The document summarizes the sizing of a 15 kVA, 480 V primary to 208 V secondary, 3 phase delta to wye transformer. Key specifications are provided, including impedance of 2.7789%, load demands, bolted fault currents, and utilization percentage of 88.13%. Circuit 4LP1 is identified as using the transformer, rated for 13.22 kVA at 208 VAC, 3 phase.
The document summarizes the sizing of a 15 kVA, 480 V primary to 208 V secondary, 3 phase delta to wye transformer. Key specifications are provided, including impedance of 2.7789%, load demands, bolted fault currents, and utilization percentage of 88.13%. Circuit 4LP1 is identified as using the transformer, rated for 13.22 kVA at 208 VAC, 3 phase.
The document summarizes the sizing of a 15 kVA, 480 V primary to 208 V secondary, 3 phase delta to wye transformer. Key specifications are provided, including impedance of 2.7789%, load demands, bolted fault currents, and utilization percentage of 88.13%. Circuit 4LP1 is identified as using the transformer, rated for 13.22 kVA at 208 VAC, 3 phase.
The document summarizes the sizing of a 15 kVA, 480 V primary to 208 V secondary, 3 phase delta to wye transformer. Key specifications are provided, including impedance of 2.7789%, load demands, bolted fault currents, and utilization percentage of 88.13%. Circuit 4LP1 is identified as using the transformer, rated for 13.22 kVA at 208 VAC, 3 phase.
Hertz 60 Hz Phase 3 Voltage (primary) 480 VAC Voltage (secondary) 208 VAC Percent of Impedance(Z) 2.7789% Configuration Delta to Wye Transformer 15 kVA 480V PRI 208V Y SEC z = 2.7789%
Transformer Sizing Analysis
Load Demand (primary) 15.90 A Load Demand (secondary) 36.70 A Load Rated (primary) 18.04 A Load Rated (secondary) 41.64 A Bolted Fault (primary) 649.26 A Bolted Fault (secondary) 1,498.28 A Load/Size (actual) 13.22 kVA Load (remaining) 1.78 kVA Percent of Utilization 88.13% Increase Factor none Derating Factors Motor Cycling none Ambient Temperature none Altitude none OCPD Input (primary) at 0% 50A per NEC Table 450.3(B) Output (secondary) at 0% 60A per NEC Table 450.3(B)