and Maintenance
VariTrane
Single-Duct and Fan-Powered Units
All VariTrane VAV models with pneumatic, electronic, DDC controls, and diffusers.
VCCF04 - 24
VCEF04 - 24
VCWF04 - 24
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
VAV-SVX08E-EN 3
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warnings, Cautions, and Notices . . . . . . . . 2
Important Environmental Concerns . . . . . 2
Important Responsible Refrigerant
Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Receiving and Handling . . . . . . . . . . . . . . . 3
Model Number Descriptions . . . . . . . . . . . . . . 5
Single-Duct Units . . . . . . . . . . . . . . . . . . . . . . 5
Dual-Duct Units . . . . . . . . . . . . . . . . . . . . . . . 8
Fan-Powered Units . . . . . . . . . . . . . . . . . . . . 9
Unit Information . . . . . . . . . . . . . . . . . . . . . . . . 11
Single-Duct Units . . . . . . . . . . . . . . . . . . . 11
Dual-Duct Units . . . . . . . . . . . . . . . . . . . . 11
Fan-Powered and Fan-Powered
Low-Height Units . . . . . . . . . . . . . . . . . . . 12
Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
(SCR) Motor Speed Control Adjustment
Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . 28
Electrically Commutated Motor (ECM) . . 28
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . 42
Heaters with Contactors . . . . . . . . . . . . . . . 42
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Installation of Diffusers . . . . . . . . . . . . . . . . . . 53
General . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
T-Bar Ceiling . . . . . . . . . . . . . . . . . . . . . . . 53
Concealed Spline Ceiling . . . . . . . . . . . . . 53
Drywall/Plaster Ceiling . . . . . . . . . . . . . . . 54
4 VAV-SVX08E-EN
Model Number Descriptions
Single-Duct Units (Water heat- N.O. 2-position)
Remote (Water- Modulating)
Remote (Water- N.O. 2-position)
DD62= UC400 DDC-Basic plus- Local
DD27= VV550 DDC-Basic plus- Local (Electric heat- Staged) Remote
Digit 1, 2 Unit Type (Water heat- N.C. 2-position) (Staged EH)
VC = VariTrane Single Duct Remote (Water- Modulating) DD63= UC400 DDC-Ventilation Flow
DD28= VV550 DDC-Basic plus- Local (Water heat- N.O. 2-position)
Digit 3Reheat (Water heat- N.O. 2-position) DD65= UC400 Basic
C = Cooling Only Remote (Water- N.O. 2-position) (Electric HeatModulating SCR)
E = Electric Heat DD29= VV550 DDC-Basic plus- Local DD66= UC400 Basic plus-Local
W = Hot Water Heat (Water heat- N.C. 2-position) (Electric heat-Modulating SCR)
Digit 4Development Sequence Remote (Water- NC 2-position) Remote (Staged EH)
DD30= VV550 DDC-Basic plus- Local DD67= UC400 Ventilation Flow
F = Sixth
(Water heat- N.O. 2-position) (Electric heat-Modulating SCR)
Digit 5, 6Primary Air Valve Remote (Water- N.C. 2-position) DD71= UC210 DDC-Basic (No water or
04 = 4" inlet (225 cfm) DD31= VV550 DDC-Basic plus- Local electric heat)
05 = 5" inlet (350 cfm) (Water heat- N.C. 2-position) DD72= UC210 DDC-Basic (Water heat-
06 = 6" inlet (500 cfm) Remote (Water- N.O. 2-position) N.C.- 2 position)
08 = 8" inlet (900 cfm) DD32= VV550 DDC-Basic plus- Local DD73= UC400 DDC-Basic (Water heat-
10 = 10" inlet (1400 cfm) (Electric heat- Staged) Remote Modulating)
12 = 12" inlet (2000 cfm) (Staged EH) DD74= UC210 DDC-Basic (Electric heat-
14 = 14" inlet (3000 cfm) DD33= VV550 DDC Vent Flow cntrl to staged)
16 = 16" inlet (4000 cfm) operate N.O. On/Off water valve DD75= UC210 DDC-Basic (Electric heat-
24 = 24" x 16" inlet (8000 cfm) DD41= UC400 DDC-Basic (No water or PWM)
electric heat) DD76= UC210 DDC Ventilation flow-
Digit 7, 8, 9Not Used DD42= UC400 DDC-Basic (Water heat- cooling only
000 = N/A N.C.- 2 position) DD77= UC210 DDC-Basic (Water heat-
DD43= UC400 DDC-Basic (Water heat- N.O.- 2 position)
Digit 10, 11Design Sequence Modulating) DD79= UC210 DDC-Flow Tracking
** = Factory Assigned DD44= UC400 DDC-Basic (Electric heat- (Cooling only)
Digit 12, 13, 14, 15Controls staged) DD80= UC210 DDC-Ventilation Flow
DD45= UC400 DDC-Basic (Electric heat- (Water heat- N. C.- 2 position)
DD00 Trane Actuator Only and PWM) DD81= UC210 DDC-Ventilation Flow
Enclosure DD46= UC400 DDC Ventilation flow- (Electric heat- staged)
DD01= UCM4 Cooling Only Control cooling only DD82= UC210 DDC-Ventilation Flow
DD02= UCM4 N.C. On/Off Hot Water DD47= UC400 DDC-Basic (Water heat- (Water heat- Modulating)
DD03= UCM4 Prop. Hot Water N.O.- 2 position) DD83= UC210 DDC-Basic plus- Local
DD04= UCM4 Staged On/Off E-Heat DD49= UC400 DDC-Flow Tracking (Electric heat- PWM) Remote
DD05= UCM4 Pulse Width MOD E-Heat (Cooling only) (Staged EH)
DD07= UCM4 N.O. On/Off Hot Water DD50= UC400 DDC-Ventilation Flow DD84= UC210 DDC-Basic plus- Local
DD11= VV550 DDC Controller - Cooling (Water heat- N. C.- 2 position) (Water heat- Modulating)
Only DD51= UC400 DDC-Ventilation Flow Remote (Water- N.C. 2 position)
DD12= VV550 DDC Ctrl to operate N.C. (Electric heat- staged) DD85= UC210 DDC-Basic plus- Local
On/Off water valve DD52= UC400 DDC-Ventilation Flow (Water heat- Modulating)
DD13= VV550 DDC Ctrl to operate Prop (Water heat- Modulating) Remote (Water- N.O. 2 position)
water valve DD53= UC400 DDC-Basic plus- Local DD86= UC210 DDC-Basic plus- Local
DD14= VV550 DDC Ctrl - On/Off Electric (Electric heat- PWM) Remote (Water heat- N.O. 2-position)
Heat (Staged EH) Remote (Water- Modulating)
DD15= VV550 DDC Ctrl w/Pulse Width DD54= UC400 DDC-Basic plus- Local DD87= UC210 DDC-Basic plus- Local
Modulation (Water heat- Modulating) (Water heat- N.C. 2-position)
DD16= VV550 DDC Controller - Remote (Water- N.C. 2 position) Remote (Water- Modulating)
Ventilation Flow DD55= UC400 DDC-Basic plus- Local DD88= UC210 DDC-Basic plus- Local
DD17= VV550 DDC Ctrl to operate N.O. (Water heat- Modulating) (Water heat- N.O. 2-position)
On/Off Water Valve Remote (Water- N.O. 2 position) Remote (Water- N.O. 2-position)
DD19= VV550 DDC Controller with Flow DD56= UC400 DDC-Basic plus- Local DD89= UC210 DDC-Basic plus- Local
Tracking (Water heat- N.O. 2-position) (Water heat- N.C. 2-position)
DD20= VV550 DDC Vent Flow cntrl to Remote (Water- Modulating) Remote (Water- N.C. 2-position)
operate N.C. water valve DD57= UC400 DDC-Basic plus- Local DD90= UC210 DDC-Basic plus- Local
DD21= VV550 DDC - Vent Flow w/ On/Off (Water heat- N.C. 2-position) (Water heat- N.O. 2-position)
Elec Heat Remote (Water- Modulating) Remote (Water- N.C. 2-position)
DD22= VV550 DDC Vent Flow cntrl to DD58= UC400 DDC-Basic plus- Local DD91= UC210 DDC-Basic plus- Local
operate prop water valve (Water heat- N.O. 2-position) (Water heat- N.C. 2-position)
DD23= VV550 DDC- Basic plus- Local Remote (Water- N.O. 2-position) Remote (Water- N.O. 2-position)
(Electric heat- PWM) Remote DD59= UC400 DDC-Basic plus- Local DD92= UC210 DDC-Basic plus- Local
(Staged EH) (Water heat- N.C. 2-position) (Electric heat- Staged) Remote
DD24= VV550 DDC-Basic plus- Local Remote (Water- N.C. 2-position) (Staged EH)
(Water heat- Modulating) DD60= UC400 DDC-Basic plus- Local DD93= UC210 Ventilation Flow
Remote (Water- N.C. 2 position) (Water heat- N.O. 2-position) (Water heat- N.O. 2-position)
DD25= VV550 DDC-Basic plus- Local Remote (Water- N.C. 2-position) DD95= UC210 Basic
(Water heat- Modulating) DD61= UC400 DDC-Basic plus- Local (Electric HeatModulating SCR)
Remote (Water- N.O. 2 position) (Water heat- N.C. 2-position) DD96= UC210 Basic plus-Local
DD26= VV550 DDC-Basic plus- Local
VAV-SVX08E-EN 5
Model Number Descriptions
6 VAV-SVX08E-EN
Model Number Descriptions
VAV-SVX08E-EN 7
Model Number Descriptions
Dual-Duct Units
Digit 1, 2, 3Unit Type supplied controller Digit 31Not Used
VDD= VariTrane dual-duct PVR = Pneumatic Volume Regulator 0 = N/A
Digit 4Development Sequence Digit 16Insulation Digit 32Not Used
F = Sixth A = 1/2" Matte-faced 0 = N/A
B = 1" Matte-faced
Digit 5, 6Primary Air Valve D = 1" Foil-faced Digit 33Special Options
05 = 5" inlet (350 cfm) F = 1" Double-wall 0 = None
06 = 6" inlet (500 cfm) G = 3/8" Closed-cell X = Varies - Factory Assigned
08 = 6" inlet (900 cfm) Digit 17Not Used
10 = 10" inlet (1400 cfm)
Digit 34Actuator
12 = 12" inlet (2000 cfm) 0 = N/A A = Belimo Actuator
14 = 14" inlet (3000 cfm) Digit 18Not Used Digit 35Wireless Sensor
16 = 16" inlet (4000 cfm) 0 = N/A 0 = Sensor/Receiver Standard
Digit 7, 8Secondary Air Valve Digit 19Outlet Plenum 1 = Wireless Sensor/Receiver
05 = 5" inlet (350 cfm) Mounted
(Connection is slip & drive)
06 = 6" inlet (500 cfm) Note: All sensors selected in
08 = 8" inlet (900 cfm) 0 = none
accessories
10 = 10" inlet (1400 cfm) A = 1 outletRH
12 = 12" inlet (2000 cfm) B = 1 outletEND Digit 36Duct Temp Sensor
14 = 14" inlet (3000 cfm) C = 1 outletLH 0 = None
16 = 16" inlet (4000 cfm) D = 2 outlets1 RH, 1 END 1 = With Duct Temp Sensor
E = 2 outlets1 LH, 1 END
Digit 9Not Used F = 2 outlets1 RH, 1 LH
0 = N/A G = 2 outlets - END
H = 3 outlets1 LH, 1 RH, 1 END
Digit 10, 11Design Sequence J = 4 outlets1 LH, 1 RH, 2 END
** = Factory Assigned
Note: See unit drawings for outlet sizes/
Digit 12, 13, 14, 15Controls damper information.
DD00= Trane Actuator Only Digit 20Not Used
DD01= UCM4 Cooling Only Control 0 = N/A
DD08= UCM4 Dual Duct
Constant Volume Digit 21Not Used
DD11= VV550 DDC Controller - 0 = N/A
Cooling Only
DD18= VV550 DDC Controller w Digit 22Not Used
Constant Volume 0 = N/A
DD41= UC400 DDC-Basic (No water or
electric heat)
Digit 23Transformer
DD48= UC400 DDC-Basic (Constant 0 = None
Volume) 1 = 120/24 volt (50 VA)
DDSS= Digital Special 2 = 208/24 volt (50 VA)
ENON= Shaft Out Side for Electric 3 = 240/24 volt (50 VA)
Units 4 = 277/24 volt (50VA)
FM00= Other Actuator and Control 5 = 480/24 volt (50 VA)
FM01= Trane Supplied Actuator, Other 6 = 347/24 volt (50 VA)
Ctrl 7 = 575/24 volt (50 VA)
PC03= NC Heating Valve, N.O. Cooling Digit 24Disconnect Switch
Valve
0 = None
PCSS= Normally Closed Special
W = With Toggle
PN08= N.O. Heat/Cool Actuators &
Linkage Only Digit 25Power Fuse
PN09= N.O. Heating, N.O. Cooling, 0 = None
w/PVRs W = With
PN10= N.O. Heating, N.O. Cooling,
w/PVRs (CV DISCH) Digit 26Not Used
PNON= Shaft Out Side for Pneumatic 0 = N/A
Units
PNSS= Normally Open Special Digit 27Not Used
0 = N/A
Notes:
N.C. = Normally-closed Digit 28Not Used
N.O. = Normally-opened 0 = N/A
DA Stat = Direct-acting pneumatic t-stat
(by others) Digit 29Not Used
RA Stat = Reverse-acting pneumatic t- 0 = N/A
stat (by others)
PN = Pneumatic
Digit 30Not Used
FM = Factory installation of customer- 0 = N/A
8 VAV-SVX08E-EN
Model Number Descriptions
Fan-Powered Units
Digit 1, 2Unit Type DD29= VV550 DDC-Basic plus- Local DD86= UC210 DDC-Basic+ Local
VP = VariTrane Fan-Powered Parallel (Water heat- N.C. 2-position) (Water heat NO 2pos)
VS = VariTrane Fan-Powered Series Remote (Water- N.C. 2-position) Remote (Water-Modulating)
LP = VariTrane Fan-Powered DD30= VV550 DDC-Basic plus- Local DD87= UC210 DDC-Basic+ Local
Low-Height Parallel (Water heat- N.O. 2-position) (Water heat NC 2pos)
LS = VariTrane Fan-Powered Remote (Water- N.C. 2-position) Remote (Water-Modulating)
Low-Height Series DD31= VV550 DDC-Basic plus- Local DD88= UC210 DDC-Basic+ Local
(Water heat- N.C. 2-position) (Water heat NO 2pos)
Digit 3Reheat Remote (Water- N.O. 2-position) Remote (Water-NO 2pos)
C = Cooling Only DD32= VV550 DDC-Basic plus- Local DD89= UC210 DDC-Basic+ Local
E = Electric Heat (Electric heat- Staged) Remote (Water heat NC 2pos)
W = Hot Water Heat (Staged EH) Remote (Water-NC 2pos)
DD41= UC400 DDC-Basic (No water or DD90= UC210 DDC-Basic+ Local
Digit 4Development Sequence electric heat) (Water heat NO 2pos)
F = Sixth DD42= UC400 DDC-Basic (Water heat- Remote (Water-NC 2pos)
Digit 5, 6Primary Air Valve Normally Closed- 2 position) DD91= UC210 DDC-Basic+ Local
DD43= UC400 DDC-Basic (Water heat- (Water heat NC 2pos)
05 = 5" inlet (350 max cfm) Modulating) Remote (Water-NO 2pos)
06 = 6" inlet (500 max cfm) DD44= UC400 DDC-Basic (Electric heat- DD92= UC210 DDC-Basic+ Local
08 = 8" inlet (900 max cfm) staged) (Electric heat-staged)
10 = 10" inlet (1400 max cfm) DD45= UC400 DDC-Basic (Electric heat- Remote (Staged)
12 = 12" inlet (2000 max cfm) PWM) DD95= UC210 DDC-Ctrl w/Modulating
14 = 14" inlet (3000 max cfm) DD47= UC400 DDC-Basic (Water heat- SCR
16 = 16" inlet (4000 max cfm) Normally Opened- 2 position) DD96= UC210 DDC-Space Temp Ctrl w/
RT = 8" x 14" inlet (1800 max CFM) DD53= UC400 DDC-Basic plus- Local Local SCR & Remote Stge Elec
Note: 10, 12, 14, 16 Not Available on (Electric heat- PWM) Remote Heat
Low-Height (Staged EH) DD00= Trane Actuator Only
DD58= UC400 DDC-Basic plus- Local ENCL= Shaft Only in Enclosure
Digit 7, 8Secondary Air Valve (Water heat- N.O. 2-position) ENON= Shaft Out Side for Electric Units
00 = N/A Remote (Water- N.O. 2-position) FM00= Other Actuator and Control
Digit 9Fan DD59= UC400 DDC-Basic plus- Local FM01= Trane supplied actuator,
(Water heat- N.C. 2-position) other control
P = 02SQ fan (500 nominal cfm)
Remote (Water- N.C. 2-position) PN00= N.O. Actuator and Linkage Only
Q = 03SQ fan (1100 nominal cfm)
DD60= UC400 DDC-Basic plus- Local PN05= N.O. 3000 Series, RA Stat
R = 04SQ fan (1350 nominal cfm)
(Water heat- N.O. 2-position) PN51= Pneumatic normally open
S = 05SQ fan (1550 nominal cfm)
Remote (Water- N.C. 2-position) w/3011,DPS fan
T = 06SQ fan (1850 nominal cfm)
DD61= UC400 DDC-Basic plus- Local PN52= Pneumatic normally open
U = 07SQ fan (2000 nominal cfm)
(Water heat- N.C. 2-position) w/3011, DPM fan
V = 08SQ Fan (500 nominal cfm)
Remote (Water- N.O. 2-position) PNON= Shaft Out Side for Pneumatic
W = 09SQ Fan (900 nominal cfm)
DD62= UC400 DDC-Basic plus- Local Units
X = 10SQ Fan (1800 nominal cfm)
(Electric heat- Staged) Remote Notes:
Digit 10, 11Design Sequence (Staged EH) N.C. = Normally-closed
** = Factory assigned DD65= Basic (Electric Heat- Modulating N.O. = Normally-opened
SCR) DA Stat = Direct-acting pneumatic t-stat
Digit 12, 13, 14, 15Controls DD66= Basic plus Local (Electric heat (by others)
DD01= Cooling Only Control Modulating SCR) Remote RA Stat = Reverse-acting pneumatic
DD02= N.C. On/Off Hot Water (Staged EH) t-stat (by others)
DD03= Prop. Hot Water DD71= UC210 DDC-Basic PN = Pneumatic
DD04= Staged On/Off E-Heat (Cooling only) FM = Factory installation of customer-
DD05= Pulse Width Mod of E-Heat DD72= UC210 DDC-Basic supplied controller
DD07= N.O. On/Off Hot Water (Water heat-nc 2pos) PVR = Pneumatic Volume Regulator
DD11= VV550 DDC Controller - Cooling DD73= UC210 DDC-Basic
Only (Water heat-Modulating) Digit 16Insulation
DD12= VV550 DDC Ctrl w/N.C. On/Off DD74= UC210 DDC-Basic A = 1/2 Matte-faced
HW Valve (Electric heat-staged) B = 1" Matte-faced
DD13= VV550 DDC Ctrl w/Prop. HW DD75= UC210 DDC-Basic D = 1" Foil-faced
Valve (Electric heat-pwm) F = 1" Double-wall
DD14= VV550 DDC Ctrl - On/Off DD77= UC210 DDC-Basic G = 3/8 Closed-cell
Electric Heat (Water heat-NO 2pos)
DD15= VV550 DDC Ctrl w/Pulse Width DD83= UC210 DDC-Basic+ Local Digit 17Motor Type
Modulation (Electric heat-pwm) D = PSC Motor
DD17= VV550 DDC Ctrl w/N.O. On/Off Remote (Staged) E = High-efficiency motor (ECM)
HW Valve DD84= UC210 DDC-Basic+ Local
(Water heat Modulating)
Digit 18Motor Voltage
DD23= VV550 DDC- Basic plus- Local
(Electric heat- PWM) Remote Remote (Water-NC 2pos) 1 = 115/60/1
(Staged EH) DD85= UC210 DDC-Basic+ Local 2 = 277/60/1
DD28= VV550 DDC-Basic plus- Local (Water heat Modulating) 3 = 347/60/1
(Water heat- N.O. 2-position) Remote (Water-NO 2pos) 4 = 208/60/1
Remote (Water- N.O. 2-position) 5 = 230/50/1
VAV-SVX08E-EN 9
Model Number Descriptions
Digit 19Outlet Connection Digit 26Electric Heat Voltage Digit 36Pre-Wired Factory
1 = Flanged 0 = None Solutions
2 = Slip & Drive A = 208/60/1 0 = None
B = 208/60/3 1 = Factory Mounted DTS
Digit 20Attenuator C = 240/60/1 2 = HW Valve Harness
0 = No Attenuator D = 277/60/1 3 = Both DTS & HW Valve Harness
W = With Attenuator E = 480/60/1
F = 480/60/3 Digit 37Bottom Access
Digit 21Water Coil
G = 347/60/1 0 = None
0 = None H = 575/60/3 W = Access Left Side of Terminal Unit
1 = 1-RowPlenum inlet installed RH J = 380/50/3
2 = 2-RowPlenum inlet installed RH K = 120/60/1
Digit 38Piping Package
3 = 1-RowDischarge installed, LH 0 = None
4 = 1-RowDischarge installed, RH Note: K not available with Low Height
A = 2-way Automatic Balancing)
5 = 2-RowDischarge installed, LH Digit 27, 28, 29Electric Heat B = 3-way Automatic Balancing
6 = 2-RowDischarge installed, RH1
A = 1-RowPremium water coil inlet
kW Digit 39Water Valve
B = 2-RowPremium water coil inlet 000 = None 0 = None
C = 1-RowPremium hot coil 050 = 0.5 kW 1 = Proportional, HW Valve, 0.7 Cv
on discharge, LH 010 = 1.0 kW 2 = Proportional, HW Valve, 2.7 Cv
D = 1-RowPremium hot coil 015 = 1.5 kW 3 = Proportional, HW Valve, 6.6 Cv
on discharge, RH 260 = 26.0 kW 4 = Proportional, HW Valve, 8.0Cv
E = 2-RowPremium hot coil Note: Electric Heat Voltage -
on discharge, LH
Digit 40Flow Rate
0.5 to 8.0 kW kW increments
F = 2-RowPremium hot coil 0 = None
8.0 to 18.0 kW 1 kW increments
on discharge, RH A = 0.5 gpm (0.03 l/s)
18.0 to 46.0 kW2 kW increments
B = 1.0 gpm (0.06 l/s)
Note: 1- and 2-row not available with Digit 30Electric Heat Stages C = 1.5 gpm (0.09 l/s)
Low-Height D = 2.0 gpm (0.13 l/s)
0 = None
Digit 22Electrical Connections 1 = 1 Stage E = 2.5 gpm (0.16 l/s)
L = Left (Airflow hitting you in the 2 = 2 Stages Equal F = 3.0 gpm (0.19 l/s)
face) 3 = 3 Stages Equal G = 3.5 gpm (0.22 l/s)
R = Right (Airflow hitting you in the H = 4.0 gpm (0.25 l/s)
Note: 3 not available with Low Height
face) J = 4.5 gpm (0.28 l/s)
W = Narrow Corridor LH, Hi-Volt Inlet Digit 31Contactors K = 5.0 gpm (0.31 l/s)
Facing 0 = None L = 5.5 gpm (0.35 l/s)
X = Narrow Corridor RH, Hi-Volt Inlet 1 = 24-volt magnetic M = 6.0 gpm (0.38 l/s)
Facing 2 = 24-volt mercury N = 6.5 gpm (0.41 l/s)
3 = PE with magnetic P = 7.0 gpm (0.44 l/s)
Note: (W & X) Fan Powered Series Only Q = 7.5 gpm (0.47 l/s)
4 = PE with mercury
Digit 23Transformer 5 = SCR heat UC400 R = 8.0 gpm (0.50 l/s)
0 = N/A (provided as standard) 6 = SCR heat FMTD/ENCL/DD00 S = 9.0 gpm (0.57 l/s)
T = 10.0 gpm (0.63 l/s)
Digit 24Disconnect Switch Note: SCR cannot be selected with the U = 11.0 gpm (0.69 l/s)
following configuration: V = 12.0 gpm (0.76 l/s)
0 = None
W = With KW > 10, 208 volt 3 phase, Low W = 13.0 gpm (0.82 l/s)
Electric Reheat w/ door interlocking Height
power disconnect, Cooling Only and KW > 22, 480 volt 3 phase, Low
Water Reheat w/ toggle disconnect
Height
Digit 25Power Fuse Voltage = 575 volt
0 = None
W = With Digit 32Airflow Switch
0 = None
W = With
Digit 33Not Used
0 = N/A
Digit 34Actuator
0 = Standard
A = Belimo actuator
Digit 35Wireless Sensors
0 = None
1 = Factory Mounted Wireless
Receiver (Sensor Assembly)
2 = Wireless Comm Interface
Modular FM
Note: All sensors selected in
accessories
10 VAV-SVX08E-EN
Unit Information
Single-Duct Units Figure 3. Typical single duct unit VCEF
The basic unit consists of a sheet metal casing with an air
valve, which is used to modulate the air being delivered
into the occupied zone. The unit is designed to modulate
either cooling or heating air between the temperatures of
40F and 140F. Air enters the air valve through the round
or rectangular inlet and exits into the sheet metal casing to
be distributed to the zone either through integral round
outlets in the casing or through rectangular duct attached
to the discharge of the unit.
The basic unit can also be ordered with factory-mounted
electric or hot water heating coils attached to the
discharge. See Figure 2, p. 11.
These re-heat units are used primarily to reheat air-to-zone
temperature when the load in the occupied space is low. Dual-Duct Units
Primary air is modulated through the VariTrane air valve by Dual-duct units provide two air valves: one as heating
rotating the damper blade. All air valves have a round/ primary air and the other as cooling primary air. Both
rectangular inlet for easy fit-up with incoming duct work. discharge into the common outlet, which leads to the zone
being controlled. See Figure 4, p. 11.
Typical Single-Duct Units
Units are provided with a slip and drive rectangular duct
connection or can be ordered with integral outlet plenum.
Figure 1. Typical single duct unit VCCF Sequencing of hot and cold air valve is dependent on job
requirements. One typical control is valves working in
conjunction to respond to zone temperature.
When the cooling valve becomes fully closed or reaches a
specified minimum, the heating valve will begin to
modulate or vice versa. The typical result is that air flowing
to the zone varies from maximum down to a minimum and
back up to maximum as load varies and controls would
cause one air valve to close and the other to open.
Another typical application is when the unit provides a
constant volume to the zone. When the zone sensor is tied
directly to the heating valve, it will modulate the heating
valve according to the zone temperature.
Figure 2. Typical single duct unit VCWF
When the heating valve is fully closed or there is a call for
cooling in the zone, the cooling valve will be at constant
supply. As the space becomes too cool, the heating valve
will modulate open, decreasing the cooling valve flow. The
typical result is that the air flowing into the zone stays at a
constant flow whether the unit is heating or cooling.
VAV-SVX08E-EN 11
Unit Information
Fan-Powered and Fan-Powered Low- Figure 8. Low height parallel: LPWF (top) & low height
parallel: LPEF (bottom)
Height Units
VariTrane fan-powered and low-height fan-powered units
can be either parallel or series, with or without re-heat.
(SeeFigure 5, p. 12 thru Figure 8, p. 12.)
12 VAV-SVX08E-EN
Unit Installation
Single-Duct 12" thru 16" 25.154" (639 mm) 37.25" (946 mm) 1.376" (35 mm)
Duct Connections
All VariTrane units should be provided with a minimum of
1.5-duct diameters of straight duct prior to the inlet of the
unit. It is recommended that at least 48 inches of straight
duct be provided from the discharge of the units prior to
any take-offs or transitions.
Depending upon the size and weight of the single-duct
unit, it may be capable of being supported by the ductwork Important: This is a requirement for electric heat fan-
that is connected to it. No hanger brackets are provided on powered units used in applications with
these units since the unit should be supported by means 100% downward discharge.
of a hanger strap. The hanger strap should be secured Note: In order to maintain good air distribution over the
directly to the unit casing as shown in Figure 9, p. 13. elements and not create turbulence which could
For cooling only single-duct units or single-duct units with cause a limit cutout there should be four feet of
hot water coil, the unit may be rotated 180 for opposite ductwork, consistent of the discharge dimensions
side connections. of the heater. downstream of the reheat coil prior to
any diffuser takeoffs for VariTrane electric coils.
For units with electric heat, the unit can be flipped to either
RH or LH connection orientation if model number digit 22 1. After all connections are made, check that the entire
Electrical Connections = F. ductwork system is airtight. In some high-pressure
systems, duct sealer may be necessary.
Dual-Duct Note: All inlet duct on the VAV boxes are sized
Dual-duct units should be supported by either hanger approximately 1/8" smaller in diameter than the
straps or by using a threaded rod in conjunction with the nominal size in order to allow the incoming duct
hanger brackets that are provided on the unit. See to slide over the inlet of the VAV box.
Figure 10, p. 13. 2. Provide insulation around the entire inlet collar (all the
way to the unit casing).
VAV-SVX08E-EN 13
Unit Installation
Note: Use caution not to damage the flow tubes when Clearances
making ductwork connections or insulating.
For proper service, it is recommended that at least 36 of
3. Cut slits in the insulation for the flow tubes and side clearance be provided to service and access single-
secure with duct tape. duct and dual-duct terminals units.
4. If the unit is to be installed in a location with high Fan-powered VAV units have a plenum inlet that must
humidity, external insulation around the heating coil be clear of obstructions. Allow at least 36 of clearance
should be installed as required. in front of the side access and plenum opening.
Water Coil Connections Low-height fan-powered terminals require the same
plenum clearance requirement that applies to the
Note: The following coils have 3/8 OD water coil piping
standard fan-powered units. However the access to the
connections.
internal components is located on the bottom of the
Single Duct 1-row coils (inlet sizes 05, 05, 06, 08 unit.
or 10 only)
It is also recommended that 6 of clearance be provided to
Low Height Parallel Inlet 1-row the top and bottom of all the units.
Low Height Parallel Discharge 1-row Note: The minimum clearance for controls and heater
All others require a 7/8 OD water coil piping connections. controls should be 36 for all models except units
with 575-volt electric heaters, which require 48 of
Note: clearance. NEC and/or local codes override all
1. If necessary, you can change the coil connection from clearance requirements.
left-handed to right-handed (and vice-versa) by
disconnecting the coil from the unit and rotating the Actuator Mounting
coil like a steering wheel 180. Important: When installing or replacing the actuator
Note: Exception - Coil connection cannot be changed tighten the actuator set screw per the
on parallel fan powered unit with hot water coil manufacturers instructions. Failure to
on plenum inlet. follow the manufacturers specifications
may result in unit malfunction.
2. Use port at the bottom for inlet and top for outlet on
single row coils. For multirow coils, always plumb in Trane offers a factory-mounted actuator with a 90-second
counter flow orientation. drive time. The actuator drives 1 degree per second. A
field-installed actuator may be used if desired. The
Water inlet is always on the airflow downstream actuator shaft has a -inch diameter and is designed to
side of the hot water coil. travel clockwise to close the damper and counter-
Water outlet is always on the upstream side of the clockwise to open the damper. There is an indicator on the
hot water coil. end of the actuator shaft that can be used to determine the
3. Care should be taken to properly support the water coil position of the damper.
piping connections while connecting the adjoining Stand Alone UCM 4.2
pipe.
When there is no communication to the UCM control and
4. It is recommended that piping to the water coil should the unit is in the stand alone mode the control action is
be done after field-mounted controls, external determined by the auxiliary temperature sensor located
insulation, and ductwork connections have been on TB3-5 and TB3-6 terminals on the UCM board. In order
completed. for the auxiliary sensor to determine the control action
Important: Do not connect water valve or pipe (heat, cool) it must be located in the supply duct. The
extensions to the water coil connections auxiliary temperature is then compared to the zone
unless supported. temperature. If the supply air temperature is 10 degrees
above the zone temperature, then the control action will be
Unit Accessibility heat. If the supply air temperature is less than or equal to
Single-duct and dual-duct units provided with hot the zone temperature, then the control action will be cool.
water reheat have an access panel located on the side If the supply air temperature is between the zone
of the water coil. All other single-duct and dual-duct temperature and the zone temperature + 10F (5.5C)(zone
units are provided without access, as all functioning temperature < supply air temperature < zone temperature
components are external to the unit. + 10F) (5.5C), the control action remains the same and the
UCM controls to the minimum flow set point. If an
Fan-powered terminals are provided with a sliding side
auxiliary sensor is not installed the UCM will retain the last
access.
control action in effect.
Low-height terminal units have a removable bottom
panel.
14 VAV-SVX08E-EN
Unit Installation
VAV-SVX08E-EN 15
Unit Installation
Water
Coil
Airflow
TOP VIEW Plenum Inlet
Parallel Cooling & Hot Water
B
Primary Optional Attenuator
Flow Ring Airflow Field Installed
Tubing
F E
Air
Valve
Airflow
Discharge Outlet
FAN SIZE A B C D E F
02SQ 26.75" (679 mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm)
03SQ, 04SQ, 05SQ 29.75" (756 mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm)
06SQ, 07SQ 36.75" (933 mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm)
Airflow
Plenum Inlet
Optional Attenuator B
Primary
Flow Ring Field Installed
Airflow
Tubing
F E
Air
TOP VIEW Valve
Parallel Electric Heat
D
A
Terminal Box
Heater
Airflow
Discharge Outlet
43.546
(1106 mm)
16 VAV-SVX08E-EN
Unit Installation
E D
2. 1.
Water
Coil
1.625"
(41 mm)
A B C D E F G J
FAN SIZE (Elec. Heat Only) (Elec. Heat Only) (Elec. Heat Only)
02SQ 18.75" (476 mm) 26.75" (679 mm) 3.25" (83 mm) 41.154" (1041 mm) 35.154 (740 mm) 20.132" (511 mm) 53.750" (1365 mm) 19.00" (483 mm)
03SQ, 04SQ 20.75" (527 mm) 26.75" (679 mm) 3.25" (83 mm) 41.154" (1041 mm) 41.154" (1041 mm) 23.875 (606 mm) 59.750 (1517 mm) 19.00" (483 mm)
05SQ 26.75" (679 mm) 26.75" (679 mm) 3.25" (83 mm) 41.154" (1041 mm) 41.154" (1041 mm) 28.966" (736 mm) 59.750" (1517 mm) 19.00" (483 mm)
06SQ, 07SQ 27.25" (692 mm) 26.75" (679 mm) 3.25" (83 mm) 41.154" (1041 mm) 41.154" (1041 mm) 29.875" (759 mm) 58.250" (1479 mm) 17.50" (445 mm)
Flow Ring A B
Tubing
Air
C
Valve
Optional Attenuator
Field Installed
TOP VIEW
Airflow
Series Electric Heat
Plenum Inlet
Electric
Heater C
J
B
VAV-SVX08E-EN 17
Unit Installation
31.65"
(804 mm)
Airflow
13.00" Plenum Inlet
23.90"
(330 mm) (607 mm)
Primary
Airflow
Optional Attenuator 19.86"
Field Installed (504 mm)
24.30"
(617 mm)
3.35"
Airflow
Discharge Outlet (85 mm) TOP VIEW
31.65"
(804 mm)
Airflow
Plenum Inlet
13.00" 23.90"
(330 mm) (607 mm)
Primary
Airflow
Optional Attenuator 19.86"
Field Installed (504 mm)
24.30"
(617 mm)
Terminal Box
Heater
3.35"
(85 mm) TOP VIEW
Airflow
Discharge Outlet
18 VAV-SVX08E-EN
Unit Installation
1.625" 38.95"
(41 mm) (989 mm)
Primary
Flow Ring Airflow
Tubing
Plenum
Air Inlet
Valve 5.625"
(143 mm)
38.75"
(984 mm)
5.625"
Optional Heater Terminal Box
(143 mm)
Airflow
Discharge Outlet
41.137"
(1045 mm)
TOP VIEW
VAV-SVX08E-EN 19
Unit Installation
3.35"
(85 mm)
34.30"
(871 mm)
31.65"
(804 mm)
3.35"
(85 mm) 10.13" 12.85" Airflow
(257 mm) Plenum Inlet
4.00" (326 mm)
Water (102 mm) Primary
Coil TOP VIEW
Airflow
Optional Attenuator 19.86"
Field Installed (504 mm)
Air
Valve
Airflow 3.35"
(85 mm)
20.00"
(508 mm)
27.00"
(686 mm)
34.30"
(871 mm)
3.35"
(85 mm)
Optional
Electric Heater TOP VIEW
Airflow
20.00"
(508 mm)
27.00"
(686 mm)
20 VAV-SVX08E-EN
Unit Installation
19.45" 19.45"
(494 mm) 10.12" (494 mm)
(257 mm)
31.65" 31.65"
(804 mm) (804 mm)
30.30"
(770 mm)
3.35"
(85 mm)
TOP VIEW
Airflow
Discharge Outlet
19.45" 19.45"
(494 mm) 10.12" (494 mm)
(257 mm) 31.65"
31.65"
(804 mm) (804 mm)
30.30"
(770 mm)
Terminal Box
TOP VIEW
Optional
Heater
1.92"
(49 mm) Airflow
Discharge Outlet
VAV-SVX08E-EN 21
Unit Installation
Mounting Bracket
Optional Attenuator
Field Installed
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
Mounting Bracket
Optional Attenuator
Field Installed
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
22 VAV-SVX08E-EN
Unit Installation
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
Notes: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
MOUNTING BRACKET
MOUNTING BRACKET
OPTIONAL ATTENUATOR
OPTIONAL ATTENUATOR FIELD INSTALLED
FIELD INSTALLED
OPTIONAL ATTENUATOR
FIELD INSTALLED
MOUNTING BRACKET
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
Bottom Access
Figure 21. Bottom access
An optional bottom access can be provided in the casing
of fan powered series or parallel terminal unit. See
Figure 21.
The 22 ga. door is lined with 1 26 ga. dual wall insulation
and thermally lined with 1 1 lb. density fiberglass
insulation with a 3.85 R-value.
Each door includes 4 to 6 cam locs that are used to secure
the door to the casing.
The cam loc engages a metal encapsulated frame on the
unit that encloses the unit insulation to prevent air erosion.
The cam loc engagements are interlocked using a flat head
screwdriver. Once unlocked the entire door assembly can
be removed for access.
VAV-SVX08E-EN 23
Unit Installation
24 VAV-SVX08E-EN
Unit Installation
VSWF VSWF
VSCF w/ VSEF w/ VSWF VSWF 1-Row 2-Row VSxF
VSCF Dual Wall VSEF Dual Wall 1-Row 2-Row w/Dual Wall w/Dual Wall Attenuator
Unit Size (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg)
0402SQ 78/35 93/42 104/47 119/54 85/39 87/39 100/45 102/46 46/21
0502SQ 78/35 93/42 104/47 119/54 85/39 87/39 100/45 102/46 46/21
0602SQ 77/35 92/42 103/47 118/54 84/38 86/39 99/45 101/46 46/21
0603SQ 76/34 100/45 105/48 129/59 88/40 92/42 112/51 116/53 48/22
0604SQ 87/39 111/50 116/53 140/64 99/45 103/47 123/56 127/58 48/22
0802SQ 79/36 94/43 105/48 120/54 86/39 88/40 101/46 103/47 46/21
0803SQ 77/35 101/46 106/48 130/59 89/40 93/42 113/51 117/53 48/22
0804SQ 88/40 112/51 117/53 141/64 100/45 104/47 124/56 128/58 48/22
1002SQ 81/37 96/44 107/49 122/55 88/40 90/41 103/47 105/48 46/21
1003SQ 80/36 104/47 109/49 133/60 92/42 96/44 116/53 120/54 48/22
1004SQ 91/41 115/52 120/54 144/65 103/47 107/49 127/58 131/59 48/22
1005SQ 92/42 116/53 121/55 145/66 104/47 108/49 128/58 132/60 48/22
1006SQ 104/47 133/60 135/61 164/74 119/54 124/56 148/67 153/69 54/24
1007SQ 117/53 146/66 148/67 177/80 132/60 137/62 161/73 166/75 54/24
1203SQ 82/37 106/48 111/50 135/61 94/43 98/44 118/54 122/55 48/22
1204SQ 92/42 116/53 121/55 145/66 104/47 108/49 128/58 132/60 48/22
1205SQ 94/43 118/54 123/56 147/67 106/48 110/50 130/59 134/61 48/22
1206SQ 105/48 134/61 136/62 165/75 120/54 125/57 149/68 154/70 54/24
1207SQ 118/54 147/67 149/68 178/81 133/60 138/63 162/73 167/76 54/24
1404SQ 93/42 117/53 122/55 146/66 105/48 109/49 129/59 133/60 48/22
1405SQ 96/44 120/54 125/57 149/68 108/49 112/51 132/60 136/62 48/22
1406SQ 106/48 135/61 137/62 166/75 121/55 126/57 150/68 155/70 54/24
1407SQ 119/54 148/67 150/68 179/81 134/61 139/63 163/74 168/76 54/24
1606SQ 107/49 136/62 138/63 167/76 122/55 127/58 151/68 156/71 54/24
1607SQ 120/54 149/68 151/68 180/82 135/61 140/64 164/74 169/77 54/24
VAV-SVX08E-EN 25
Unit Installation
26 VAV-SVX08E-EN
Unit Setup
Figure 22. Flow sensor P vs. airflow delivery
10
8" x 12"
6
Flow Sensor Differential Pressure (inches water)
0.1
0.01
10 100 1,000 10,000
Airflow (CFM)
VAV-SVX08E-EN 27
Unit Setup
Max
120 v
208 v
277 v
347 v
28 VAV-SVX08E-EN
Unit Setup
VAV-SVX08E-EN 29
Unit Setup
30 VAV-SVX08E-EN
Unit Setup
VAV-SVX08E-EN 31
Unit Setup
32 VAV-SVX08E-EN
Unit Setup
VAV-SVX08E-EN 33
Unit Setup
34 VAV-SVX08E-EN
Unit Setup
VAV-SVX08E-EN 35
Unit Setup
36 VAV-SVX08E-EN
Unit Setup
VAV-SVX08E-EN 37
Unit Setup
38 VAV-SVX08E-EN
Unit Setup
VAV-SVX08E-EN 39
Unit Setup
40 VAV-SVX08E-EN
Unit Setup
VAV-SVX08E-EN 41
Wiring Diagrams
Note: See programming guides listed below for detailed wiring information on the following:
UCM 4.2: VAV-SVX01*-EN UC400: VAV-SVX07*-EN VV550: VAV-SVP01*-EN
42 VAV-SVX08E-EN
Wiring Diagrams
VAV-SVX08E-EN 43
Wiring Diagrams
44 VAV-SVX08E-EN
Wiring Diagrams
VAV-SVX08E-EN 45
Wiring Diagrams
46 VAV-SVX08E-EN
Wiring Diagrams
}
GREEN GREEN
GROUND L1 N GROUND L1 N 5.
5.
SCREW SCREW
TRANSFORMER TRANSFORMER
6.
} Y DISCONNECT BK W DISCONNECT BK W
24V
24V
TO VAV BL BK SWITCH NO BK SWITCH
C
CONTROLLER BR
2. 2.
R
NC
BK W BK W
BK DUCT PRESSURE BK
BK BK
MOTOR 2 4 SWITCH MOTOR 2 4
BK BK
RELAY RELAY
BR FUSE BR FUSE
1 4. 1
4.
3 3
24V 24V
R R
W W
W W
MOTOR MOTOR
TERMINAL TERMINAL
SPEED SPEED
BLOCK BLOCK
CONTROL CONTROL
W-COM
W-COM
BK
BK
FAN CONTROL BOX FAN CONTROL BOX
W BK W BK
BR BR BR BR
CAPACITOR MOTOR CAPACITOR MOTOR
FAN FAN
3. 3.
}
DISCONNECT, LOCK OUT AND TAG GREEN
ALL ELECTRIC POWER INCLUDING N
DUCT PRESSURE MAIN CONTROL GROUND L1 5.
REMOTE DISCONNECTS BEFORE
SERVICING. SCREW
6.
DISCHARGE MOTOR START/RUN
CAPACITORS BEFORE SERVICING.
FAILURE TO DISCONNECT POWER DISCONNECT BK W
SWITCH
BEFORE SERVICING CAN CAUSE BK NO NO
SEVERE PERSONAL INJURY OR DEATH.
C C 2.
BK
CAUTION NC NC
BK W
USE COPPER CONDUCTORS ONLY!
P.E. SWITCH-1 P.E. SWITCH-2
UNIT TERMINALS ARE NOT DESIGNED BK BK
TO ACCEPT OTHER TYPES OF
BK
CONDUCTORS. NO
FAILURE TO DO SO MAY CAUSE 6. BK FUSE
DAMAGE TO THE EQUIPMENT.
C 4.
NC
P.E. SWITCH
NOTES: W
1. FACTORY INSTALLED
BY OTHERS MOTOR
OPTIONAL OR ALTERNATE CIRCUITRY TERMINAL
SPEED
BLOCK
CONTROL
2. DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
W-COM
VAV-SVX08E-EN 47
Wiring Diagrams
}
MOTOR
4. L1 N 4.
BK
GR
Y GR
GREEN
GREEN
BK
GROUND
BK
W
BK
W
SCREW
W
SCREW
TERMINAL
RED RED BLOCK
TERMINAL
BLOCK
DISCONNECT 2 4 2.
SWITCH 3. DISCONNECT
SWITCH W
2. FUSE BL
BK
W
G
R
BK
3. W
ECM
FUSE 1
24V 3 BOARD Y
MOTOR 5.
BK
RELAY
3. NO BL POWER
NEUT. 24V
FACTOR
BL CORRECTION
}
RED RED
CHOKE
C
Y TO VAV NC
CONTROLLER
24V
BL DUCT
PRESSURE Y
BK
W
G
R
SWITCH ECM
24V
BK BL
TRANSFORMER BOARD
TRANSFORMER
POWER FACTOR
CORRECTION CHOKE FAN CONTROL BOX
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
CAUTION
USE COPPER CONDUCTORS ONLY!
GR
GREEN
BK
POWER FACTOR
BK NO NO CORRECTION CHOKE
C BK C NEUT. 24V
Y
24V
NC NC BL RED RED
BK
NOTES: NO
BK
W
G
R
ECM
1. FACTORY INSTALLED C
BOARD
BY OTHERS NC
OPTIONAL OR ALTERNATE CIRCUITRY
P.E. SWITCH
2. DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
EXTERNAL TO CONTROL BOX. FAN CONTROL BOX
3. FUSE IS OPTIONAL.
48 VAV-SVX08E-EN
Wiring Diagrams
W
BK
4. BK
}
W or BR Y
FUSE BK BK
24V
BK TO VAV
BK BL
2 4 MOTOR CONTROLLER 6. BK 2 4
BR
RELAY
R
TRANSFORMER NO 24V
BR BL
BL Y
BL C
1 24V 3
NC
TRANSFORMER 1 24V 3
R
DUCT
MOTOR
PRESSURE
RELAY
SWITCH
FAN CONTROL BOX
FAN CONTROL BOX
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
CAUTION
USE COPPER CONDUCTORS ONLY!
LINE VOLTAGE 5. BR
3.
BR
OR FROM HEATER TERMINAL
}
BK
UNIT TERMINALS ARE NOT DESIGNED CAPACITOR W
TO ACCEPT OTHER TYPES OF L1
BR
N BK
CONDUCTORS. W
CAPACITOR
FAILURE TO DO SO MAY CAUSE
DAMAGE TO THE EQUIPMENT. GREEN
GROUND MOTOR
SCREW SPEED
CONTROL
6. W W
BK W
TERMINAL
BLOCK
BK NO NO 2.
DISCONNECT W
C BK C BK W
SWITCH BR
W
NC NC 4.
BK
BK
NOTES:
NO
1. FACTORY INSTALLED
BK
BY OTHERS
C
OPTIONAL OR ALTERNATE CIRCUITRY NC
4. FUSE IS OPTIONAL.
VAV-SVX08E-EN 49
Wiring Diagrams
Fan-Powered Low-Height Control Box w/ ECM with Electronic or DDC Controls Fan-Powered Low-Height Control Box w/ ECM with Pneumatic Controls
(Depending on the size of the unit, the ECM board may or may not be located
in the fan control box.) Duct Pressure Switch Option
4.
LINE VOLTAGE
LINE VOLTAGE 4. OR FROM HEATER TERMINAL
}
OR FROM HEATER TERMINAL FAN FAN
MOTOR MOTOR 2 FAN FAN
}
BK
GR GR
GREEN W GREEN
Y W
BK
W
GROUND BK GROUND
BK
BK
W
SCREW
BK
SCREW
W
BK
W
NEUT. 24V
TERMINAL TERMINAL
BLOCK RED RED BLOCK
DISCONNECT 2.
SWITCH 3. DISCONNECT
SWITCH W
2. 2 4 FUSE BL
3. BK
W Y
FUSE
BK
W
G
R
ECM
5.
1
24V 3 BOARD
NO BL
MOTOR BL
NEUT. 24V
} TO VAV
DUCT
PRESSURE Y
BK
W
G
R
Y SWITCH ECM
24V
CONTROLLER
BK BL
24V
BK BL
BOARD
TRANSFORMER
TRANSFORMER
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
CAUTION
USE COPPER CONDUCTORS ONLY! Fan-Powered Low-Height Control Box w/ ECM with Pneumatic Controls
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT OTHER TYPES OF
CONDUCTORS.
LINE VOLTAGE 4.
FAILURE TO DO SO MAY CAUSE FAN FAN
DAMAGE TO THE EQUIPMENT. OR FROM HEATER TERMINAL MOTOR MOTOR 2
(SIZE 10 ONLY)
}
GR
GREEN W
GROUND BK
BK
W
BK
SCREW
W
NC NC
NEUT. 24V
P.E. SWITCH-1 P.E. SWITCH-2 Y
BK RED RED
24V
BK BL
NOTES: TRANSFORMER
1. FACTORY INSTALLED
BK
W
G
R
BY OTHERS ECM
NO
OPTIONAL OR ALTERNATE CIRCUITRY BOARD
C
2. DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED NC
EXTERNAL TO CONTROL BOX.
P.E. SWITCH
3. FUSE IS OPTIONAL.
FAN CONTROL BOX
4. DETERMINED BY MOTOR VOLTAGE ON ORDER.
VOLTAGE FOUND ON UNIT NAMEPLATE.
50 VAV-SVX08E-EN
Maintenance
Periodic maintenance of the VariTrane product is minimal,
but necessary for efficient operation. Routine Figure 34. Standard motor removal
maintenance consists of inspecting/replacing the air filters
of the fan-powered terminals.
Motors
Both the PSC (permanent split capacitor) and the ECM
(Electrically Commutated Motor) require no lubrication
during its normal life of operation.
Fan Wheel
Periodically, the fan wheel should be inspected for dirt or
debris and cleaned as necessary.
Filter
The filter on fan-powered terminals will need to be
inspected/replaced routinely depending on the
environmental conditions of the plenum.
Standard height fan-powered series and parallel fan
Filter Change Out motors are replaceable through the filter opening and the
To remove the filter, turn each of the filter retaining standard sliding side access panel. To access the fan
clips 90 (CW or CCW) motor, the fan housing must be detached by removing the
mounting bolts that hold the housing to the fan board.
Remove the filter and replace with new filter of the Removing the entire housing allows the fan motor, fan
same frame size. housing, and fan wheel to be re-aligned on a workbench or
Return the filter clips to their retainng position by floor and prevent any possible fan wheel rubbing that may
turning them 90 (CW or CCW) back to their original occur. Removing the housing will provide access to the
position. motor shaft set screw that holds the fan wheel to the motor
shaft.
Water Coil
Water coils should be inspected and the fins should be
cleaned periodically.
Water coils have been provided with an access panel as
standard to assist with inspection and cleaning.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturers
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. Failure to disconnect power
and discharge capacitors before servicing could result
in death or serious injury.
VAV-SVX08E-EN 51
Maintenance
The low-height fan assembly was designed with an inlet Figure 36. Typical heat sink fin orientation
ring that assists with removal of the fan motor. To access
the fan motor assembly, the bottom panel must be
removed. The inlet ring is held in place by six bolts and
three motor mount bolts. Remove these bolts and the
motor and fan wheel will come out of the fan housing.
Bottom View
52 VAV-SVX08E-EN
Installation of Diffusers
General Concealed Spline Ceiling
All units must be installed upright and level as indicated by Follow these procedures to finish installation of control
the arrow on the side of the units. Return air slots should and satellite diffusers and concealed spline for suspension
be placed perpendicular and offset to the slot diffusers to ceilings before completing the ceiling construction
avoid short-circuiting of air distribution patterns. (Figure 38, p. 53).
Place the unit in its approximate final position and check Place the units in their approximate final positions. If using
that it is upright and level. For single-slot units, engage the trim angle diffuser, its slots must be even with the
the back of the diffuser over the t-bar with an edge and spline level. If applying the trim accessory, the bottom of
both ends resting on the t-bar. For double-slot units, the diffuser must be level with the finished ceiling.
slide the unit over the t-bar. For center-notch units, place If installing the trim accessory, insert the trim into the
diffuser over the t-bar, straddling it across a t-bar and ceiling opening from below and engage the diffuser slot to
resting on the units ends. the trim t-bar structure. With bottom flange of trim
If the unit has a fire damper, make sure that the damper is accessory against the ceiling, and using the pre-drilled
still fully open. Diffuser discharge must always be flush holes in the flange as a guide, drill holes in the flange of the
with the ceiling tiles to assure the proper airflow (Coanda diffuser. Join the diffuser and trim accessory with self-
effect). taping sheet metal.
Diffusers require specific installation information when
mounting to a desired ceiling type. Select the ceiling type Figure 38. Diffuser with trim accessory installation in
that closely matches the job site application and use the concealed spline ceiling
following procedures.
T-Bar Ceiling
Finish installation of the diffuser in t-bar ceiling. (See
Figure 37, p. 53.) Follow these procedures before the
ceiling construction is completed.
1. Position the diffuser at each end resting directly on the
structural t-bar for support and the t-bar fitting into the
channel provided at the unit discharge air throw.
2. A ceiling tile support flange is provided on each side of
the discharge slot of the unit.Trim ceiling tile
approximately 1 inches each to allow for width of
discharge slot. For revealed edge ceilings, tile must be
cut in a Z pattern.
3. Install ceiling tiles in usual manner with cut edges
resting on the flanges of the air slot.
VAV-SVX08E-EN 53
Installation of Diffusers
Drywall/Plaster Ceiling
Finish installation of diffusers in plaster ceiling. Follow
these procedures before completing the ceiling
construction (Figure 39, p. 54).
NOTICE:
Equipment Damage!
Do not install trim frame into ceiling using screws.
When diffuser is placed on the trim frames, it will pull
out.
Diffuser Flange
Trim Accessory
54 VAV-SVX08E-EN
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.