the piping is warm, the fuel lines should
Valve and fuel filter or separator be insulated to prevent the fuel and piping from picking
Overflow tank under the bulk tank. up any excess heat. All pipes should be inspected for
The area that bulk tank will be stored, should be %10 leaks and general condition, including cleanliness be-
larger than bulk tank. fore installation. Back flush all lines to the tank before
The floor should be waterproof and a little bit slope to start-up to avoid pulling excess dirt into the engine and
allow the fluid to flow into a specified area. fuel piping system. After installation, the air should be
Easy access to all around the Bulk tank. bled from the fuel system. A petcock should included
There should be hand or electric pump to drain the at some high point in the system to allow air removal.
sludge from sludge collecting area. Use plugged tees, not elbows, to make piping bends.
All metal parts should be earthed according to local This will allow for cleaning by removing the plugs and
regulations. flushing out the lines. All threaded pipe fittings must be
sealed with a suitable paste.
4.9. Determining Pipe Sizes Supply and return fuel lines must be capable of with-
Minimum pipe sizes are determined by the size of the standing 250 psi(1,7mPa) peak pressure, 20 in Hg
inlet to the fuel transfer pump. The pipe inner diameter (500mm Hg) vacuum, and be capable of operating in a
must be a least as large as the transfer pump inlet. If the temperature of -40 F (-40 C)(in very cold climates)
piping must carry the fuel over long distances, the pipe to 200 F (93 C).
size must be increased. An auxiliary transfer pump at Caution: Do not use tape to seal fuel line fittings. Pieces
the tank outlet may also be needed to avoid high suc- of tape could shear off a jam in the pump or injectors.
40-800 6 0,9 6 1
800-1500 6 0,9 6 1 1/2
1500-2200 6 0,9 6 2
17
Max Fuel Flow Rate Flex NPS DN Boru ap
GPH (L/hr) Hose Pipe (mm)
No.* Size (in)
Less than 80 (303) 10 1/2 15
81-100 (304-378) 10 1/2 15
101-160 (379-604) 12 3/4 20
161-230 (605-869) 12 3/4 20
231-310 (870-1170) 16 1 25
311-410 (1171-1550) 20 11/4 32
411-610 (1551-2309) 24 11/2 40
611-920 (2310-3480) 24 11/2 40
* Generic fuel hose suppliers size specification.
Table 4.2. Recommended Minimum Fuel Hose and Pipe Sizes ; Up to 50 Feet (15 Meters) Equivalent Length.
Example
Maximum Allowable Head on Injector Return Line : 6,5 in Hg
Fuel Return Line is routed 5 ft ( 1,5 m) above the injectors.
Static Head =
12 in 1 in Hg
5ft (fuel) x -------- x -------------- = 3,7 in Hg
ft 16,3 in Fuel
the fuel drain line restriction must then be less than = 6,5-3,7 = 2,8 in Hg (71 mm Hg)
18
ITEM DESCRIPTION
1 GATE VALVE
2 STRAINER
3 NON RETURN VALVE
4 MECHANICAL FIRE VALVE WITH FUSIBLE
LINK SITED OVER AIR IN TAKE ON ENGINE
5 SOLENOID VALVE ENERGISED TO OPEN IN
CONJUNCITION WITH THE PUMP OPERATING
6 FUEL PUMP OPERATED BY FLOAT SWITCH IN
SERVICE TANK
7 GATE VALVE
8 2BSP GATE VALVE
9 SLUDGE OUTLET
1BSP OVERFLOW
VENT VENT PIPE
2BSP FILL PIPE STANDARD
FROM ENGINE
MANHOLE
CAPILLARY TUBE TO ST
4 5 6 SERVICE TANK WITHIN
CONTENTS GAUGE TANK PLINTH NOTE:
SOLENOID PROTECTION SAME ROOM AS SET
9 1 FALL (BY OTHERS) BUNDED AREA CAPABLE
FUEL FILTER
OF CONTAINING 110% OF,
BULK TANK CONTENTS
Figure 4.4. Typical fuel installation using a base tank fed from a bulk tank.
1. Fill cabinet with overfill alarm and 11. Electrical fuel shut off valve
2. Tank fill line 12. Optional band
3. Vent line 13. Day tank incorporated in base frame
4. Contents gauge 14. Float Control switches
5. Bulk storage tank 15. Manuel fill and vent
6. Sludge drain 16. Level gauge
7. Bund tank 17. Drain
8. Outlet valve 18. Leakage alarm unit (optional)
9. Supply line to day tank 19. Fuel filter
10. Electric fuel transfer pump 20. Engine fuel pump
19
WARNING - The size of the fuel lines between Bulk tank and daily
- Fuel storage should be in accordance with local regu- tank should be equal or bigger than the daily fuel sup-
lations. ply lines.
- Do not allow any spark and smoking around the fuel - In fuel system line, using the water filter separators
tanks. will prevent the injectors and fuel pump and it is useful
- Fuel pipes must be made of black pipe, not galvanized for healthy working of the engine.
pipe. - The fuel must be clean and must not contain any
- Dont over fill the fuel tank; allow 6% of tank capacity water
for expansion of fuel.
- When the engine stops, there should not be any 5. EXHAUST SYSTEM
gravitational free flow in the fuel pipes towards of the An exhaust system should be designed to dispel the
engine. exhaust gases to atmosphere at the nearest conveni-
- The fuel temperature is a critical factor for appro- ent point in an installation. The gases must not have
priate working conditions of the engine.Excessive Fuel the opportunity to enter any vital air intakes (windows,
temperature, due to expansion of the fuel, will de- doors, ventilation ducts)
crease the engine output power.
Mounting
Supports Isolation
plate
Silencer
Exhaust System
Flexible Pipe Drain
FLEXIBLE
JOINT
20
Make sure that condensation shouldnt be towards the gine power and engine life, even damage the engine
engine exhaust manifold, so horizontal runs of exhaust turbochargers.
piping should slope downwards, away from the engine The back pressure limit for most Cummins engines is
to prevent condensed water vapor from getting in to 3 ins Hg (76 mm Hg) although gensets using the latest
exhaust manifold. designs are down to 2 ins Hg (50mm Hg) based on
A valve should be mounted on the exhaust system to the maximum exhaust flow stated.(look at the engines
drain the condensed water vapor. datasheets for their exhaust back pressure limits.)
A thimble should be made between the wall that ex- The practice of manifolding or plumbing engines into
haust pipes go through and the exhaust pipe and also a common exhaust system with furnaces, boiler, or
insulation should be made between the thimble and other engines is not recommended. Non - running en-
exhaust pipe . This thimble must be closed from inside gines are at great risk to suffer damage due to the built
and outside of the room by mounting plates. Exhaust up of carbon and condensation from a running engine
outlets may be protected with bird screen. or other exhaust source. The turbocharger on a non
To reduce radiated heat from the exhaust pipework running engine can be driven by the exhaust flow from
within an engine room, it is recommended the pipe- other sources and results and result in turbocharger
work is insulated with insulating wrappers 25mm to bearing damage due to lack of lubrication.
50mm thickness Do not lag exhaust manifolds or turbochargers; this
The exhaust outlet must be fitted with rain cap to pre- will lead to operating deficiencies and failure of parts
vent rainwater and snow from entering the exhaust due to thermal stress
system. If the engine have 2 exhaust outlet , those outlets
The exhaust noise created by the engine must be at- could be connected in to one pipe.
tenuated sufficiently to satisfy all local ordinances
5.2. Sizing
The three common attenuation categories are: Before calculating the exhaust backpressure, engines
- Industrial (or Non-Critical) 12 to 18 dBA attenuation exhaust data should be learned from its datasheet (ex-
- Residential 18 to 25 dBA attenuation haust max. back pressure, flow,temp. etc.)
- Critical 25 to 35 dBA attenuation How to calculate an exhaust system as seen at Figure
5.2. is explained below.
The exhaust back pressure should be as low as pos-
sible, excessive exhaust backpressure reduce the en-
21
90Elbow
Industrial
Silencer 90Elbow
8 Flex. Bellow
FLEXIBLE
JOINT
1-) Determined the exhaust back pressure caused by Silencer , for the most accurate data contact the
silencer manufacturer.
a)Find the cross sectional area of the silencer inlet by using Table 5.1.
8 silencer cross-sectional area = 0,3491 (ft2)
d) Using Table 5.3 , determine the backpressure caused by this flow in the specific silencer used.In this
example , the backpressure caused by silencer is found 12,8 in H20 (12,8 in W.C)
2) Find the equivalent length of all fitting and flexible tube section by using Table 5.2
22
b) 250 mm Flexible tube = 3 ft (the value is taken as the pipe is smaller than 18 inches)
3) Find the backpressure at the given exhaust flow per unit length of pipe for each nominal pipe diameter used in
the system.
The back pressure coefficient for 8 inches pipe and 4605 cfm = 0,098 in H2O/feet
4) Add total back pressure for all elements of the example as follows ,
8 Flex.pipe = 0,098 x 3 ft = 0,294 in H20
2 x 90 Standard elbow = 42 ft x 0,098=4,116 in H20
8 straight pipe back pressure = 2000 +1500 + 4000 = 7500 mm = 24,6 foot (1m = 3,28 foot)
Toplam dz boru boyu = 24,6 x 0,098 = 2,41 in H20
Silencer = 12,8 in H20
Total Back pressure = 0,294 + 4,116 + 2,41 + 12,8 = 19,62 in H20 = 1,44 in Hg
If this values is smaller than the allowable back pressure of the engine ,which is written at the datasheet,
Exhaust system is O.K.
24
(610)
22
Exhaust Pressure, Inches (Millimeters) Water Column
(560)
16
(406) Residential Grade Mufflers
14
(356)
10
(254)
8
(203)
6
(152)
4
(102)
2
(51)
2,000
(610)
4,000
(1219)
6,000
(1829)
8,000
(2438)
10,000
(3048)
12,000
(3658)
14,000
(4267)
16,000
0
24
1.00
(25.4) 2.5 (65) 3.5 (90) 5 (125) 8 (200)
Exhaust Back Inches (Milimeters) Water Column Per Foot of Pipe Length
0.50
(12.7)
0.40
(10.1)
10 (250)
0.30
(7.6)
0.20
(5.1)
12 (300)
0.10
(2.5)
14 (350)
0.05
(1.3)
0.04
(1.0)
0.03
(0.76)
16 (400)
0.02
(0.51)
0.01
200
(5.66)
300
(8.50)
400
(11.33)
500
(14.16)
1,000
(28.3)
2,000
(56.6)
3,000
(85.0)
4,000
(113)
5,000
(142)
10,000
(283)
20,000
(566)
(0.25)
100
(2.83)
25
6. COOLING SYSTEM louvers could be used to close the air inlet and outlet
6.1. General louvers while the generator is not running. In
Liquid cooled engines are cooled by pumping a cool- additional to that, thermostatically controlled block
ant mixture through passages in the engine cylinder heaters could be used to keep the engine warm.
block and heads by means of an engine driven pump.
Engines have specific cooling system as mentioned be- 6.3. Remote Radiator Cooling
low , Remote radiators are optional.
- Not aftercooled Remote mounted radiators are necessary in some ap-
- jacket water aftercooling (JWAC) plications because of space, noise ,or accessibility
limitations .Generator noise level will drop in remote
- Air to air aftercooling (ATA or CAC) radiator application. All remote radiator system has to
- One pump two loop (1P2L) be protected against freezing.
- Two pump two loop (2P2L) Before filling the cooling system check all valves, con-
Some Generator cooling systems are mentioned be- nections, fittings etc. to make sure that there is no
low. leakage. Use flexible pipe between radiator and engine.
- Engine mounted radiator
- Remote Radiator
- Exchanger
Air Intake
Engine
Driven Fan
FLEXIBLE
Radiator
JONT
26
Heat Exchanger Cooling system It is recommended that, steel, artificial rubber, alu-
Heat Exchanger Cooling system could be used in re- minum, copper or galvanized steel pipe could be used
mote radiator applications where the pipe pressure on cooling system
loss is higher than accepted, or if there is raw water The external circuit must be coupled to the engine via
sources around the generator set. a flexible connection which permits engine
An expansion tank is needed and has to be installed movement without restrain and thermal expansion of
above the engine and heat exchanger level. the line and also provides vibration isolation.
Circulation pumps should be installed at the lowest Chose a proper ventilation fans to avoid build up of
level of the cooling system. engine room temperature.
EXPANSON
TANK STRAIN MANOMETER
THERMOMETER
HOT
WATER
OUTLET
EXPANSON TANK
BUTTERFLY VALVE
AND
BUTTERFLY VALVE HEAT
FLEX. CONNECTION
AND EXCHANGER
FLEX. CONNECTION HOT COOLANT INLET
COLD
WATER
INLET BUTTERFLY VALVE BUTTERFLY VALVE
AND AND
FLEX. CONNECTION FLEX. CONNECTION
STRAINER
6.4. Ventilation
Ventilation of the Genset room is necessary to pro- cated in the genset room.In this case, extra large room
vide combustion air to the engine , remove the heat inlet openings and or ducts pressurizing fans etc. may-
emitted from the Genset and any other equipment in be required.
the room - In cold climates, thermostatically controlled louvers
Ventilation of engine mounted radiator cooling system; could be used , louvers will be close when the engine
In this applications , air will flow across the entire gen is not running, it will open partially when the genset is
set from alternator end to radiator end. started for combustion air ,and then will be full open
Recommendations; after genset coolant temp, or room temperature is
- Once all equipments (louvers ,airout inlet and ou- high enough for Generator Set. In this system ,the hot
let ducts etc) is installed ,the air flow restriction must air come out of the radiator could be recirculated in to
be verified to insure that it is within the limits ,before generator room this will help the generator set warm
GenSet is started. up faster and keep fuel temperature higher than the
- In most applications set mounted fans will be capable cloud point.
of providing the required airflow , however some cal- - Airflow should be limited to 500-700 feet/min (150-
culations must be done to verify that fan is adequate. 220 m/min) to prevent rainwater/snow from getting
- The ventilation system may cause a slight negative into GenSet room.
pressure in the genset room, it is recommended that - A flexible duct connector must be provided at the
combustion equipments such as boilers not to be lo radiator to take up generator set movement and vibra-
27
tion and prevent transmission of noise. PIPE HEAT FROM PIPE HEAT FROM
- In order to find total radiated heat (H) to the genera- DIAMETER BTU/MIN-FOOT MUFFLER
tor room , add all heat inputs to the room from all INCHES (mm) (kJ/Min-Meter) BTU/MIN (kJ/Min)
sources (Engine, alternator, exhaust pipes, silencer etc.) 1.5 (38) 47 (62) 297 (313)
2 (51) 57 (197) 490 (525)
- Ventilation system have to be designed to keep the
2.5 (64) 70 (242) 785 (828)
room temperature rise within the limits of 10-15 C
3 (76) 84 (291) 1,100 (1.160)
while the Genset is running at full load. If the room 3.5 (98) 96 (332) 1,408 (1,485)
temperature exceeds 40 C , intake combustion air 4 (102) 108 (374) 1,767 (1,864)
should be taken from outdoors via air duct. 5 (127) 132 (457) 2,500 (2,638)
Ventilating air flow formula; 6 (152) 156 (540) 3,550 (3,745)
8 (203) 200 (692) 5,467 (5,768)
H 10(254) 249 (862) 8,500 (8,968)
V (cfm) = -------------------------- + combustion air flow 12(305) 293 (1014) 10,083 (10,638)
0,0754 x 0,241 x T
veya Tablo 6.1. Heat losses From Uninsulated Pipe and Si-
H lencers
V(m3/dk) = -------------------------- + combustion air flow Not: Use 30% of the heat values given in Table 6.1 for
1,21x0,017x T
insulated systems
ple, sum of radiated heat from engine and alternator QST30G3 137 152
QST30G4 152 N/A
is 4100 BTU/min (72kW) ,10 feet of 5 inch diameter KTA50G3 176 229
exhaust pipe is mounted in the room .Allowable tem- KTA50G8 236 N/A
KTA50G9 N/A 224
perature rise in the room is 30 F .
1- Add the heat inputs to the room from all sources, Table 6.2. Radiated heat from Cummins Engines
find radiated heat from silencer and exhaust pipe from
table 6.1. Radiated heat from 5 inch exhaust pipe is
132BTU/min , radiated heat from silencer is 2500
BTU/min
Radiated heat from GenSet------------------------- 4100 Btu/dk
Radiated heat from exhaust pipe 10 x 132 ----- 1320 Btu/dk
Radiated heat from silencer------------------ 2500 Btu/dk
Total radiated heat---------------------------- 7920 Btu/dk
2- The required airflow account for heat rejection in
the room is proportional to the total heat input di-
vided by allowable room air temperature rise .
55 x Total radiated heat (Btu/dk)
Air Flow = --------------------------------------------------
Temp.Rise (F)
55 x 7920
= ------------------- = 14520 cfm
30
28
Figure 6.4. Single GenSet Air Ventilation
29
6.5. Water Treatment Colant capacity (litre) nits Liter
General 19-28 10 1.0
The engine cooling system is subject to rust and cavita- 29-43 15 1.4
tions attacks. To minimize the severity of this 44-58 20 1.9
condition an anti-corrosive agent can be added to to- 59-77 25 2.4
tally clean and limpid coolant water. 78-115 40 3.8
An antifreeze solution is also required to prevent 116-191 60 5.7
freezing of the coolant in the cold weather. 192-285 90 8.5
286-380 120 11.4
Engine Coolant
Water for coolant should be clean and free from any Table 6.3. Recommended amount of DCA4 according
corrosive chemicals such as chlorides, sulphates and to coolant capacity
acids. It should be kept slightly alkaline with a pH value
in the range 8,5 to 10,5 2. Add the required amount of antifreeze, if used, to
Generally, any water which is suitable for drinking can the water solution and mix thoroughly.
be used, with treatment as described below.
3. Add the coolant to the cooling system
Protection against corrosion Cold Weather Protection
Supplemental Coolant Additive (Cummins DCA4 or Antifreeze must be added to the coolant where there
equivalent) is required to protect the cooling system is any possibility of freezing to protect the engine
from fouling, solder blooming and general corrosion. from damage due to coolant freezing.
The use of antifreeze is also recommended as DCA4 A 50% antifreeze 50 % water mixture is recommended
concentrations are dependent upon the presence of because DCA4 concentrations are dependent upon
antifreeze. Antifreeze also interacts with DCA4 to pro- the presence of antifreeze. The dosage of DCA4 must
vide greater corrosion and cavitation protection. be increased to higher concentration if antifreeze is
Procedure for Treating Coolant not added to the coolant. A low- silicate antifreeze is
1. Add the required amount of water to mixing con- recommended.
tainer and dissolve in the required quantity of DCA
mentioned at table 6,3. the amount of DCA is 4% of
the total coolant capacity.
30
and decrease the noise level by silencer(see the ex- Other oils may be used if they meet one or more of
haust system).Radiator outlet should be ducted to air the following:
out let via flexible joint to avoid recirculation of hot air. John Deere UNI GARDTM
Insufficient air will cause engine power decrease and API Service Classification CG-4
carbon residue on some engine parts. API Service Classification CF-4
ACEA Specification E3
7. LUBRICATING OIL ACEA Specification E2
Oil system of diesel engine is one of the most impor- CCMC Specification D5
tant elements of the engine. Correctly made engine CCMC Specification D4
overhaul (this subject includes oil change periods, filter Multi-viscosity diesel engine oils are preferred
change periods, paying attention about selecting the If diesel fuel with sulfur content greater than 0,5 % is
true type of oil) prolongs the life cost of the engine. used, reduced the service interval by 50%
(15W-40 Lub-oil should be preferred for 6081 model
7.1. Oil Performance Properties engine).
The American Petroleum Institute (API) the American
Society for Testing and Materials (ASTM) and Society 7.4. Lubrication Oil Recommendations for Doosan
of Automotive Engineers (SAE) has developed and Engines
preserved a system in order to classify the lubrication Initial factory fill is high quality break-in oil for API Ser-
oils for their performance categories vice CH-4 grade. To obtain the best engine perfor-
mance and engine life, engine oil is specified engine
7.2. Lubrication Oil Recommendations for Cummins oil is not available, use a reputable brand of engine oil
Engines labeled for API Service CH-4 and SAE viscosity 15W-
Cummins recommends that high quality multi grade 40. Refer to oil identification symbol on the container.
SAE 15W/40 high service engine oil in diesel engines
are used. At ambient temperatures above 15 C is 7.5. Lubrication Oil Recommendations for Mitsubishi
15W40. Engines
The minimum API oil quality levels recommended for Many oil standards, which established through spe-
use is CH / CI-4, CH or CI-4 can be used in areas cial oil depending application of engines and operat-
where CF4 oil is not yet available, but the oil interval ing conditions. Among those standards, SAE viscosity
must be reduced API CA, CB, CC, CD, CE, CG4 cat- grades and API service classifications are mostly used
egories not recommended, do not use to classify engine oils. There are several categories of
diesel engine oils. For Mitsubishi diesel engine, CD or
7.3. Lubrication Oil Recommendations for John CF graded oils are recommended as they are suitable
Deere Engines for supercharging and high load application.
New engines are filled John Deere engine break-in oil. Use the following chart to select the appropriate oil
After the break-in period, use John Deere PLUS-50 viscosity according to the ambient temperature.
or other diesel engine oil as recommended.
Temperature F
IMPORTANT -40 -20 0 20 40 60 80 100 120 140
Do not use John Deere PLUS-50 oil or engine oils
meeting API CG4, API CF4, ACEA E2 or CCMC D5 All Seasons 5W40-15W40
performance levels during the first 100 hours of opera- All Seasons CI-4-10W30
tion of a new or rebuilt engine. These oil will not allow
Winter Conditions 10W30
the engine to break-in properly.
Winter Conditions 5W30
Use oil viscosity based on the expected air tempera-
ture range during the period between oil changes. Arctic Conditions 0W30
31
8. ELECTRIC STARTING SYSTEMS power cables are drawn from generator set, mains
Electric starting systems are generally used on all gen- panel and emergency power panel.Furthermore 8x2,5
sets. mm2 control cable must be drawn from the generator
The power source for electric starting systems is a 12 set control panel.
or 24 VDC battery system. Starting system consist of If the transfer panel is mounted on the GenSet, 2
starter, battery, and control panel .There could be 2 power cables should be taken from Customer Panel,
starters on big engines one of them is Mains the other one is Load cable. You
The starting voltage is determined by engine size, 24 can see a typical emergency power system installation
VDC being used for larger engines to reduce start- at Figure 9.1.
ing current and hence cable size. Control of starting is
via a start solenoid which is controlled by the gen-set 9.2. ATS Standards
control system. European and international standards for ATS are, IEC-
947-4 ACI ,IEC-158-1,VDE0106,BS4794 . UL stand-
8.1. Battery Systems ards are used in North America.
Batteries are of two types lead acid and NiCad. Lead
acid batteries are generally used, being the least ex- 9.3. ATS Power Contactors
pensive. NiCad batteries are used where longer life, Transfer switches could be consists of 3 or 4 pole con-
etc., is required. tactors or a change over contactor (optional). Electri-
Please contact the engine O&M Manuals of the en- cal interlock contactors are used below 1050 A ATS
gines sent with the generator for detailed information. panels, mechanical interlocks are optional. Motorised
Circuit breakers are used above 1050 A ATS.
9. THE PLACEMENT AND INTALLATION OF
TRANSFER SWITCH
MAINS
9.1. ATS Panel and Its Installation GENERATING SET
power panel.
Locate the transfer switch in a place where it is clean, Figure 9.1. Typical emergency power system installa-
not over- heated, and having a good ventilation. tion.
If the environment temperature is above 40C, break-
ers will open more easily. There must be enough 10. ELECTRICAL CONNECTION
working place around the transfer switch. 10.1. General
Share the loads equally to all 3 phases, current from Only full qualified and experienced electrical techni-
one phase should not exceed the nominal current, The cians should carry out electrical installation, service and
size of the power cables according to ampere is on the repair work.
Table 10.1. Warning:
Having breaker between the generator set and the - Make electrical connections in compliance with rel-
transfer switch is optional. evant Electrical Codes, Standards or other
If the transfer switch panel is apart from the genera- requirements.
tor set, transfer switch must be placed as
close as possible to the distributor panel.In this case
32
10.1.1. Cabling 10.2. Cable Size Selection
Single core and multi core cables are used for GenSet Cables should be selected according to their current
installation, there are various ways for cable carrying capacities. The current carrying capacity has to
installation ,some of them are ; be equal or more than full load ampere of the GenSet.
- Around the walls, beams and columns as an open Installation conditions have to be considered too, while
type selecting the cable size.
- On the floor in an open or closed cable duck The factors that affects the cable current carrying ca-
- In a metal or plastic cable duck or ladder cable tray pacity ;
- Underground channels - Substance of the cable , Copper or aluminum
Cables are installed as short as possible between - The type of insulation
GenSet,ATS and Control Panel. - Cable protection type
The factors that affects the cable size; - Ambient temperature of installation area
- Temperature - Installation method ; open ,in a duct, or in a group
- Loading type (continuous etc.) with other circuits cable
- Protection against over loading
- Cable type 10.3. Cable Installation Methods
- Rated Voltage Cable protection duct
- Current carrying capacity - Ducts have to be earthed
- Determined voltage drop - Ducts have to be done before starting the cable in-
- Cable installation type and distance between cables. stallation.
It is almost impossible to determine the harmonic load - There have to be enough empty place
before the GenSet is loaded , so that neuter cable size - Ducts should be protected against dust and water
should be as big as phase cable size.
On the other hand, there is a one more important 10.4. Cable ducts
point while cable cross sections are being selected. If Perforated Cable Ducts are common method used for
the distance between load and generator is too much, cabling system Ducts have to be galvanized or coat-
voltage falling at the load side can be too much at the ed against rust. Clamps and Clips should be made of
transient current duration. The voltage drop across a galvanized steel or brass. Cables should be laid down
cable can be determined as follows: flatwise . There should be empty space for cable con-
nection. The distance between cable ducts supports
3 x L x I x (R. Cos + X. Sin ) should be 1200 mm. the supports should be chosen
e = ------------------------------------------ in proper size and strong enough to carry 20% more
1000 cable that used.
e = Voltage drop (V)
I = Rated current (A) 10.5. Protection
L = Length of conductors (m) The cables connecting the generator set with the dis-
R = Resistance (/km to VDE 0102) tribution system are protected by means of a circuit
X = Reactance (/km to VDE 0102) breaker to automatically disconnect the set in case of
overload or short circuit. (Manual models only)
In additional to that, cables should be in compliance
with relevant Electrical Codes, Standards or other re-
quirements
Due to movement of generator sets on their vibration
mounts, the electrical connection to the set should be
made with flexible cable.
If ATS panel is very far away , it will be expensive to
use flexible cable for all installation ,so that , a cable
connection box could be used to minimize usage of
flexible cable
For all installations, fuses should be used between
mains supply inlet and GenSet control panel supply
inlet terminals, in order to maintenance control panel.
33
10.8. Synchronization
0,6/1 kV, YVV type Cable Current If the GenSet will be synchronized with another Gen-
Capacity Set or Mains , additional equipments will be needed.
Cable
Section Soil 25oC 40oC
at Air at Air
Multiple Multiple Multiple Single H07RN-F
10.9. Grounding / Earthing Requirements
mm2
Core Core Core Core The frame of the generator set must be connected to
2,5 36 25 22 25 21 an earth ground. Since the set is mounted on vibration
30 33 28
isolators, the ground connection must be flexible to
4 46 34
avoid possible breakage due to vibration. Ground con-
6 58 44 38 42 36
nection cables or straps should have at least full load
10 77 60 53 57 50 current carrying capacity and meet applicable regula-
16 100 80 71 76 67 tions.
25 130 105 94 101 88 The generating set and all associated equipment, con-
35 155 130 114 123 110 trol and switchgear panels must be earthed before the
50 185 160 138 155 138
set is put into operation. Earthing provides a reference
for system voltages to:
70 230 200 176 191 170
Avoiding floating voltages
95 275 245 212 228 205
Prevents insulation stress
120 315 285 248 267 245 Allows single earth faults to be detected
150 355 325 283 305 271 Prevents touch voltages on adjacent components
185 400 370 322 347 310 There are a number of different earthing systems:
240 465 435 380 .... ....
10.9.1. Solid Earthing
The system is earthed with a direct connection via
Table 10.1. Current carrying capacity of power cables an earth electrode with no intentional impedance to
earth. This method is used and required by the elec-
10.6. Loading trical code on all low voltage systems, 600 volts and
When planning the electrical distribution system, it is below with a grounded earth electrode. This earthing
important to ensure that a balanced load is presented system is made up of the following:
to the generator set. If loading on one phase is sub-
stantially higher than the other phases it will cause over Earth Electrode
heating in the alternator windings, imbalance in the The earth electrode is one or more copper clad steel
phase output voltage and possible damage to sensitive rods driven into the ground. (neither water or gas
3 phase equipment connected to the system. mains used separately or together are acceptable as an
Ensure that no individual phase current exceeds the earth electrode.) It must have a low resistance to earth
current rating of the generator set. For connection to to prevent a dangerous voltage appearing between
existing distribution system, it may be necessary to re- any points which a person could reach simultaneously
organize the distribution system to ensure these load- and be capable of carrying a large current.
ing factors are met.
Earth Lead
10.7. Power Factor The earth lead is a copper conductor of sufficient
The power factor (Cos ) of the connected load cross sectional area, connecting the earth terminal to
should be determined. Power factors below 0,8 lag- the earth electrode. The point of connection of the
ging (inductive) can over load the generator. The set earthing lead to the earth rod(s) should be protected
will provide its kilowatt rating and operate satisfactorily from accidental damage, but also must be accessible
from 0,8 lagging to unity power factor (1.0) . Particular for inspection.
attention must be given to installations with power fac-
tor correction equipment such as capacitors to ensure Earth Terminal
that a leading power factor is never present. This will The earth terminal is situated to the generator termi-
lead to voltage instability and may result in damaging nal box. The earth continuity conductor bonds all non
over voltages. Generally whenever the generator set is current carrying metalwork, metallic conduit, enclosure
supplying the load any power factor correction equip- and generator frame etc. in the installation and cus-
ment should be switched off. tomer premises, plant room to the earth terminal. The
34
conductor shall be connected to the customer earth It will provide protection discrimination.
terminal, which will be effectively earthed to an earth There is less risk of nuisance tripping.
electrode. The protection relay can be set to low levels, reduc-
ing damage to the alternator or cables in the event of
Earth Rods a fault.
The number of rods that are required to form a satis- The protection relay can be set for instantaneous
factory earth electrode is dependent upon the ground operation reducing the possibility of touch voltages.
resistance. The earth loop resistance (of which the
electrode is part) must be low enough that in the 10.9.4. Earthing
event of an earth fault occurring, sufficient current will Earthing or Grounding a conductor means the connec-
flow to operate the protection devices (fuses or circuit tion of the earth (the earth is a conductor of electric-
breakers). ity). The purpose of this is:
- To decrease hazard to human life
10.9.2. Impedance (Resistance or Reactance) - To stabilize the voltage of the system with respect
Grounding to earth
An earthing fault limiting resistor is permanently in- - To ensure that the voltage between any phase and
stalled in the path of the neutral point of the generator earth does not normally exceed the phase voltage of
phases to the earth electrode. Used on three phase the system
three wire systems where continuity of power with - To reference the neutral point so that its potential
one ground fault is required. Systems 600 volts and does not fluctuate
blow. - To allow a means of implementing protection of fault
current between any phase and earth
Unearthed
No internal connection is made between the AC gen- 10.9.5. Earthing of Low Voltage Single Generating
erator system and earth. Used on three phase, three Sets
wire systems where continuity of power with one It is usual for Low Voltage system (LV) (below 600V
ground fault is required. Used on systems of volts and ), to have their neutral conductor connected directly
below. to earth. This is done between the neutral point of the
alternator frame, with a physical linking cable or copper
10.9.3. Protections bar. The alternator frame should in turn be earthed
Unrestricted Earth Fault into the soil through bonding conductors via the main
A single Current Transformer is fitted in the neutral building earth, in accordance with local legislation. In
earth link, protections is by a simple current sensing practice, the resistance of the path between neutral
relay, which will respond to any current flowing in the and earth should be less than 1 in good soil, and less
earth path, it protects the whole system. The advan- than 5 in highly resistive soil.
tages of unrestricted earth fault are: (Absolute maximum 20)
The neutral to earth connection can be monitored
It provides protection for all earth faults on the gen- to detect current flowing between earth and neutral.
erator, switchgear and system. Current will only flow between earth and neutral. Cur-
It provides a good level of personnel protection rent will only flow between these two conductors in
throughout the system. the case of a short between one of the phases and
earth. A direct sustained short via earth represents a
Restricted Earth Fault near infinite load for the alternator and will result in
Current transformers are fitted in all phases and neu- burning out of the windings.
tral of the system. Protection is by a simple current
sensing relay, which again, will respond to any current 10.9.6. Earthing of High Voltage Generator Sets
flowing in the earth path, it operates only within a pro- In the case of high voltage systems, the fault current
tection zone. which will flow as a result of one phase being shorted
The zone being limited to the generator and the posi- to earth would be many times higher than that of a low
tion of the neutral relative to the current transformers. voltage system. In order to limit this current to a level
It does not discriminate with downstream protection. which is convenient for detection of CTs and discrimi-
The advantages of restricted earth fault protection are: nation a resistance is often placed between neutral and
earth in HV systems.
35
10.9.7. Typical Earthing Arrangements Restricted
Standby generating set earthing with 3 and 4 poles Restricted earth fault protection concerns only one
ATS. N denotes NEUTRAL, E denotes EARTH. zone of protection. Restricted earth fault protection
should be used on generating set systems to confine
UTILITY SUPPLY GENERATOR SET the trip in the event of an earth fault to the generating
3-POLE AUTOMATIC
TRANSFER SWITCH set system zone of protection and not its load. In this
way, it is possible to set up more systems which
discriminate between the earth faults of the load.
Unrestricted
Unrestricted earth fault protection concerns all con-
nected load all the way down the supply line. The zone
3 3 WIRES & GROUND of protection will in effect be all of the loads connected
TO LOAD
to the generating set and the set itself. For operator
safety 30mA unrestricted protection is used. That is
Fig. 10.1. 3 phase 3 wire connection when 30mA is detected in the earth path, the protec-
tion operates.
UTILITY SUPPLY GENERATOR SET
3-POLE AUTOMATIC
TRANSFER SWITCH
ZONE OF
PROTECTION
Fig. 10.2. 3 phase 4 wire connection 3 pole switched 4 WIRES & GROUND
TO LOAD
3
Loudness in dB(A)
90
An easier method is to use the curve below and the Distance From Source in Meters (feet)
L+
dB
12.1. Fire Protection
3 Example ; The design, selection and installation of fire protection
Lp2 = 55 dB systems require the following considerations:
Lp1 = 51 dB
DLp = 4 dB The fire protection system must comply with the
2 L+ = 1,4 dB
Lpresult = 55 + 1.4=56.4 dB
requirements of National Standards.
1.4 dB
Typically, the generator room will be required to
1 have a one hour fire resistance rating. Generator room
construction will have to have a two hour fire resist-
ance rating.
0
0
4 dB
5 10 15 Generator room shall not be used for storage pur-
poses
Table 11.1. Noise Level Calculation Curve The authority may specify the quantity, type and sizes
of approved portable fire extinguishers required for
Effect of distance to Noise Level the generator room.
In a free field area sound level decreases as distance A manual emergency stop station outside the gen-
increases. erator room or enclosure or remote from the genera-
You can use Figure 11-2 to find out the noise level of tor set in an outside enclosure would facilitate shutting
a Gen.Set at a distance. For example as shown at the down the generator set in the event of a fire or an-
Figure 11-2 , if the Gen.Set noise level is 95dB(A) at 7 other type of emergency.
37
General Always ensure that bonding and equipment earthing
Do not fill fuel tanks when the engine is running, are correctly done. All metallic parts that could be-
unless tanks are located outside the generator room. come energised under abnormal conditions must be
Do not permit any flame, cigarette, pilot light, spark, properly earthed.
arcing equipment, or other ignition source near the Always disconnect the batteries and battery charger
generator set or fuel tank. when serving or carrying out maintenance particularly
Fuel lines must be adequately secured and free of on equipment arranged for automatic mains failure op-
leaks. Fuel connection at the engine should be made eration. Always disconnect a battery charger from its
with an approved flexible line. Do not use copper pip- AC source before disconnecting the battery cable. Ac-
ing on flexible lines as copper will become brittle if cidental starting of the generator set while working on
continuously vibrated or repeatedly bent. it can cause severe personal injury or death.
Be sure all fuel supplies have a positive shut-off. Do not tamper with interlocks.
Electrical connections and mountings should be
12.2. Exhaust Gases made only by authorized and qualified persons
Be sure the exhaust system will properly dispel dis- Do not connect the generator set directly to any
charged gases a way from enclosed or sheltered areas building electrical system.
and areas where individuals are likely to congregate. Always follow all applicable state and local electrical
Never connect the exhaust system of two or more codes. Have all electrical installations performed by a
engines. qualified licensed electrician.
Never discharge engine exhaust into a brick, tile or High voltage sets work differently to low voltage ones.
cement block chimney, or a similar structure. Exhaust Special equipment and training is required to work
pulsations could cause severe structural damage. around high voltage equipment. Operation and main-
Exhaust manifold should be protected against to ac- tenance must be done only by persons trained and
cidentally touching. Exhaust pipes and silencer should qualified to work on such devices. Improper use or
be lagged. procedures may well result in personal injury or death.
Do not use exhaust gases to heat a compartment. Do not work on energised equipment. Unauthor-
Ensure that there is independent support for the ex- ised personnel must not be permitted near energised
haust system. No strain should be imposed on the en- equipment. Due to the nature of high voltage electrical
gine exhaust manifolds. Which is especially important equipment includes voltage remains after the equip-
on a turbocharged engine. ment is disconnected from the power source. Equip-
ment should be de-energised and safety earthed.
12.3. Moving Parts
Tighten supports and keep guards in position over 12.5. Water
fans drive belts etc. Make sure that fasteners on the Water or moisture inside a generator increases the
set are secure. possibility of flashing and electrical shock, which can
Keep hands, clothing and jewellery away from mov- cause equipment damage and severe personal injury
ing parts. or death. Do not use a generator which is not dry
If adjustment must be made while the unit is running, inside and out.
use extreme caution around hot manifolds, moving
parts, etc 12.6. Coolant and Fuel
The coolant heater must not be operated while the
12.4. Hazardous Voltages cooling system is empty or when the engine is run-
Improper wiring can cause fire or electrocution, result- ning or damage to the heater will occur. Coolant under
ing in severe personal injury or death and property or pressure have a higher boiling point than water.
equipment damage. Do not open a radiator, heat exchanger or header
For personal protection, stand on a dry wooden plat- tank pressure cap while the engine is running. Allow
form or rubber insulating mat, make sure clothing and the generator set to cool and bleed the system pres-
shoes are dry, remove jewellery from hands and use sure first.
tools with insulated handles. Never use galvanised or copper fuel lines, fittings or
Do not leave cables trailing on the engine room floor. fuel tanks. Condensation in the thanks and lines com-
Do not use the same duct for electric cables and bines with the sulphur in the fuel to produce sulphuric
fuel water lines. acid. The molecular structure of the copper or galva-
Do not run AC and DC cables in the same looms nised lines or thanks reacts with the acid and contami-
or duct nates the fuel.
38
13. LOAD CHARACTERISTIC AND APPLICATIONS Particular care must be taken to ensue that:
13.1. General 1. engines can develop sufficient kilowatts
Generating plants are used in three main duties: 2. alternators can develop sufficient kVA
1) Primary or Base Load Duty 3. frequency and voltage drops can be maintained
2) Peak Looping Operation within acceptable limits when the various loads are
3) Standby to Utility mode applied.
It is recommended that the client, or his consultant be
13.2. Load Characteristics on contacted to discuss the load profile, particularly in
An overall assessment of load characteristics is neces- cases where worst case loading (i.e. the most onerous
sary therefore the nature and characteristics of load impact load starting with all other loads connected)
must be established, supported by analysed data. In- provides a less economical solution in terms of capital
stalled equipment should be listed and duty cycles cost of equipment. A better solution may be achiev-
known. able by re arranging the profile.
The proposed method of plant operation should be
known so that the load factor can be assessed and 13.4. Unusual Loads
demand deduced. 13.4.1. Non-linear Loads
Where loads of different power factor are being con- The use of solid state power devices such as thyris-
sidered, the active and reactive powers should be ters and triacs are major sources of harmonic distor-
segregated and then added separately. More accurate tion in supply networks. The non linear load currents
predictions can be made by applying diversity on both that characterise such equipment may well be within
the reactive and active power. acceptable limits, where the power source is a low im-
Generating capacity must be sufficient to meet peak pedance public utility supply, but if a converter is used
power demand, even if the peak only occurs for a few in the installation the non linear loads will be more
hours once a year. Future load expansion should not significant and less predicable. The harmonic currents
be ignored, as there may well be a rise in energy re- generated will depend upon the type of converter
quirements. Designs must be flexible enough to allow used, where as the resulting voltage harmonics will re-
for planned expansion with the minimum of disruption late to the property supply network.
to existing plant. It is usual to provide at the outset, To suppress harmonic distortion the following meth-
10 to 20% margin of capacity over and above that re- ods can be used;
quired by the annual peak demand. Filter banks: their design requires considerations of the
load duty cycle and knowledge of the impedances, to
13.3. Motor Starting avoid them acting as sinks for harmonics generated
The effect of motors starting and start sequence elsewhere.
should be determined in conjunction with the running Grouping the converters to form a single unit.
loads so that the least size of genset can be selected Phase shifting; with the use of special rectifier trans-
to match the load profile. In certain circumstances, it formers which alter the phasing of the secondary wind-
may be more prudent to consider the miss-matching ing or the angle at which the harmonics are produced.
of engine and alternator to find the optimum solution. Reduction of the supply system impedance: by in-
Sizing creasing the frame size of the alternator or using a spe-
It should be noted that the larges motor may not nec- cially designed low reactance machine.
essarily have the largest impact on load, the impact
being determined by the starting method. 13.4.2. Fluorescent Lights
The various normal starting methods, with their gen- At switch on fluorescent lights produce high tran-
eral starting characteristics, are as follows: sient terminal voltages, as a purely capacitive load is
present without any appreciable level of active load.
a) Direct on line 7 x flc, 0.35 pf The power factor correction capacitors of fluorescent
b) Star Delta 2,5 x flc, 0,4 pf lamp installations can have the effect of imposing high
c) Auto transformer 4 x flc (75% tap), 0,4 pf transient stresses on the rotating diodes of the brush-
d) Electronic Soft start 3x flc, 0,35 pf less alternator. A non inductive and matched resistance
e) Inverter Drive 1.25 flc, 0,8 pf in parallel with the main field offers a solution to the
flc = full load current) problem.
39
13.4.3.Lift and Cranes minal to earth. The insulation resistance should be in
Mechanical energy may be fed back to the power excess of 1 M to earth. Should the insulation resist-
source in the form of electrical energy when braking ance be less than 1 M the winding must be dried out.
lifts and cranes. This energy may be absorbed by the
other equipment operating but the surplus power will 14. TOWING (Mobile Generator Sets)
cause the generator to act as a motor tending to drive 14.1. Preparing to Tow
its prime mover. The generator speed will increase and Inspect all components of the coupling equipment on
the governor will reduce its fuel supply. The reverse the towing vehicle and the generator set for defects
power must be totally absorbed by the mechanical such as excessive wear, corrosion, cracks, bent metal,
losses and the generators electrical losses. However or loose bolts.
the generator is capable of absorbing limited regenera- Inspect tyres for condition and proper inflation. Check
tive power so if regenerated load is connected to the that all tail lights, if equipped, are operating properly
generator, the total of the other load elements should and that all reflectors are clean and functional.
be equal to the regenerated power . It may also be
necessary to connect a continuously rated resistive 14.2. Towing
load to absorb the regenerated power, such as load Whenever towing a mobile generator set, remember
banks. that manoeuvrability and stopping distance will be af-
fected by the weight of the trailer.
13.4.4. Capacitive Loads
As the capacitive load increases, there is a tendency WARNING
to over excite the generator unless the main field cur- ! When mobile generator set, observe all Codes,
rent can be reversed by the action of the machines Standards or other regulations and traffic laws. These
excitation control system. This is not possible with an include those regulations specifying required equip-
ordinary brushless alternator. The effect of capacitive ment and maximum and minimum speeds.
loads, produces a high terminal voltage, limited by the ! Do not permit to ride on the mobile generator set.
magnetic saturation of the machine. Do not permit personnel to stand or ride on the draw-
bar or to stand or walk between the generator set and
13.5. Unbalanced Loads towing vehicle.
Unbalanced currents are caused by faults other than ! Avoid gradients and avoid potholes, rocks or other
those involving all three phases. Faults are usually obstructions and soft or unstable terrain.
cleared by circuit protection, any failure of remote pro- ! Ensure the area behind and under the mobile set is
tection to operate or related circuit breakers to trip clear before reversing.
would result in the fault circuit remaining connected to
the generator. Action should be taken to trip the gen- 14.3. Parking
erator breaker if the unbalanced condition persists or Park the set on a dry level area that can support its
if the level of the negative phase sequence current rises weight. If it must be located on a slope, park it across
the grade so that it does not tent to roll downhill. Do
13.6. Alternator Connection not park the set on grades exceeding 15
Different voltages can be acquired only by changing
connections in most alternators. If you changed the al- 14. GENERAL PRECAUTION
ternator voltage , ensure that current transformers ,ca- Dear AKSA generator set operator. Please take care to
bles and measuring devices are suitable for this change. the following order to prevent the generator set war-
ranty to become invalid before the termination of the
13.7. Insulation Test warranty period and to ensure trouble-free operation
Before starting the generator set after installation, test of the generator set with a long life.
the insulation resistance of the windings. The Auto-
matic Voltage Regulator (AVR) should be discon- 1. Maintenance and repair works will not be covered
nected and the rotating diodes either shorted out with by the warranty certificate. If the invoice or delivery
temporary links or disconnected. Any control wiring certificate of the generating set is not submitted.
must also be disconnected.
A 500 V Megger or similar instrument should be used. 2. The warranty of the generator set will become inva-
Disconnect any earthing conductor connected be- lid in case of any intervention of any person other than
tween neutral and earth and megger an output ter- authorized AKSA services or by prior written approval
40
from AKSA power generation on the generator set and contactor failures) are not covered by the war-
for any reason. ranty.
3. Control and maintenance works indicated in the 13. When the manually operated generating set is
periodical maintenance schedule and the operating started up, it should be warmed by operating at idle
manual must be carried out completely and timely the for 5 minutes . When stopping the diesel engine, it
failures due to incomplete or untimely maintenance should be unloaded and then continued to be oper-
are not covered by the warranty. ated for cooling for 5 minutes before stopping. Oth-
erwise problems which are likely to occur will not be
4. Generator set should be installed as indicated in the covered by the warranty
installation manual otherwise, the problems which are
likely to occur will not be covered by the warranty. 14. Never run the Genset for a long time under the
30% of prime power , the problems which are likely to
5. Customer is responsible for the failures which are occur will not be covered by the warranty
likely to occur in case that the diesel oil used contains
dirt or water. 15. Use only original spare parts . The problems which
are likely to occur will not be covered by the warranty
6. The oil type indicated in the maintenance manual
should be used in the engine otherwise, the failures 16. The first starts of the Gen.Sets have to be done
which are likely to occur will not be covered by the by AKSA Authorized Services, otherwise Gen.set war-
warranty. ranty will be invalid.
7. Batteries will not be covered by the warranty if they 17. Any project or additional equipments couldnt be
are subjected to breakage, excessive acid fill or harden- done or installed to the Gen.Set within the warranty
ing by leaving uncharged. period. If those plans (synchronizations , additional
control panel ,panel , transfer panel etc,) are done
8. Dont over crank the generator set , if the generator without notifying the AKSA Authorized services , Gen.
is not started at the first attempt , wait 10 second and Set wont be covered by warranty.
then try to start the engine again , the cranking mustnt
be done more than 3 times ,and cranking time have to 18. Warranty period is 1 year or 1000 hour which ever
be less than 10 seconds ,otherwise starter gear could comes first, beginning from the shipment date.
be broken or starter could be burn up. These condi-
tions are not covered warranty.
15. CUSTOMER RESPONSIBILITY
9. Generator sets, never start or stop the diesel engine 1. The First Start is only valid for the location where
when the generating set is under load. Engine should the Gen.Set is installed ,if the location of the Gen.Set is
be started and stopped after load is disconnected and going to be changed , the Gen.Set has to be controlled
the generating set is at idle condition. Otherwise, the and tested by AKSA Authorized services again. War-
valves can be seized, the voltage regulator, transformer ranty of the generator set will become invalid if the first
and diodes can be broken down. These conditions are start and controls are done by any person other than
not covered warranty. authorized AKSA services .The customer will bear the
10. Our company does not take the responsibility of cost of Second Start.
the damages on the mains supply contactor of the
automatic generator sets due to over current, low or 2. Control and maintenance works indicated in the
high voltage. periodical maintenance schedule and the operating
manual must be carried out completely and timely by
11. Never remove the battery terminals while the gen- AKSA Authorized services for a fee. The maintenance
erating set is in use. Even a moment of disconnection schedule and Manuals are given to the customer with
can cause damage on the electronic closing relay of the the Gen.Set. if these Manual and schedules are lost,
charge alternator and customer has to have a new one.
on the electronic engine speed control circuit these
conditions are not covered by the warranty. 3. Other than manufacturing defect , Customer will
bear the fee of all maintenance, troubleshooting and
12. Failures due to overload and unbalanced load in problems
excess of the generating set power (such as alternator
41
4. If the Gen.Sets wont be started more than 2
Months, These Gen.Sets have to be stored as men-
tioned in the Manuals. The necessary information and
help can be provided from AKSA Authorized services
42
Generating Set, 50 Hz, 400V
Consumption
Oil Capacity
at Full Load
Oil Specifications
Fuel Tank
Capacity
Capacity
Coolant
Fuel
Standby Cummins Not; Lubricating oil viscosity level will be
Power chosen from Figure 7.1 according to the
Model Engine ambient temperature
Model
kVA
L/h Liter Liter Liter
AC 55 55 S3,8-G6 12,8 100 14,5 11
AC 66 66 S3,8-G7 14,7 240 16,5 11
AC 110 110 6BTA 5.9-G5 25 240 19,8 16,4
AC 175 175 6BTAA 5,9-G5 37 380 20,1 16,4
AC 200 200 6CTA 8,3-G2 40 380 27 23,8
AC 250 250 6CTAA 8,3-G2 51,8 470 45 23,8
AC 350 350 QSL9-G5 63 470 28,6 26,5
AC 400 400 NTA 855-G4 76 700 66 38,6 API CH
AC 500 500 QSX 15-G6 95,9 850 66 91 API CI-4
AC 550 550 QSX 15-G8 103 850 66 91 API CF4
AC 703 700 VTA 28-G5 140 1000 170 83
AC 825 825 VTA 28-G6 164 1000 170 83
AC 880 880 QSK 23-G3 161 1500 120 103
AC 1100 1100 QST 30-G4 202 1500 342 154
AC 1100K 1100 KTA38G5 209 1500 350 135
AC 1410 1410 KTA 50-G3 261 2000 415 177
AC 1675 1675 KTA 50-G8 289 2000 420 204
AC 2250 2250 QSK 60-G4 394 2000 500 280
Table 14.1. Fuel consumption and coolant, fuel and lubricating oil capacities and lubricating oil specifications (50 Hz
Cummins Engine Open Gen-sets).
43
Generating Set, 60 Hz, 480V
Consumption
Oil Capacity
at Full Load
Oil Specifications
Fuel Tank
Capacity
Capacity
Coolant
Fuel
Standby Cummins Not; Lubricating oil viscosity level will be
Power chosen from Figure 7.1 according to the
Model Engine ambient temperature
Model
kW
L/h Liter Liter Liter
AC 182-6 182 6CTA 8.3-G2 48 380 27 23,8
AC 290-6 290 NT 855-G6 74 700 66 38,6
AC 315-6 315 QSL9-G5 75 470 28,6 26,5
AC 355-6 355 NTA 855-G3 87 700 66 38,6
AC 400-6 400 QSX15-G6 97,6 850 66 91
AC 496-6 496 KTA19-G4 122 850 120 50
AC 500-6 500 QSX15-G9 117,8 850 66 91
AC 501-6 501 QSX15-G9 117,8 850 66 91
AC 600-6 600 VTA 28-G5 154 1000 170 83 API CH
AC 810-6 810 QSK 23-G3 189 1500 120 103 API CI-4
AC 820-6 820 QSK 23-G3 189 1500 120 103 API CF4
AC 920-6 920 QST 30-G3 207 1500 224 154
AC 921-6 921 QST 30-G3 207 1500 224 154
AC 1015-6 1015 QST 30-G4 240 1500 342 154
AC 1016-6 1016 QST 30-G4 240 1500 342 154
AC 1275-6 1275 KTA 50-G3 291 2000 415 177
AC 1285-6 1285 KTA 50-G3 291 2000 415 177
AC 1530-6 1530 KTA 50-G9 330 2000 643 204
AC 1540-6 1540 KTA 50-G9 330 2000 643 204
AC 2000-6 2000 QSK 60-G7 471 2000 682 280
Table 14.2. Fuel consumption and coolant, fuel and lubricating oil capacities and lubricating oil specifications (60 Hz
Cummins Engine Open Gen-sets).
44
Generating Set, 50 Hz, 400V
Consumption
Oil Capacity
at Full Load
Oil Specifications
Fuel Tank
Capacity
Capacity
Coolant
Fuel
Standby Johndeere Not; Lubricating oil viscosity level will be
Power chosen from Figure 7.1 according to the
Model Engine ambient temperature
Model
kVA
L/h Liter Liter Liter
AJD33 33 3029DF128 6,8 70 15,5 6
John Deere PLUS 50
AJD45 45 3029TF120 9,8 100 23 8,5
John Deere TORQ - GARD SUPREME
AJD75 75 4045TF120 16 240 32 13,2
API CG-4
AJD90 90 4045TF220 23 240 32 13,2 API CF-4
AJD110 110 4045HF120 27,6 240 32 17 ACEA specification E3
AJD 132 132 6068TF220 26,7 380 35 17 ACEA specification E2
AJD 170 170 6068HF120 34 380 36,5 24,6 CCMC specification D5
AJD 200 200 6068HF120 41 380 36,5 32 CCMC specification D4
Table 14.3. Fuel consumption and coolant, fuel and lubricating oil capacities and lubricating oil specifications (50
Hz Johndeere engine Gen-sets).
Oil Capacity
at Full Load
Oil Specifications
Fuel Tank
Capacity
Capacity
Coolant
Fuel
Table 14.4. Fuel consumption and coolant, fuel and lubricating oil capacities and lubricating oil specifications (60
Hz Johndeere Engine Gen-sets).
45
Generating Set, 50 Hz, 400V
Consumption
Oil Capacity
at Full Load
Oil Specifications
Fuel Tank
Capacity
Capacity
Coolant
Fuel
Standby Doosan Not; Lubricating oil viscosity level will be
Power chosen from Figure 7.1 according to the
Model Engine ambient temperature
Model
kVA
L/h Liter Liter Liter
AD 220 220 P086TI 43,1 380 46 15,5
AD 275 275 P126TI 53 470 52 23
AD 330 330 P126TI-II 63,1 470 52 23
AD 410 410 P158LE-1 78,7 700 68,5 21
AD 490 485 P158LE 89,3 700 68,5 21 API CH-4
AD 550 550 P180LE 111,6 850 91 35
AD600 600 P180LE 111,6 850 91 35
AD 660 660 P222LE 134 1000 114,2 40
AD 700 700 P222LE-S 130 1000 114,2 40
AD 770 770 P222LE-II 147 1000 110 40
Table 14.5. Fuel consumption and coolant, fuel and lubricating oil capacities and lubricating oil specifications (50
Hz Doosan engine Gen-sets).
Oil Capacity
at Full Load
Oil Specifications
Fuel Tank
Capacity
Capacity
Coolant
Fuel
Table 14.6. Fuel consumption and coolant, fuel and lubricating oil capacities and lubricating oil specifications (60
Hz Doosan Engine Gen-sets).
46
Generating Set, 50 Hz, 400V
Consumption
Oil Capacity
at Full Load
Oil Specifications
Fuel Tank
Capacity
Capacity
Coolant
Fuel
Standby Mitsubishi Not; Lubricating oil viscosity level will be
Power chosen from Figure 7.1 according to the
Model Engine ambient temperature
Model
kVA
L/h Liter Liter Liter
AMT11 11 S3L2 3,3 50 6,5 4,2
AMT16 16 S4L2 4,9 50 7,5 6
AMT22 22 S4Q2 6,3 50 12 6,5
AMT33 33 S4S 8,8 70 21 10
APD825M 825 S6R2-PTAA 157 1300 132 94
APD1100M 1100 S12H-PTA 216 1000 244 200 API CD
APD1425M 1425 S12R-PTA 261 2000 335 180 API CF-4
APD1650M 1650 S12R-PTAA2 317 2000 TBD 180
APD1915M 1915 S16R-PTA 348 2000 350 230
APD2100M 2100 S16R-PTA2 399 2000 445 230
APD2250M 2250 S16R-PTAA2 404 2000 413 230
APD2500M 2500 S16R2-PTAW 478 2000 TBD 290
Table 14.7. Fuel consumption and coolant, fuel and lubricating oil capacities and lubricating oil specifications (50 Hz
Mitsubishi Engine Open Gen-sets).
47
Generating Sets, 400V, 50 Hz Current capacity Cable Section
of cable at air for (YW) Single
Standby Full load single core cable core for each
current at (40C ambient phase
Model Power temperature)
Cos: 0,8
kVA A A mm2
AC 55 55 79 101 25
AC 66 66 95 123 35
AC 110 110 159 191 70
AC 175 175 252 305 150
AC 200 200 288 382 2 x 70
AC 250 250 360 456 2 x 95
AC 350 350 505 610 2 x 150
AC 400 400 577 684 3 x 95
AC 500 500 721 915 3 x 150
AC 550 550 794 915 3 x 150
AC 700 700 1010 1220 4 x 150
AC 825 825 1190 1335 5 x 120
AC 880 880 1270 1525 5 x 150
AC 1100-1100K 1100 1587 1830 6 x 150
AC 1410 1410 2035 2440 8 x 150
AC 1675 1675 2417 2745 9 x 150
AC 2250 2250 3248 3660 12 x 150
Table 14.8. Recommended cable cross sections (50 Hz, Cummins Engine Gen-set).
Note: PVC isolated cables YVV suitable to 0,6 /1 kV, VDE norms and TSE
48
Generating Sets, 380V, 60 Hz Current capacity Cable Section
of cable at air (NYY) Single
Standby Full load (40C ambient core for each
current at temperature) phase
Model Power
Cos: 0,8
kW A A mm2
Table 14.9. Recommended cable cross sections (60 Hz, Cummins Engine Gen-set).
Note: PVC isolated cables YVV suitable to 0,6 /1 kV, VDE norms and TSE
49
Generating Sets, 400V, 50 Hz Current capacity Cable Section
of cable at air for (YW) Single
Standby Full load single core cable core for each
current at (40C ambient phase
Model Power temperature)
Cos: 0,8
kVA A A mm2
AJD 33 33 47 57 10
AJD 45 45 65 76 16
AJD 75 75 108 123 35
AJD 90 90 130 155 50
AJD 110 110 158 191 70
AJD 132 132 190 228 95
AJD 170 170 245 305 150
AJD 200 200 288 382 2 x 70
AJD 275 275 397 456 2 x 95
Table 14.10. Recommended cable cross sections (50 Hz, Johndeere Engine Gen-set).
Note: PVC isolated cables YVV suitable to 0,6 /1 kV, VDE norms and TSE
AJD 28-6 27 51 76 16
AJD 39-6 35 67 101 25
AJD 68-6 68 129 155 50
AJD 78-6 75 142 191 70
AJD 96-6 90 171 228 95
AJD 97-6 95 180 228 95
AJD 125-6 105 199 267 120
AJD 126-6 123 233 305 150
AJD 148-6 145 275 382 2x70
AJD 177-6 165 313 382 2x70
AJD 182-6 182 346 456 2x95
Table 14.11. Recommended cable cross sections (60 Hz, Johndeere Engine Gen-set).
Note: PVC isolated cables YVV suitable to 0,6 /1 kV, VDE norms and TS
50
Generating Sets, 400V, 50 Hz Current capacity Cable Section
of cable at air for (YW) Single
Standby Full load single core cable core for each
current at (40C ambient phase
Model Power temperature)
Cos: 0,8
kVA A A mm2
Table 14.12. Recommended cable cross sections (50 Hz, Doosan Engine Gen-set).
Note: PVC isolated cables YVV suitable to 0,6 /1 kV, VDE norms and TSE
Table 14.13. Recommended cable cross sections (60 Hz, Doosan Engine Gen-set).
Note: PVC isolated cables YVV suitable to 0,6 /1 kV, VDE norms and TSE
51
Generating Sets, 400V, 50 Hz Current capacity Cable Section
of cable at air for (YW) Single
Standby Full load single core cable core for each
current at (40C ambient phase
Model Power temperature)
Cos: 0,8
kVA A A mm2
Table 14.14. Recommended cable cross sections (50 Hz, Mitsubishi Engine Gen-set).
Note: PVC isolated cables YVV suitable to 0,6 /1 kV, VDE norms and TSE
52
STANBUL AVRUPA YAKASI
AVCILAR
MUSTAFA KEMAL PAA MAH. YILDIRIM BEYAZIT CAD. DEMET SOK. NO:132 AVCILAR/STANBUL
T: 0 212 428 66 66 PBX F: 0 212 423 22 22
BACILAR
MERKEZ MAH. GNEL YOLU CAD. NO:24 YENBOSNA/STANBUL
T: 0212 630 79 80 / 0212 630 79 98
KAITHANE
ALAYAN MAH. KAITHANE CAD. NO:93 KAITHANE
T: 0212 222 13 38 PBX F: 0212 210 08 81
KARAKY
NECATBEY CAD NO.74 KARAKY / STANBUL
T: 0212 251 92 48 / 293 07 32 - 33 F: 0212 251 92 64
DOLAPDERE SAN. ST. 13.ADA NO:9 KTELL
T: 0212 671 35 48 - 49 F: 0212 671 35 41
KADIKY
ESK SKDAR YOLU CAD. MEZARLIK SK. NO:2/1 ERENKY
T: 0216 469 58 58 F: 0216 469 57 56
PENDK
AYDINEVLER IK VEYSEL SOK. AK PLAZA NO:24 KKYALI/MALTEPE
T:0216 489 68 68 PBX F:0216 489 21 60
ANKARA GAZANTEP
VELER 86. SOK. NO.7/A ANKAYA FATH MAH. FEVZ AKMAK BULVARI NO:153 EHTKML
T: 0312 472 71 71 F: 0312 472 76 01 T: 0342 321 39 59 F:0342 321 37 67
ADANA ZMR
TURHAN CEMAL BERKER BUL. ADANA MERKEZ KAZIM DRK MAH. YENYOL ANKARA CAD.
A BLOK NO:24/27 YELOBA SEYHAN NO:75 BORNOVA
T:0322 428 11 61 PBX F: 0322 428 15 40 T: 0232 462 24 62 - 461 82 82
F: 0232 462 24 63 - 462 24 40
ANTALYA
ASPENDOS BULVARI YELOVA MAH. 198/2-3 MURATPAA KAYSER
T: 0242 322 16 88 322 91 88 F: 0242 322 97 55 OSMAN KAVUNCU BULVARI NO:207/H MELKGAZ
T: 0352 331 97 77-78 F: 0352 331 97 71
BODRUM
CUMHURYET CAD. KIVILCIM MERKEZ DYARBAKIR
A-BLOK NO:24 ORTAKENT ERGAN YOLU 1. KM. 1. SAN. ST. CAM KARISI
T: 0252 358 70 30 F: 0252 358 70 25 ASTAY PLAZA YENEHR
T: 0412 255 12 21 - 255 12 22 F: 0412 262 00 92
BURSA
NLFER TC. MRK. ALAADDNBEY MAH. 70 SK. TRABZON
NO:12/B NLFER YAVUZ SELM BULVARI MANOLYA STES NO:281
T: 0224 443 53 15-16-17-18 F: 0224 443 53 19 T:0462 230 10 60-61 F: 0462 230 10 64
DENZL
ZMR ASFALTI NO:56 GMLER
T: 0258 371 71 10 - 372 08 44 F: 0258 372 09 46
ALGERIA CHINA IRAQ
Eurl Aksa Gnrateurs Algrie Aksa Power Generation Co. Ltd. Aksa Power Generation (Iraq)
Cooprative EL-TASSADI Villa No: 42 No.19 Tongjiang North Road, English Village House
Tixerain Bir Khadem Alger / Algerie New District, Changzhou / China No:353 Arbil / Iraq
T : + 213 21 55 00 04 T: + 86 519 856 01 250 T : + 964 771 115 59 17
F : + 213 21 40 27 94 F: + 86 519 851 50 130 F : + 964 771 115 59 17
contact@aksa-dz.com aksa@aksapowergen.com export@aksa.com.tr
+ 971 4 880 91 40
+ 971 4 880 91 41
N / CHINA
No.19 Tongjiang North Road,
New District, Changzhou / China
T : + 86 (0) 519 856 01 250
F : + 86 (0) 519 851 50 132
e-mail: aksa@aksapowergen.com
28.01.14