Professional Documents
Culture Documents
04 Setting of REL 511
04 Setting of REL 511
OF
REL 511
The distance protection function blocks are independent of each other for each
zone. Each function block comprises a number of different functional inputs and
outputs, which are freely configurable to different external functions, logic gates,
timers and binary inputs and outputs.
This makes it possible to influence the operation of the complete measuring zone or
only its tripping function by the operation of fuse-failure function, power swing
detection function, etc.
Independent settings
Reactive reach
Resistive reach
Earth return compensation
Vsec
Z sec =
I sec
Through the CT and VT transformation ratios, the secondary quantities
can be expressed in terms of the primary quantities:
I prim I prim
= CTr I sec =
I sec CTr
Vprim Vprim
= VTr Vsec =
Vsec VTr
BOOSTING YOUR ENERGY
REL 511 - ZM function: Secondary values
By substituting Isec and Vsec in the expression of the secondary
impedance Zsec:
Vprim
Z sec =
Vsec
= VTr CTr Vprim
=
I sec I prim VTr I prim
CTr
Vprim/Iprim is the expression for the primary impedance Zprim and
the ratio CTr/VTr is the Impedance Transformation Ratio Kimp:
CTr Vprim
Z sec = = K imp Z prim
VTr I prim
BOOSTING YOUR ENERGY
REL 511 - ZM function: Primary Line Data
CT ratio: CTr
VT ratio: VTr
Phase-to-Phase Loops
E ph1 E ph 2
Zm =
I ph1 I ph 2
Z1 + R f + Z1
II1
Z1 Iph1 I ph 2 = I ph1
1
Eph1
Eph1-Eph2 Rf
Eph2 Z1
E ph1 E ph 2 E ph1 Eph2
Zm = Zm =
I ph1 I ph 2 2 I ph1
I2
2 Z1 + R f Rf
Zm = = Z1 +
2 2
BOOSTING YOUR ENERGY
REL 511 - What is Measured. ZMPh-Ph
The result is the so called Ohm/Phase
Impedance.
This impedance belongs to phase 1
I1 Z1
Rf
Zm = Z1 +
Eph1
Rf
2
Eph2
Z1
I2
I2
Once it is understood how the relay measures the impedance, it is necessary to
enter correct setting values to limit the trip zone.
Information about positive sequence impedance of the line must be entered:
R1PP and X1PP (both ohm/phase)
And information about the fault resistance must be entered:
RFPP (ohm/loop) BOOSTING YOUR ENERGY
REL 511 - ZM: Operating characteristic for PP loops
Im
j X1PP
RFPP
+j0
2
R1PP + j X1PP
X1PP
= arctan
R1PP
Re
RFPP RFPP
R1PP +
2 2
It can also be seen that the characteristic involves fault resistance also to the
left of the line impedance. This is for example useful if the distance protection
shall operate as remote back-up protection for a transformer with small
resistance in relation the its reactance.
Im
j X1PP
Re
RFPP
2 BOOSTING YOUR ENERGY
REL 511 - What is Measured. ZMPh-Ph (3-phase faults)
Rf
Zm = Z1 +
Eph1
Z1 Rf/2
2
I2
Eph2
Z1 Rf/2 V=0
Eph3 I3
Z1 Rf/2
II11
Rf
Zm = Z1 +
Eph1
Z1 Rf/2
2
I2
Eph2
Z1 Rf/2 V=0
Eph3 I3
Phase-to-Earth Loops
E ph1 Z 0 Z1
Zm = KN =
I ph1 + K N 3I 0 3 Z1
Z1
II1
1
Eph1
Iph1 E ph1
Eph1
Z1
Rf Zm = = Z1 + R f + Z N
Eph2
I2
Z1
I ph1
Eph3 I3
ZN
Eph1
I2
Z1
Rf Z m = Z1 + R f + Z N
Eph2
Z1
Eph3 I3
ZN
Loop
Ohm/loop quantities help to remember how the relay measures. It can be
underlined that ZM measures the ohm/loop value of the fault resistance and the
fault resistance is set in ohm/loop values. Z1 is the positive sequence impedance
of the line. ZN is the earth return impedance.
BOOSTING YOUR ENERGY
REL 511 - How Much is ZN ?
Z 0 = Z1 + 3 Z N
Z 0 Z1
ZN =
3
Z0 Z1
ZN =
Z1
3 Zm = Z1 + R f + Z N
II1
1
Z0 Z1
Eph1
Z1
Zm = Z1 + + Rf
Eph2
I2
Rf
3
2 Z1 + Z0
Zm = + Rf
Z1
Eph3 I3
3
Zm = Z1 (1 + K N ) + R f
ZN
Z Z
KN = 0 1
3 Z1
BOOSTING YOUR ENERGY
REL 511 - What is Measured. ZMPh-E
Z1
II1
1
Eph1
2 Z1 + Z 0
Z1
Zm = + Rf
I2
Rf
3
Z 0 Z1
Eph2
Z m = Z1 + + Rf
Z1
Eph3 I3
3
ZN
R1PE + j X1PE
2 X 1PE + X 0 PE
= arctan
2 R1PE + R0 PE
2R1PE + R0PE Re
RFPE + RFPE
3
There is a directional function that limits the zone to see the faults in either
forward or reverse direction.
It can also be seen that the characteristic involves fault resistance also to the
left of the line impedance. This is for example useful if the distance protection
shall operate as remote back-up protection for a transformer with small
resistance in relation to its reactance.
Im
2 X1PE + X0PE
j
3
Re
RFPE
BOOSTING YOUR ENERGY
ZM function: Settings and characteristic
Directional line X
Directional line
TRIP:
0 Fault Resistance (R f ) RFPP
0 Line Impedance (Z1 ) R1PP + j X 1PP
Im
j X1PP Rf
Zm = Z1 +
2
RFPP
+j0
2
R1PP + j X1PP
X1PP
= arctan
R1PP
Re
RFPP RFPP
R1PP +
2 2
PP loops:
RFPP = K imp R f
It is recommended that RFPP 1.6 Zloadmin
70.00
0.8 Rloadmin
60.00
50.00
40.00
Zloadmin
30.00
Im
20.00
10.00
0.00
-30.00 -20.00 -10.00 0.00 10.00 20.00 30.00 40.00 50.00 60.00
-10.00
PhiMAX
-20.00 ( cosphi min)
-30.00
Re Rloadmin
RFPP/2
BOOSTING YOUR ENERGY
ZM1 function: Underreaching Zone 1 setting
PP loops:
For Zone 1 it is also recommended not to exceed with the ratio
resistive reach / reactive reach in order to avoid overreaching of
the zone:
Im
2 X1PE + X0PE
j
3
R1PE + j X1PE
2 X 1PE + X 0 PE
= arctan
2 R1PE + R0 PE
2R1PE + R0PE Re
RFPE + RFPE
3
PE loops:
The main requirement on Zone 1 reach setting is that
it should never overreach the line length.
PE loops:
This is valid also for the earth-return path, i.e. for the
zero-sequence settings:
X 0 PE = K imp (0.85 X 0 )
R 0 PE = K imp (0.85 R0 )
RFPE = K imp R f
It is recommended that RFPE 0.8 Zloadmin
70.00
0.8 Rloadmin
60.00
50.00
40.00
Zloadmin
30.00
Im
20.00
10.00
0.00
-30.00 -20.00 -10.00 0.00 10.00 20.00 30.00 40.00 50.00 60.00
-10.00
PhiMAX
-20.00 (cosphimin)
-30.00
Re Rloadmin
RFPE
BOOSTING YOUR ENERGY
ZM1 function: Underreaching Zone 1 setting
PE loops:
PP loops:
The main requirement on Zone 2 setting is that it should always
cover at least 120% of the complete line length (to avoid
underreaching) and it should (preferably) not be set longer than
80% Zone 1 of the next shortest line.
PP loops:
RFPP = K imp R f
It is recommended that RFPP 1.6 Zloadmin
PE loops:
The main requirement on Zone 2 setting is that it should always
cover at least 120% of the complete line length (to avoid
underreaching) and it should (preferably) not be set longer than
80% zone1 of the next shortest line.
PE loops:
This is valid also for the earth-return path, i.e. for the zero-
sequence settings:
X 0 PE = K imp (1.20 X 0 )
R 0 PE = K imp (1.20 R0 )
PE loops:
RFPE = K imp R f
It is recommended that RFPE 0.8 Zloadmin