Professional Documents
Culture Documents
Turbine Application Report E PDF
Turbine Application Report E PDF
Turbine Application Report E PDF
Gateway to
plant management system
Events
Messages
ME-AIS ME-DRP
server ME-AIS server Client 1 Client n
Video printer client 1
Project
Printer server Workstation Workstation Workstation AIS-LAN database
PD-LAN computer computer computer DRP-LAN
Bridge
PD-LAN
Radio
Master computer 1 Master computer 2 clock
P
FD
N
_1
> _1
> _1
>
& & &
- +
f L L
2v3 2s 0 2v3 2s 0 2v3 2s 0
+
+ - + LS 01 LS 01 LS 01
F
DE n
G
K X HP MP LP G SS Turbine SS Turbine SS Turbine
HP MP/
LP ~
S
#
S #
#
~
Turbine-
M F
Hydraulic protection block shaft
2v3
G
M
TR
Steam generator Turbine controllers Turbine auxiliary plants Turbine monitoring Turbine no-load current protection
- Coaling, pulverization - Speed and speed master controller 1v2 Closed-loop control - Shaft oscillation - Overspeed
- Air / flue gas - Power and power master controller - Gland steam pressure control - Bearing housing oscillation - Condenser pressure Sensor and
- Coaling ( fail-safe ) -Live steam prepressure and - Gland steam temperature control - Relative expansion - Bearing oil pressure processing
- Feed -water limit pressure contol - Bearing oil temperature control - Shaft position - Tank protection 2v3,
- Superheater - Hot reheater accumulation control - Condenser level control - Absolute expansion - Generator protection
- Condensed steam - Condenser minimum quantity control - Axial thrust - Tail blade protection trip NC current
- Heat extraction control
- Long-range energy branch - HP / MP coordinator - Generator auxiliary control circuits - Shaft position 1v2
- House service - Valve positioner HP, MP/LP - HP outlet temperature
- MP bypass control with Function groups Turbine load current protection
Auxiliary plants pressure and injection control - Function group Cooling water - Dual-channel
- Flue gas desulfurization - FG Condensed steam transport - Dual-channel processing Protection monitoring No-load current
Turbine temperature and
- DeNOx, NH 3 tankage - FG Bearing oil, actuating fluid and rotary mech. - Trip criterion 1v2 - Electronic protection system
power controller (TLFG)
- Water treatment - TFD ,TZ and turbine power - FG Evacuation - Hydraulic 2v3 protection block
- Condensed steam treatment - Transient limiting - FG Blocking steam - Single test Quick-action stop valve
- Coal, lime supply - Logging and reporting - FG Bleeding Single test Quick-action stop valve - Single test Control valve
- Ashes, gypsum disposal - FG Water extraction
Block power coordinator - FG Turbine control
- Setpoint control Steam generator
- Setpoint control Turbine
Digital Turbine Control Concepts The Temperature and Power Reference Unit comprises:
for Retrofitting or Modernization Projects
Industrial computer
SUB-NET process bus connection through the serial interface to
Conditions Recommendations the turbine controller CPU; this connection handles all process
for future operation for future operation data acquisition and control command output
Hard disk
Life expectancy Monitor and keyboard connection (for system administration and
DVG guide lines for Availability / Reliability
plant safety Extended safety
parameter setting only)
Operation monitoring Turbine Auxiliaries Control
In addition to the automatic control of turbine speed and power, the
Primary control Turbine temperature and turbine auxiliary equipment plays an important role in ensuring
(frequency stability) power reference control unit
Secondary control (TPR unit) efficient and safe turbine operation. These auxiliaries are basically
(system characteristic control) Load limit device in charge of the following tasks:
Unit control reserve HP/IP balancing control
Overspeed protection Protection monitoring Gland steam pressure control
Fundamental protection Turbine operation monitoring
Extended protection Turbine auxiliary plant Gland steam temperature control
Control of high pressure (HP) and intermediate pressure (IP)
bypass stations
Control System Overall Concept These separate control and automation tasks are solved by stan-
dard modules of the ME 4012 process control system. They are
smoothly incorporated into the overall turbine control scheme to
provide a fully integrated control solution.
The Turbine Controller
The auxiliary system comprises the following modules and facilities:
The turbine controller is a task-oriented configuration using standard
Field units for process data acquisition
software function blocks of the ME 4012 process control system. Its
modular design allows single-channel structures for the control of Field installations and cabling
industrial turbines as well as dual-channel structures with bumpless Measured value conditioning
changeover for power station turbines. Binary signal conditioning
Functions of the turbine controller Drive control
Measured data conditioning
Closed-loop control and power actuators
Speed control
Pressure control Failsafe modules with type approval
Power control Message generation and alarm annunciation
Coordination of the HP and IP turbines
Automated function groups
Valve positioning control
Control logics Operator control, logging and reporting facilities
Message generation and alarm annunciation These control components and modules fulfil the following principal
Operator guidance tasks:
Special features of the turbine controller Closed-loop control of the turbine auxiliary servo loops
Controller cycle time 2 ms, typical Control of the auxiliary drives
Controller response time 5 ms, typical
Failsafe protection for the HP and IP bypass system
Speed signal resolution 0.5 mHz
Speed measurement accuracy 2 mHz absolute, at 50 Hz Automatic function groups to ensure controlled operation
Operator guidance
Turbine Temperature and Power Reference Unit (TPR Unit)
Operator control and plant monitoring in a central control station
The Temperature and Power Reference Unit (TPR unit) reads a
number of process quantities, such as steam pressure, steam Turbine Operation Monitoring
temperature, turbine valve positions and turbine speed, and cal- Turbine operation is monitored by the following functions:
culates thermal stress values on the basis of these input quantities. Measured value conditioning
It then compares the results with the admissible stress parameters
defined for the high pressure and temperature components of the Signal evaluation and limit value generation
turbine which are subjected to the highest strain (i.e., the turbine Display of measured values, message generation, alarm
shafts). The TPR unit controls the rate of change of the steam annunciation
temperatures (i.e., of the live steam and intermediate superheater Amongst others, the following process parameters are monitored:
steam) and the rate of change of the turbine power such that the
Shaft vibration (eddy current measurement in x and y directions)
limit strain values are never exceeded. This ensures optimized
turbine operation while at the same time taking into account Bearing vibration (seismic sensors)
thermal stress limitations associated with the turbine with the aim to Relative/absolute expansion (expansion and distance sensors)
avoid thermal stress-related fatigue and achieve the envisaged Shaft position (distance and eddy current sensors)
service life of the turbine.
As the hardware of the TPR unit is installed in the turbine controller Axial thrust (evaluation of strain gauges)
cubicle and directly connected to the process bus, it is optimally
integrated in the overall control strategy of turbine operation.
Overview of the hardware of the ME 4012 control system for steam turbogenerators
The success of digital control of steam turbines in the 9 to 600 MW In our example, the steam generator is controlled by a power
range is based upon standard components of the ME 4012 controller which is capable of providing the required transfer power
process control system. The automatic controller of the ME 4012 of the unit at a sufficient precision. U.S. technical literature refers to
system can be installed in new turbine installations as well as in this type of control for power station units as "turbine follow mode.
retrofit projects. To date, for the control of drum-type boilers, turbine follow mode is
Principally, the turbine is controlled by the quantity of live steam fed applied much more frequently than the better known "boiler follow
to the HP turbine. If the turbine is of the intermediate superheating mode usually applied in the control of forced flow-through boilers
type, then control also considers the quantity of the superheated (also known as Benson boilers).
steam fed to the intermediate and low-pressure parts. Servo- Today, digital process control systems such as ME 4012 allow us
hydraulic actuator drives implement the control action. to implement the simulations of fairly complex controlled systems
The closed-loop control strategy described in this application report and elaborate control algorithms. This method yields the required
has been applied to a condensing turbine with superheating. It maximum dynamic response while at the same time reducing the
runs on the ME 4012 process control system and uses ME 4012 strain on the high-pressure power station components. Such
standard function blocks as well as function blocks specifically implementations could for instance be the import and export
developed for highly dynamic processes. The completed processes that may be caused by fluctuations in the grid frequency,
configuration of the software controller and the turbine controller or that may even be desirable in the event of scheduled load
hardware can be tested on a unit simulation device. The ME 4012 changes. In addition, digital control allows selective intervention
controller also allows automatic control of other turbine types, such and adjustment of turbine valves in the event of fuel problems in
as back-pressure turbines, bleeding turbines, tapped back-pressure order to restore process stability.
turbines, condensing turbines and tapped condensing turbines. During the start-up phase of the steam generator and turbine units
The multi-variable control rule is always designed according to the -which is the initial non-coordinated operating phase- a start-up
German VDI/VDE guidelines,
no. 3521, sheet 3. Power setpoint
DE/Turbine E PTx PTx
+ X
DE -
The Control Strategy TLFG
Load capability
"FFD "
[MW ]
contrary, a turbine set must be E Unit PTx
Frequency stability: model + +
considered as only one Primary control
component of the technological D Condensate build-up + [MWE ]
control + -
process of a power station and + + + -
+
generator is started under load From/to unit control EHU - Electro-hydraulic converter
f - Frequency
N - Correction
pV / p GV - Pre-pressure/pre-pressure limit diff. value
by applying a target power 4 3 1 PG Soll 2 PFD Soll h - Position
n - Speed
PG - Generator active power
PG Soll - Generator setpoint power
n - Overspeed differential value
value to the setpoint transmitter - Control loop/signal generation,
- Transducer - processing
of the unit coordinator. As a PV
+
- Setpoint
+
result, the base power value in f PG
-
-
+
-
the coordinator changes in line PGV
+
+
MAX
with a permissible transient PG2 PG1
reached. -
MAX
n
1 +
W
- -
+
This transient selection restricts Start/
n - -
Stop # dn/dt
the preselected power transient Operation
-
+ +
-
Speed setpoint master The electrohydraulic transducers with integrated jitter voltage
generation ensure highest precision in the control of servo control
Acceleration measurement valves. Their power amplifiers are driven by standard 4 to 20 mA
Feedforwarding of additive and multiplicative correction signals to signals.
the controller output YDR All other functional sections of the turbine controller are in charge of
Acquisition and processing of binary signals which are required as the following tasks:
starting condition for the speed setpoint master controller. Power control, taking into account frequency influences
Manual/automatic sequence control logics Pre-pressure control
Alarm acquisition and signalling Limit pressure control
Limit value processing and event time stamping HP/IP balancing
Setpoint transfer to the integrated HP and IP valve position The turbine controller is available in redundant master/slave
actuators (also referred to as valve positioners) for the following configuration with hot standby for high availability.
tasks:
Reliable I/O signal processing is a particularly important factor for
Actuator control for each servo drive without steady state error the availability of the overall turbine controller system. Special
Position feedback with load independent current and normalization emphasis has therefore been placed on the development of I/O
of rising or falling characteristics modules with robust electronic characteristics that meet the high
requirements in power station operation. For detailed specifications
Selection of setpoint position by means of selectable max/min
of the modules employed in the described turbine control project,
selection
please refer to chapter "System Hardware of the Digital ME 4012
Linearization of the valve characteristics Turbine Control System at the end of this application report.
Bumpless change of the operating mode of several parallel-driven However, the acquisition and processing of speed values will be
servo drives (full-arc/partial-arc admission) explained in more detail on the next pages as speed control in
particular puts a fairly high demand on input signal processing.
Valve check with selectable closing speed
Control of electrohydraulic transducers with load independent Firmware with Function Blocks
current ( 4 to 20 mA)
The configuration that implements the turbine control system was
High-speed closing via cascaded intrinsically controlled cartridge programmed with the aid of function macros offered by the ME
valves 4012 firmware library.
Position measurement monitoring The process control engineer responsible for the turbine control
Alarm signalling and annunciation strategy may decide to divide the controller into a slow and a fast
acting function.
Functional section for time-critical tasks (faster than 5 ms).
This functional section is
Turbine controller (B)
Slave (option)
reserved for the control
Turbine controller (A) algorithms of the turbine speed
Master control and of the individual
Non-time critical valve positioners.
function areas
<20ms Functional section for
Automated function groups Option
Power control
standard tasks.
Power controller This functional section
Frequency influence
Closed-loop control
HP/IP balancing controller contains all the other control
Pressure controller Turbine protection
- Steam generator HP outlet load limit device N/C current
tasks, including the turbine
- Network Turbine protection system (TS) (2 oo 3) protection system.
Operating current 2 oo 3
TS test units
2 oo 3
All configuration work and
parameter setting can be done
Time-critical
function areas during online operation.
< 5 ms Developing and expanding the
Speed control Pulse
Speed controller pre-amplifier configuration has no noticeable
Acceleration measurement and
Valve position controller decoupling
effect upon the cycle time of the
fast-acting controller section.
Voter
Master / Slave The possibility of carrying out all
E / H converter E / H converter G configuration work and
Servomotor Servomotor parameter setting during online
operation is of considerable
importance for the different
Shut-off valve Control valve
phases of commissioning, test
Master/slave turbine speed and power controller with functional sections for time-critical and slow runs and process optimization.
control tasks
2oo3
measurement. The trigger &
Turbine
wheels teeth are scanned by Channel 2
SUB-NET
Signal resolution : 0.5 mHz Speed and
monitoring of the ISV3 power controller
preamplifiers installed in the Signal scan cycle : 5 ms
vicinity of the machine are Measuring range : 3 min-1
provided by the protected power Long-term and temperature stability due to digital acquisition and processing
supply of the turbine controller
cubicle. The three pulse
generator signal trains are Pulse signal acquisition with sensor /pulse pre-amplifier (three-channel, decoupled outputs) and signal
decoupled and sent to the conditioning for the areas turbine protection and turbine speed control
turbine controller, to the turbine
protection facilities and to the independent turbine speed
measurement facility, respectively..
To ensure safe pulse signals, every pulse generator is monitored
for device faults and wire-break in the signal lines. The pulse
The IE2F2 Pulse Input Module inputs are electrically isolated to prevent potential carry-over.
To obtain the turbine speed, the pulse trains produced by the three
The pulse input module is supplied by two separate d.c. voltage
magnetic pulse generators are processed by a module that has
transducers which ensure an electrically isolated power supply for
special redundant pulse input channels. Should one of the speed
the two independent input channels. Due to the high measuring
transmitters fail, a MAX selection logic in the turbine controller
accuracy of the pulse input modules, the turbine speed controller
ensures that the maximum value of each pulse signal train is read
can also be used for frequency stability operation.
and passed on for further processing.
Efficient turbine speed control requires high-precision acquisition of To ensure fast and accurate conversion of the pulse signals into
the turbine RPM value. To ensure that the signals of the pulse speed signals, the pulse input module is connected to the speed
generators reach the IE2F2 input module safely and free of noise, controller module through the I/O bus.
the signals are transmitted by screened cables at a signal level of
The speed controller compares the input signals of the pulse
24V +/- 20%. The input channels of the IE2F2 module are
transmitters with the specified setpoint and calculates the
designed for pulse frequencies in the range from 2 Hz to 500 kHz.
command signal for the actuators of the HP and IP control valves.
At nominal turbine speed the frequency is about 10 kHz. The
The control of the cascaded servo drives is based on the principle
pulses are evaluated by a gating circuit which adjusts to the RPM
that the servo valve modulates the differential pressure at a follow-
value. Thus, if for instance the turbine speed is low, the speed is
up piston unit (which is the main slide valve of the servo drive)
not measured by counting the scanned trigger wheel teeth in a
according to the control error of the actuator. The proportional
specified period, but by letting a quartz-stabilised oscillator obtain
gradient which is typically set to 8% is continuously adjustable in
the time between two leading tooth edges. To compensate for
the wide range from 2% to 11%.
possible mechanical inaccuracies, this procedure is carried out
over several tooth edges depending on the RPM value. For low The start-up unit of the speed controller controls turbine
turbine speeds, but particularly for very high turbine speeds, this acceleration from slewing gear mode to nominal speed. A speed
procedure ensures a digital and very accurate speed measurement master controller modifies the speed setpoint in line with a set fixed
on the basis of the number of teeth of the trigger wheel. transient value until finally the selectable target speed is reached.
The absolute accuracy of this type of speed measurement is +/- The speed controller obtains the difference between the speed
4 which corresponds to 2.0 mHz at 50 Hz nominal frequency. setpoint value and the speed actual value and provides at its output
The accuracy of the quartz-stabilised time base is 15 . The the command signal to the HP and IP control valves.
resolution of the speed measurement is as high as 0.5 mHz.
3300 dn
= 300 U/s =Turbine running time constant
dt
3240
3150
Load connection, Dxd
Target speed load operation on network Max. = 5-7% Dxw
3000
10 rpm 350-500 ms Steady-state deviation
2990 10s dn Synchronization phase w.r.t. depending on load and
dt power frequency proportional band
(Xp = 4-6%, V = 16-25)
Load shedding
600 rpm
dn
1 min dt
Turndrive operation
40
5 min 10s
Turbine controller B
Turbine controller A
Power control
Power controller Pre-pressure controller Limit pressure controller
SUB-NET
(Opening setpoint)
Speed
control
n1 (n2) IS
Acceleration HP/IP HP limiting
Speed limit pressure
n2 (n3) meter balancing controller
controller controller
controller
HP/IP coordinator
HP valve IP valve
position controller position controller
IS
n 1 n 2 n3
HP IP G
IS = Intermediate superheater
16
electric feedback transmitter
Analog 1
mounted to the end of the output ..
16
Turbinen-
welle
Computer-aided test of all modules Speed test Turbine controller Turbine controller
1
Channel A Channel B
Heat endurance and function test of turbine controller (master) (slave)
Step-by-step
Hardware and software test in conjunction with turbine simulator test 2
program Turbine protection Feedback control
Channel 3 HP bypass station
ME 4012 System Cubicle IP bypass station
3 Turbine protection
Typical Layout of Functional Areas test program
A B C D E
Turbine controller (master/slave), Turbine protection with shunt 1
2 4
tripping (2oo3), Turbine protection with failsafe tripping (2oo3), 3
Turbine Temperature and Power Reference unit (TPR unit), A Turbine HP and IP
B temperature and bypass
Control of the HP and IP bypass stations, Failsafe trip protection of 5
power control protection
Controll. presel. Master / Slave reference unit (failsafe)
the bypass stations, Electronic power stages (2oo3) for the control ON (TPR unit)
of the control valve and shut-off protection functions. OFF 6
Overspeed test
Activation of the L L
trip solenoids (shut-off S S Speed
N N
Electrohydraulic Power Actuators (E/H Transducers) 7 and control valve) ANS 1 2
moni-
toring
Todays balanced valves require only low actuating forces which in 2oo3 protection
L
S DW 1-3
Function group panel for cyclic
turn allows the servo drives, too, to operate with low hydraulic fluid 1 speed test (9xDW), EAM module N
3
speed > 100 min -1
or spring forces. In modern turbogenerator installations, every Fuses for
2 Step display for speed test
admission valve has its own hydraulic servo drive whose hydraulic function group
Protection and
power section
pressure opens the valve against the force of the closing springs. 3 Reserved for special functions cubicle monitoring
The electrical actuating signal supplied by the turbine controller is 4 Display of the function groups
unfulfilled criteria
converted to an oil-hydraulic actuating signal by a proportional- 5 Preselection for master / slave Cubicle in-feed
turbine controller (2x +24V DC, 1x -24V DC)
action valve. The valves control piston is located inside a control 6 Key switch for the start of the
overspeed test
cylinder and is driven by a 4 to 20 mA current signal supplied by a
7 Reserved for special functions
linear motor. Due to the setting of a built-in return spring, the motor
drives into a safety position (i.e., A to boiler, P to B) in the event of
signal failure or wire break. The electronic position control loop Cubicle layout for the control of turbo sets (up to 300 MW)
integrated in the proportional valve section amplifies the actuating Step response D634 Frequency response D634
signal and -based on the travel information picked up by the built-
Stroke [%]
the piston until finally setpoint and actual value of the piston
Screw plug
Zero setting
HP-RV 1
Proportional
valve
pi
HP-RV 2 Cartidge
valve
Stop valve
HP-RV 3
HP-RV 4
G
HP servomotor
IP-RV 2
Proportional
valve pi
IP-RV 3 Cartidge
valve
Stop valve
IP-RV 4
IP-RV 5
G
IP servomotor
Power transient
Disc
Shaft
0.5
Wm = 100 C
Wm = 300 C
Wm = 500 C
8
7
6 Another control quantity in the power controller is the power
5
4
transient P which is derived from the safety coefficient S and the
3 mean shaft temperature Wm. The above diagram shows the rate
2
1 of change of P as a function of S and Wm.
Hardware of the TPR Unit
Arithmetic model for the shaft temperature distribution
The industrial-type computer for the TPR unit has been designed
Temperature and Power Transients during On-Load Operation for DIN rail mounting and is installed in the system cubicle of the
turbine controller. It comprises the following components:
The steam turbine transient for temperature changes at the
turbine is determined from the safety coefficient S and the shaft PC of industrial design
surface temperature Wo, as shown in the figure below. Serial connection e with multi-function processor, with SUB-NET
connection to channel 3 of the failsafe protection system
Printer (Centronics)
Keyboard
5 Monitor
Temperature transient K/min
Speed
Absolute expansion
Trigger pulse for shaft
Shaft position
Axial thrust measuring device
M
Turn drive
HP IP LP G
Oil pump
Tasks of the Turbine Protection System classified in four criteria groups. These criteria represent the scope
The turbine protection system detects hazardous operating of protection required for a steam turbine. It is not permissible to
conditions that may injure people or cause damage to equipment run the turbogenerator set without these protection circuits. As
and installations. According to the guidelines issued by the soon as one of the turbine protection criteria exceeds its perm-
German VGB PowerTech Association (Guidelines VGB-R103-M issible value, special protective devices interrupt turbine operation
"Supervision, Limiting and Protection Devices in Steam Turbine by closing all shut-off valves (i.e. emergency stop valves), control
Units, see http://www.vgb.org), turbine protection criteria are and backpressure valves via the turbine emergency trip system.
Types of Turbine Protection The processing and speed monitoring logics on the module are
Turbine Protection Replacing an Existing Hydraulic based on the failsafe principle. To enhance safety and availability
Overspeed Protection (typical for retrofit projects) even further, the DW modules are connected in a 2-out-of-3 failsafe
protection logic. This prevents spurious tripping.
This is a cost-effective method of modernizing an existing
hydraulically operating turbine overspeed protection system. A The tripping signals are pulse-width modulated by the speed
combination of sensors, electronic signal conditioning and monitoring modules and then forwarded to 3x2 solenoid valves
processing modules is installed together with a centralized mounted onto a central hydraulic 2oo3-type protection block.
hydraulic protection block using 2-out-of-3 logic. The new Speed Monitoring Modules (DW Modules)
protection block is incorporated in the existing hydraulic system. DW Modules: Design
In the design of the protection system, care must be taken to meet The speed monitoring module is a highly integrated double-height
the demands on tripping safety and availability which differ in the printed circuit board, also referred to as sandwich-type Eurocard.
individual sections of the overall protective system, as there are: The speed monitoring circuit, the logics and the important functional
units are implemented in 2oo3 logic circuits. The use of SMD
Process value measurement
components made it possible to provide each channel in a dualized
Information processing and autonomous arrangement to ensure redundancy.
Protective tripping All binary inputs are surge proof and electrically isolated by means
of optocouplers. The binary outputs are short-circuit proof and non-
reacting.
Failsafe Protection (FS)
The modules faceplate indicates operating states and faults.
In compliance with the VGB R-103-M guidelines, this group of
Important parameters can be sampled through 2mm multiple-string
protection criteria covers turbine overspeed protection and
wire plugs.
emergency stop switches.
Using a key switch or binary input, the electrical overspeed trip can
Overspeed Protection (2-out-of-3 logic)
be triggered for turbine speeds lower than 3300 min-1.
Decoupled by preamplifiers, the measured signals supplied by
The following trigger values can be selected:
three pulse generators are sent to three independent DW modules
(i.e., speed monitoring modules). Each DW module comprises 750 min-1
three speed monitors which check the three turbine speed values, 1500 min-1
both for underrange and overrange conditions 3000 min-1
(i.e., < 3 min-1, > 3300 min-1). 3300 min-1
Generator
protection Protection criteria and operation monitoring
+L1 +L2
>
=1 2oo3 >1
= 2oo3 >
=1 2oo3
Turbine controller Turbine controller
(master) (slave)
OC >1
OC >1
OC >
= = =1
protect. 1 protect. 2 protect. 3 +L3
SUB-NET
OC protection system
Open-circuit protection
Test program
Overspeed governor
RS
RS
RS
RS
RS
RS
AS
AS
AS
AS
AS
AS
RS
RS
RS
AS
AS
AS
24V +L1
24V +L2
24V +L3 Turbine protection
Manual trip Failsafe Failsafe Failsafe
2oo3 closed-circuit closed-circuit closed-circuit
LSN24 protection protection protection
DW module 1 # DW module 2 # DW module 3 #
Turbine protection system (open-circuit shunt trip) with cascaded failsafe turbine protection
Open-Circuit Protection System (OC Turbine Protection) channel from triggering, the signals received through the SUB-Net
bus are negated a second time before they are finally connected to
Turbine protection criteria of the classes 2 to 4 are monitored by an
the 2oo3 logic. The extremely safe data transmission over the
open-circuit shunt protection system (also known as reverse-acting
SUB-NET process bus ensured by its redundant and distributed
tripping) whose components must energize to trip. In the hierarchy
architecture and the balanced and active network nodes makes the
of turbine protection mechanisms, open-circuit turbine protection is
OC turbine protection system highly immune to spurious tripping.
placed one level above the failsafe protection system. We say it is
A failure of one of the network nodes does not affect the operative
upstream from the failsafe system. The open-circuit protection
direction of the trip system in any way. However, permutation can
sequences comprise two or three channels. The signals coming
no longer take place. Should several network nodes fail, however,
from sensors and transducers placed in or around the turbine are
then the OC protection system triggers immediately. All analog
pre-processed in the control cubicle in which three independent
signals and criteria data are available for further processing: for
CPU modules handle all limit value generation and binary signal
message generation with time stamp, for processing in automatic
processing. The open-circuit part of the turbine protection system
function groups, for archiving and display, for instance.
comprises three functional sections:
Analog signal conditioning Trip Criteria
Binary signal conditioning Apart from the existing hydraulics devices responsible for
Processor groups for logic operations overspeed tripping, modernization of turbine protection systems
All measured analog process values required for turbine protection usually involves the installation of additional hydraulically-operated
are collected in analog signal processing units. Critical values that encoders which will supply measured data on additional protection
are measured twice by two redundant measuring points are criteria, such as:
collected channel by channel and kept and processed by separate Bearing oil pressure
CPUs and signal conditioning modules. To achieve the highest Condenser vacuum
possible degree of availability, the open-circuit protection system is Shaft position in block bearing
powered by a dualized 24V d.c. power supply. Modernizing the turbine protection system and changing to
Monitoring of the OC Protection System electronic methods of measurement usually does not require any
mechanical changes in the turbine equipment. Only the shaft
Static monitoring of the measuring chain:
displacement measurement makes it necessary to do some
The measuring chains that are part of the open-circuit protection
retrofitting as the new measurement system must be fitted inside
system are continuously monitored for the following faults in the
the block bearing. Depending on the conditions of the machines
protection system to prevent unwanted turbine tripping caused by
and the retrofitting plans decided by the power station company,
these types of faults:
the hydraulic transmitters are replaced completely or partially by
Wire break
electronic sensor/transmitter equipment and signal processing in
Short circuit
the OC protection system. The principal protection criteria and their
Earth fault
permissible trip delays:
Voltage failure
Voltage recovery Deenergize-to-trip system (failsafe, 2oo3), non-delayed trip:
Out-of-range signals Speed (channels 1 to 3)
Should a fault of this type occur, the associated limit values are Emergency Stop
actually generated and any tripping initiated by these values is Fundamental protection (2oo3), non-delayed trip
suppressed. Instead, a fault message is produced, displayed and HP outlet temperature (60s delay)
recorded, and the reliability logic is changed from 2oo3 to 1oo2 or Condenser pressure
from 2oo2 to 1oo1. Bearing oil pressure
Shaft position at thrust bearing
Logic and Permutation Operations on the Turbine Trip Criteria
End blade protection
Depending on the weighting of the protection criterion, the
IP outlet pressure (at butterfly valves in overflow passage)
emergency trip signals are processed by a 2oo3 or 2oo2 reliability
logic and forwarded to the DW speed monitoring modules. OC protection system (energize to trip, 1oo2), delayed trip (2s)
Messages are generated with information about the process signal Bearing temperatures
that caused the tripping, as well as about the operational and error Steam and casing temperatures
states prevailing at the instance of tripping. Comprehensive Steam pressure before turbines
monitoring of the signals and the electronic modules ensures that Shaft vibration (vector quantity)
errors are detected and indicated. To avoid unwanted tripping Relative expansion
caused by the open-circuit protection system, the protection criteria External criteria (generator, boiler, fire protection)
of the three protection channels are permutated to form criterion- Test Programs for the Turbine Protection System
specific 2oo3 reliability logic. This arrangement prevents tripping in The test programs of the turbine protection system allow a
situations, such as functional check of the following modules and equipment:
Channel 1 "Condensate pressure > max. DW modules, for overspeed monitoring and sensor failure
Channel 3 "Shaft vibration > max.. Trip solenoid valves (seat and cartridge valves)
The protection system only triggers when 2 out of 3 channels Emergency stop valves and control valves
indicate the same criterion violation. In all other cases, the The test programs can be executed on the plant in service without
detected faults and criterion violations are only indicated. They affecting the protection of the running machine in any way. To test
generally serve for plant monitoring and can mostly be eliminated the DW modules for correct overspeed monitoring and the
on plant in service. The data informing about the status of the hydraulic protection block, a step program is started either
monitored protection criteria is transmitted over the SUB-NET automatically at regular intervals, or manually by a command from
process bus. Prior to transmission, the signals are negated at their the control.
source so that the signals transmitted over the bus can be
considered as failsafe signals. To prevent the neighbouring
Electronic 2oo3 Turbine Protection with Manual Release of the Emergency Stop Function
Distributed Hydraulic 1oo2 Trip When the 3-channel Emergency STOP switches provided locally
In new turbine installations, and in installations that require on site and in the control room are in their normal non-tripped
extensive repair and maintenance work on the hydraulic and the operating mode, the three power contactors LNS 24V can be
servo drive equipment, a turbine protection system with distributed energized. Going through a 2-out-of-3 reliability logic, the contacts
hydraulic trip facilities is often the best and most economic solution. of these power contactors activate the turbine control system,
With this approach, the method of criteria acquisition, conditioning including the turbine shut-off valves for emergency stop and the
and processing is principally the same as described earlier. The control drives. The 2oo3 reliability logic ensures a high degree of
main difference lies in the conversion and implementation of the trip safety and availability. A single-channel error can be corrected on
signal. plant in service. If two of the three channels trigger, the turbine is
safely shut down.
In this distributed arrangement, the DW modules do not drive the
2oo3 hydraulic protection block, but electronically control special
protection modules instead, the EAM 15A modules. These Test Programs
modules are responsible for disconnecting the control voltage of In plants that work without the hydraulic protection block, special
the solenoid valves (always 2 channels at a time) and as a result test programs are put in place in addition to those described earlier
activating the emergency stop valves. on. They ensure that all parts of the turbine protection system that
The 24V power bus bar which supplies the emergency stop have distributed hydraulic trip devices are automatically tested at
solenoid valves and the associated ANS-MV current control regular intervals on plant in service.
modules is disconnected by a 2-out-of-3 failsafe trip circuit obtained
by interconnecting three identical EAM 15A modules. Test Program "Electrical Trip Device
The EAM 15A protection modules are driven by the outputs (NF This test program is started either manually by the operator or
signal) of the DW modules. To ensure a continuous and selective automatically at regular intervals, once a day, for instance.
test of the three protection channels during turbine operation, the Detected errors are indicated in the electronics section of the ME
DW modules have special test inputs that are connected to an 4012 system control cubicles. Again, the errors can be eliminated
"Electrical trip function group. A trigger signal coming from the in situ with the turbine running as the error logic is based on the 3-
"Electrical trip function group activates the protection trip of the channel principle. Electrical protection is provided by the EAM 15A
channel selected. 2oo3 modules which replace the complete functionality of the
The DW modules monitoring channels generate check-back complex hydraulic turbine protection block employed in earlier
messages of the trip circuits. These feedback signals tell the turbogenerator plants.
"Electrical trip function group that it can continue the test program.
In the event of errors, an error message is fed back and the cyclical Test Program "Steam Valves
test program is stopped. This test program checks whether the steam valves are running
smoothly. It can be started manually by the operator or
ANS MV Modules for Solenoid Valve Control automatically and can usually only be run at part-load turbine
The ANS-MV modules are interfaces to the distributed solenoid operation. This again depends on the number of shut-off and
valves. The solenoid valves convert the electrical trip signals to control valves employed and on their layout in the plant.
hydraulic signals that drive the emergency stop and control valves.
To achieve shortest possible valve release times, pulse-width
modulation is applied to the solenoid valves after energizing which
regulates the valve power down to the minimum that is required for
holding in the solenoid.
The ANS-MV modules special test inputs allow in-situ trip testing
while the turbine is running.
+L1 +L2
C # C # C
>1
= >
=1 >1
= Turbine
shaft
OC OC OC
>1
= >1
= >1
=
protect. 1 protect. 2 protect. 3 +L3
SUB-NET
OC protection system
Test program
Overspeed governor
RS
RS
RS
RS
RS
RS
AS
AS
AS
AS
AS
AS
RS
RS
RS
AS
AS
AS
& & & & & & & & &
t 0 2oo3 t 0 2oo3 t 0 2oo3
& & &
Activate turbine
>3 revolutions min -1
from FG Turbine control
Test program
Emergency stop switch Electrical
(turbine trip) tripping devices
Electronic
disconnection # # #
Solenoid valves
Monitoring
Monitoring
Monitoring
# # #
(2oo3)
Test program
Shut-off valves
and control valves Solenoid valve
Electronics
activation Test Test Test Test
(current controller)
MV MV
G SV servomotor G SV servomotor
2oo3-type electronic turbine protection with distributed hydraulic trip devices in 1oo2 logic
p -
Setpoint
to MDU1 control
HPBS P
Auxiliary steam
M M M Bearing oil
DE HP IP/LP G
SSV1 SSV2
pV/G
EHU
MDU1 MDU2
EHU
Control fluid
P
SSV1 SSV2
F
Mako
- Transducer
Injection water
# low overpressure level of about
S
+ 15 mbar (selectable) by
# feeding in seal steam through a
S # S # supercritical gland steam
# # pressure valve. In the event of
excessive steam, a subcritical
butterfly valve
Overflow overflow butterfly control valve
continues to increases the
volume of the discharged steam
until a point is reached where
the gland steam pressure valve
M M
M P T maintains control with a very
low stroke, just sufficient to keep
the seal steam feeder line
Auxil./IP steam
Gland steam warm.
cooler
Gland Steam Temperature
Control
HP IP / LP The steam going to the LP shaft
Short designations:
seals must be kept constant at
EHU - Electro-hydraul. converter
- Transducer - Partial control, subgroup control a sufficiently low temperature of
F - Flow
L - Level about 150 C. However, the
MDU - Interm. pressure bypass station - Control loop/signal gen., # - Logic operations temperature of the steam
P V/G - Pressure ( pre-, back- ) - processing coming from the gland steam
P GG - Back-pressure limit
SSV - Shut-off valve - Setpoint pressure valve or from the shaft
and spindle seals is usually not
constant but varies with the load
Gland steam pressure and temperature control situations of the turbine. To
provide low-temperature steam
of about 150 C at the LP shaft
seals, the temperature controller
feeds the required condensate
volumes to the injection nozzles
of the gland steam cooler.
S # #
#
T T
Control fluid
Heating
from turbine
Short designations:
L
EHU - Electro-hydraul. converter
+ F - Flow
L - L - Level
MDU - Interm. pressure bypass
P V/G - Pressure ( pre-, back- )
P GG - Back-pressure limit
SSV - Shut-off valve
+
+ - + - Transducer
F
- Control loop/signal
processing
K X
S S - Setpoint
# #
M
to inj.water tank
Auto
-pMIN
SW
setpoint.
Hand
SW
X
Max
- -
opening pressure is corrected
according to the boiler load.
Emergency Situation
The three pressure switches of
the steam test unit respond to a Short designations:
tripping pressure of 44 barGP. EHU - Electro-hydraul. converter
- Transducer S - Partial control, subgroup
control
The IP bypass opens as soon F - Flow
as one of the three pressure L - Level - Control loop/signal generation,
processing
# - Logic operations
MDU - Interm. pressure bypass station
switches is activated. At a reset PV/G - Pressure ( pre-, back- ) - Setpoint
pressure of about 42 barrGP. on PGG - Back-pressure limit
SSV - Shut-off valve
all three pressure switches the
units close.
IP bypass station pre-pressure control
Pressure Stability
Maintaining pressure stability is not based on finely tuned pressure The valves close when the pressure drops to a value below the
adjustment processes: As soon as the pressure reaches the control opening characteristics. The closing pressure difference should not
characteristic, the valves open by a minimum. Should the pressure exceed a value of about 2 bar.
continue to rise the valves open a little further, depending on the
pressure increase. Overpressure Conditions
The sliding pressure adjustment
60 is only active at "FIRE ON".
If the sliding pressure
characteristics (see pressure
50 diagram) are exceeded, the
Design pressure 47.5 bar GP
valves open and the pressure is
adjusted.
Safety function 44 barGP
Pressure [bar abs.]
40
Temperature After the IP
Bypass Station (IPBS)
30 Space is a factor when it comes
Regular opening characteristic to the integration of IP bypass
stations in todays turbo
20 generator-set and machine
Preheater outlet condenser systems. This may
Preheater slop valve result in measurement difficulties
10 due to restricted space. The
distance between the pressure
reduction station and the
machine condenser, for
0
20 30 40 50 60 70 80 90 100 110 instance, is too short for the
cooling water to condensate
Boiler load in %
before the temperature is
Pressure characteristics of the IP bypass station with sliding pressure adjustment measured.
Temperature control can
therefore not be based on the
Enthalpy temperature measurement in
Z
Z the heat exchanger. So, if the
P T steam temperature after
Enthalpy
control of the injection cannot be accurately
MDU outlet measured, the cooling water
EHU temperature quantity must be controlled on
MDU the basis of a model.
KB
Proportional valve
KA
Hydraulic
drive HP/U EA EB EC
Hydraulic protection block
MVA MVB MVC
HPBS R R R
HPBS/IPBS Overpressure Protection with Failsafe Control If the pressure in the protected system rises above the operating
Steam overpressure protection for hydraulically operated HP pressure of the pressure switch PS, the electric circuit to the 3/2-
overflow and HP and IS relief valves is implemented with our way seat valve is interrupted via the intermediate relay Z. This
ME 4002S Failsafe System. valve opens the way for the control fluid pressure to the 2/2-way
built-in valve E which is subsequently relieved. The hydraulic
pressure acting on the valve plug of the 2/2-way built-in valve
Principal of Operation
opens the valve against the spring force. Hydraulic fluid fed
The ME 4002S Failsafe System works identically for HP overflow through the hydraulic lines L1 and L4 flows from the lower to the
valves with safety function and for IS relief valves, irrespective of upper piston space of the hydraulic servo drive. The force exerted
the number of parallel relief valves (two, three or four valves) used on the valve plug by the medium opens the relief valve.
in the steam system.
Upon activation of the failsafe functions the normal closed-loop
The reliability logics are based on the "3 out of 3" principle, i.e., the
control function of the HP overflow valves must be interrupted.
relief valves open as soon as one of the three paths A, B, C is
This interruption is monitored by two channels. For this purpose
activated. Closed-circuit protection on the deenergize-to-trip
the failsafe control system offers two relay contacts for every valve.
principle is implemented for all three paths.
If the pressure drops below the operating pressure, normal closed-
Each relief valve has three solenoid valves which are normally loop control takes effect again and the valves are closed.
energized and thus closed under normal conditions. As soon as a Intermediate superheater relief valves do not have a closed-loop
solenoid valve de-energizes, it opens and subsequently the spring- control function. The failsafe control system therefore offers one
powered relief valve is opened. This means, however, that a output for every relief valve for the activation of a solenoid valve
power failure, too, would cause the relief valve to open. Therefore, which keeps the relief valve shut under normal conditions.
the failsafe protection system is supplied by two power supplies.
This redundancy structure ensures continued plant availibility. The relief valves can also be opened by releasing the intermediate
As valve operation is not based on a hydraulic force, overpressure relay Z either manually from the operator console, or by means of
protection is not affected by hydraulic pressure failure an additional signal coming from the boiler control system. These
signals, too, are usually connected in a redundant circuit.
.
In the event of errors, the failsafe protection system generates an Two types of tests are available:
error message signal by means of a relay contact. The following Test of all valves and stroke limiting
situations are indicated: Test of individual valves, full stroke
Contact fault Checkback contact Isolating valves IV The test logic of the higher-level ME 4012 process control system
Isolating valve IV isolated and lockswitch test not "ON" is linked to the three paths of the failsafe protection system via the
High system pressure during test (non-blocked pressure switch crosspoint relays K. An end contact of the shut-off valve IV
activated) establishes the electric connection between the test logic and the
failsafe protection system. This connection is only available during
Pressure switch activated, relief valve has not opened
the test procedure. A mechanical key interlock ensures that only
Supply fault, 24 V DC one shut-off valve IV is closed at the time and thus only one of the
Automatic circuit breaker of power supply tripped three paths is put out of operation. In addition, the test logic must
Oil pressure too low (medium voltage supply only) be enabled by the operator by means of an electric key switch on
the operator console.
Key switch test more than 8 hours "ON"
To start the test procedure, the operator closes the shut-off valve IV
The messages are transmitted to the higher-level ME 4012 process
of the relevant path. Via the shut-off valve VP and using a hand
control system where they are time-stamped at a resolution of
pump, pressure can now be built up in pressure switch PS until the
1 ms.
switch responds. This is the switching point that must be checked.
In addition, a Failsafe protection triggered signal is transmitted via Now, pressing the test button switches over the 3/2-way valve M
relay contact. (of one or all relief valves, depending on the test mode pres-
elected). As a result, the relief valve (or all relief valves) starts to
Test Circuit open. When the required position is reached (indicated by a limit
The failsafe protection system allows regular testing of the relief switch on the relief valve) or when the defined maximum period has
valves, including the pressure switches and all signal paths. The elapsed, the 3/2-way solenoid valve is switched back and the relief
function test is carried out separately for each path, i.e., two of the valve is closed again.
three paths always remain active so that overpressure protection is Generator Auxiliary Servo Loops
ensured at all times during a test procedure. The generator auxiliary servo loops can be integrated in the
general auxiliary servo loop section if turbine and generator are part
of the same station design and installation project.
PE; calc. = f (F1; Pk; Tk; Const. LP turbine; F k; LSPW; PSPW; Load capability)
from IP
PE = k* f
MIN
P+ P' E
Load capability LP
F3 F1
G
F2
E3
E2
E1 F
DVG
P Condensate
to unit k storage tank
load control PSpw
PE LSpw
to turbine L
k
(frequency stability) +
-
L
M
F
m3 m2 m1
Fk Tk
T
Condensate build-up control forms the basis for the efficient stability must be made available by the power unit within a
generation of the active-power seconds reserve in accordance with specified period of time in line with the supply obligations agreed
the requirements laid down in the DVG guidelines. The reserve upon with the power distribution board.
power fed into the grid for the purpose of maintaining frequency
The following plant components are included: Sealing steam controller Pressure 1x
The Oil Circulation and Turn Drive function group controls the turbo Synchronization facilities 1x
sets bearing oil circulation system so that the conditions for the After numerous criteria have been scanned, the hydraulic
slewing gear mode and turbine run-up of are fulfilled. The function emergency protection is activated. This opens all shut-off valves.
activates and deactivates (at turbine shut-down) the oil temperature
control. It is assumed that the cooling water for the oil coolers is Also, all drainage valves of the turbine are opened or closed
provided by means of an auxiliary cooling water circuit. depending on the current process conditions. The shut-off valves
This function group also ensures the circulation of the control fluid and control valves are warmed up by means of the preheating
by activating the control fluid pump. The oil circulating system also valves (the valves open or close according to the permissible
activates the lifting oil pumps. The turn drive motor is started after temperature differences). After the steam has reached the required
a delay period which is necessary for the relief pressure to build up, start-up temperature and various additional criteria have been
and after a number of criteria have been scanned, such as bearing scanned, the speed master controller of the turbine controller
metal temperatures, relative expansions and generator status. The accelerates the turbo set to nominal speed.
lifting oil pumps are switched off as soon as the turn drive speed is When the nominal speed is reached, voltage controller activation,
reached. The turn drive motor is switched off at a rotational speed generation and synchronization are enabled. As soon as the
of n 100 min-1, and switched on at speeds of n 100 min-1. If the generator is connected to the network, the power master controller
rotational speed drops down to or below 40 min-1, the lifting oil takes over the setpoin control in line with the permissible transient
pumps are activated. The turn drive motor and lifting oil pumps are values calculated by the Temperature and Power Reference Unit
switched off in the Off program. (TPR unit), until the set target power is reached or the control
The bearing oil circulating system is deactivated when the turn valves are fully open.
drive is shut down. The oil circulating system has a start and a
stop program.
The processes described next apply to a condensing turbine with Drainage of Casings and Piping
reheat which is equipped with an IP bypass station and started up At a power output of more than 15 % all casing or inlet piping
in the sliding pressure/sliding temperature operating mode. The drainage systems are closed. At a power output of less than 15 %
start-up and load period is determined by the permissible all casing or inlet piping drainage systems are open.
temperature transients of the principal turbine components. The
The drainage systems of the piping towards the non-return valves
influence of the turbine temperature at the beginning of the start-up
are opened when the non-return valves are closed. They are
process and the behaviour of the boiler, particularly in the lower
closed when the non-return valves open.
temperature and load range, must be taken into account.
In order to keep the initial temperature jump at start-up and the All drainage systems are closed when the turbine is at rest.
subsequent temperature transient within permissible limits, it is
necessary to adjust the inlet steam temperatures to the current Sealing Steam Supply
temperatures of the main turbine components. Auxiliary steam with a temperature > 270 C must be provided for
Bypass stations allow non-coordinated operation until the steam the shaft sealing.
temperatures are in line with the temperature values required by
the individual turbine stages and the steam parameters fulfil the Activation Criteria for the Emergency Trip System
connecting criteria. The activation of the emergency trip facilities opens all shut-off
At cold start-up, the steam temperatures cannot always be valves. The steam flowing to the shut-off valves must therefore be
sufficiently reduced. Therefore the component temperatures must within a specified temperature range so that the temperature jump
be adjusted to the lowest stable steam temperature the steam in the valve housings does not exceed the permissible limit.
generator can provide before the turbine is run up to its nominal
Apart from the temperature difference between the steam and
speed. For this reason, the turbine is equipped with a casing
valve housings, and various generator criteria, the following values
heating facility which allows casings and rotors to be warmed up
are taken into account:
with auxiliary steam of 12 bar and 320 C supplied by the auxiliary
steam circuit. Temperature difference
upper/lower housing section < max.
Start-up of the Turbo Generator Set Condenser pressure < max.
Preparations Live steam and IS pressure > min.
To prepare the plant for the heating and bypass operation the Bearing temperatures < min.
function groups and systems are activated in the following sequence: Bearing oil temperature > 30 C
The bearing oil must have a minimum temperature of 30 C to
Cooling water circulating system avoid
Oil circulating system and turn drive (still active at warm start-up)
Inefficient lubrication due to higher oil viscosity
Condensate extraction
Sealing steam supply Reduced clearance due to sudden cooling of the bearing shell
Air exhaustion The maximum bearing oil temperature should always stay below
50 C to prevent the turbine protection facilities from tripping due to
The turbine is now in turn drive mode and under vacuum high bearing metal temperatures during turbine acceleration to
conditions. The condenser is ready for the admission of heating nominal speed.
steam and bypass steam. All drainage systems within the turbine
are open.
Warm-up of Live Steam Piping and HP Valve Housings
Heating of the Turbine Housings To ensure that the steam attains the condition required for the
When the centre line temperatures of the HP inner casings and IP opening (activation) of the shut-off valves, the piping towards the
inner casings are below 220 C of the IP inner casings and 200 C, valves must be warmed up in line with the permissible component
respectively, (e.g., after down times longer than 80 to 90 hours), the transients.
turbines heating valves are opened and the turbine is run up to a The pressure in the live steam pipe is in line with the pressure
heating speed of about 700 min-1. The casing heating remains build-up in the boiler. Taking into account the saturated steams
active until the centre line temperatures of the HP inner casings rate of temperature change, the boilers rate of pressure change
and the IP inner casings are risen above 220 C and 200 C, must be adjusted to the permissible rates of change
respectively. Of the live steam piping and
To keep the LP outlet temperature within permissible limits, the LP Of the fittings of the live steam piping.
casing injection is activated as soon as the condenser pressure
has reached a value of 0.4 bar.
HART
Switchgear
HART
HART
SUB-NET
WW Pumpe 1
Process M P Q M
Distributed I/O station C
G M
MWR
M M
Typical cycle times of the AE 4012 Subprocessors and I/O modules with process bus interface can be
programmable controller: inserted at any position in the subracks. This allows complete inte-
Speed control < 5 ms gration of arithmetic, closed-loop control, alarm and monitoring fun-
ctions required for efficient turbine control.
Function group control circuits 20 ms
The multifunction processor modules are equipped with Pentium
Drive control 20 ms
processors to cater for the high 32-bit computing accuracy required
Multi-loop feedback control for analog value processing. The I/O bus connects the
circuits with complex arithmetic subprocessors with the I/O modules.
functions 20 ms
Visual/acoustic alarm system 20 ms All subprocessors and I/O modules have their own onboard power
supply unit.
With time stamp at the
signal source 1ms
1
1
External MZI A
1
Positioning Power
A
Actuating electronics electronics
External MZI 1 variable
External MZI
Signal processing processor
converter
converter
2
D/A
A/D
2 A
Servo
drive
8 A
BE 1 BA 1
BE 2 BA 2
BE 3 BA 3
BE 4 BA 4 A= Analog value monitoring
BE 5 BA 5
BE 6 BA 6
BE 7 BA 7
BE 8 BA 8
BE 9 BA 9
BE10 Master BA10
P"
M
I/O bus
Redundant CPU
SUB-NET channel 1 CONFIGURATION
SUB-NET channel 2 UMFPR
M
P' P' Contact supply K
+24V
17 18 34 59
P5'
24V P L- L+
SE 80mA
KB 1
& K
220V
AC
--- 1 B+ S
KB ON 1 + 21
K
K1 K1
20
KB B- BE1
P 2 - 19
KB SZ SO
SIM
Res
KB
7 + 15
SA 80mA K2 K2
KB 14
1 BE2
& K 8 - 13
--- 1 B+
KB OFF
KRD 22U
K K3
RE
Diagnosis inputs
KB B- K3
P
RA 10 11 12
SW
KB SZ SO
P'
RAS F6ATR 01AF
KB
RAS
K1
I/O bus
RE
RA
SUBNET channel 1 CONFIGURATION K1
SUBNET channel 2 U1 V1 W1 PE
UMFPR N
M
3PH
xd
I X Y
T W PID
Transducer W
I xd
PI
Heat
exchanger L1 L2 L3
RL LL
SP
Reversing RL Actuator Y
md M LL drive
controller
Control panel
T Bypass
butterfly vallve
I xd
PI
L1 L2 L3
RL LL
SP
Reversing RL Actuator Y
md M LL
controller drive
Controlpanel
T
Heat exchanger
butterfly vallve
Return
Actuator drives Power reversal Multifunction processor UMFPR Control panels and display elements
Transducers controller and switching level modules Operator control and process
monitoring system
Vertical level hiearchy with process, switchgear, process control system and control room
Power Controllers for Step-Action Servo Drives In modern turbines, every inlet valve has its own hydraulic
Actuating times of 30 seconds are often sufficient to achieve the servomotor using oil pressure to overcome the seating thrust.
required control quality and dynamic process behaviour. In these Electric 4-20 mA signals drive the servomotor. The failsafe
cases, servo drives with thyristor-controlled three-phase a.c. motors protection system triggers emergency tripping, i.e. the shut-off
are the first choice. The robust and cost-effective three-phase a.c. valves. The control valve servomotors, however, are additionally
motors produce high actuating torques which allows a simplified driven by the electric positioning control loop implemented in the
valve design without complex pressure relief systems . turbine controller (cycle time 2 ms). As a result, only one
4-20 mA signal is sent to the power amplifier of the E/H converter.
Please note:
When using simple reversing contactor arrangements for the To ensure smooth seating of the valve plugs even at rapid closing
activation of the servo drives, they must be designed for the the servomotor piston enters a damping chamber at the end of the
SA4/S5 -25 % ED operating mode (operations per hour: stroke which delays the last part of the stroke.
1,200 c/h max.). The power contactors must comply with the .
utilization category AC 4 (AC 4 lays down the startup, plug braking,
reversing and inching specifications for squirrel-cage motors). Control Valves and Servo Drives
Under these conditions the power contactors have a lifetime of The control valves are designed according to the valve
about 300,000 operating cycles. However, a number of about specifications supplied by the turbine supplier.
10 million operating cycles per year may be necessary to achieve
the required control quality, depending on the dynamic disturbance
of the control loop and the defined control parameters. Due to the Cabling
high maintenance requirements and the resulting reduced The cable systems of the individual process sections are installed
availability we therefore do not recommend the use of reversing according to the cabling diagram shown below. The cables for the
contactors. power section and the supply of the electronic equipment cubicles
must be supplied, installed and connected by the customer (except
Electro-Hydraulic Power Controller (E/H Converter) the power cables to the servo drives).
Due to the relieved valves only low actuating forces are required.
Therefore servomotors are capable of operating with low fluid and
spring forces.
In-feed
In-feed In-feed
~ ~
Trunk
cable
UV UV UV
Solenoid valve Solenoid valve Actuator or FU
24V/DC 230V/AC servo drive
ZKK ZKK
Radial
cable
M M M M M
SA RA
X11
AE 4012
failsafe power electronics that is
common for new turbine plants. 60/60 X32 X22
.
1 23
X12
The protection and central BT:02
X33
monitoring modules are BT: 02
X23
AE 4012
installed in the X-subrack. .
X13
X34 X24
The cubicle mains infeed is 60/60
BT:04
X35 X14
X25
BT: 04 ME4012 TN:
AE 4012
I/O Connections
X36 X26 X15
External signals are connected 60/60 .
by means of 8 x 25 terminal
1 23
max.). Supply
BT:Z
X18
BT: Z X3A X2A
All distribution wiring is carried MAUELL-BT-DIN-17
40/60
Swivel frame
ME 4012 system cubicle with space for two-source mains infeed, 4 subracks and terminal blocks for
1800 process signals and 1800 distribution wiring connections
L+
LM
L-
Module auxiliary
power
Group fusing of the process interface system
1
Module Subrack
Module
L+
LM
L-
Module auxiliary
Group fusing of the process interface system
power
1
Module Subrack
Module
L+
LM
L-
Module auxiliary
= Short-circuit-proof output stage Overvoltage protection power
L+
LM Supply
L-
Peripheral cable shield earthing
DC
DC
Earth bar
L+ L+
LM LM
= =
E
Battery 1 Battery 1
Voltage supply, internal distribution and protection for an ME 4012 system cubicle (example)
Site-specific
documentation and configuration
Cubicles Cable list Function Autom. Control Flow
plans units diagrams
Commissioning Analog values coming from the I/O equipment or going to the valve
position controllers can be measured on the module frontplate
The plant components delivered by us can be commissioned by
without any disturbance to the other signals. All process states
adequately trained personnel of the turbine supplier. During cold
(binary and analog) can be monitored online with the ME-DRP
commissioning, the individual functions and setting values are
configuration system. It is also possible to simulate signals. If
tested and the results are documented.
required, the system can be equipped with an interface for remote
During warm commissioning, the turbine control system is diagnosis.
optimally adapted to the dynamic and other operating conditions of The ME-DRP configuration sysem also allows the generation of
the overall plant. updated graphical project documentation that integrates all current
The clients operating personnel takes part in the commissioning to parameter settings. This updated description of the user
get acquainted with the system. configuration can be printed out on a laser printer, even in graphical
Mauell engineers can support the commissioning engineers of the form, to ensure that one "as built" documentation is always
turbine supplier upon request. The commissioning of retrofitting available.
and modernization projects is carried out by Mauell. Owing to the larger format (A4 landscape) of the printed
documentation, the IDs, plain text descriptions and hardware
addresses of inputs and outputs can all be displayed on the same
printout. The printout is sorted according to the function areas
which are indicated by the appropriate title block. The printed
document is automatically provided with page numbers and the
date of printing.
Reference example: VEAG Kraftwerk Jnschwalde with 6 turbo sets (500 MW each) and the ME 4012 turbine control system
01.4012.28E03