GUIDELINES FOR LOW VOLTAGE (LV ) MOTOR MAINTENANCE(EXCLUDING SPECIAL APPLICATION MOTORS)
1.2 Use of temperature sticker at connection in motor Yearly Plant IEM <70 Deg. C
1
TB & MCC Cubicle.
(Maximum range of temperature sticker should
be 85 Deg. C) Note-All CDT values
1.3 Monitoring of motor body temperature , Bearing Yearly Plant IEM 1.3.1 Motor body & should be recorded for
temperature bearing temperature analysis & future
Should be <70 Deg. reference.
C
1.4 Monitoring of motor vibration Yearly Plant IEM Ref: ISO-2372 & IS- Reading of vibration
12075 to be compared with
previous reading i.e
Page 2 of 5
MEG/UTE/SOP/01/2012 Rev 00 Effective Date-14.03.2012
Above 15 KW & up to
300KW- Less than 2.8
mm/sec
1.5 Inspection of motor JB, TB, MCC Cubicle Yearly Plant IEM
2.1 Greasing in motor bearings to be done with As per Motor Plant IEM Greasing to be done
2 listening rod. Name Plate in running Condition
2.2 Cleaning & blowing of motor at site Yearly Plant IEM This may vary based
on site condition
OVERHAULING
3.1 LV motors overhauling at Electrical Repair Shop Based on Plant IEM Overhauling
CDT result frequency should be
decided by Plant IEM
3 based on CDT ,
failure history /
environment condition
3.2 LV motors ( having sealed bearings ) 3 Years Plant IEM Based on sealed
overhauling at Electrical Repair Shop bearing life
Page 3 of 5
MEG/UTE/SOP/01/2012 Rev 00 Effective Date-14.03.2012
PROTECTION
4.1 Up to 5KW Motors- Thermal overload One time Plant IEM 1.Three phase fault
relay/EOCR current and fault at
4.2 >5KW up to 15 KW-EOCR with at least Plant IEM which motor tripped
One time
overload protection should be recorded
4.3 >15KW up to 30 KW-EOCR with at least and analyzed before
One time Plant IEM each reset/restart
overload protection & Earth fault protection
5.1 Installation of Space heater in motors operating One time Power arrangement of
in moisture /steam environment or install motor with space heater should be
5 proper design which can work without space heater Plant IEM such that, its power
in moisture/steam environment will be off when main
power put off.
Page 4 of 5
MEG/UTE/SOP/01/2012 Rev 00 Effective Date-14.03.2012
Insulation Monthly Yearly Yearly Yearly Monthly Monthly Quarterly Half Yearly
Resistance
Winding Monthly Yearly Yearly Yearly Monthly Monthly Quarterly Half Yearly
Resistance and
Inductance
CDT
Motor Quarterly Monthly Quarterly Fortnightly Monthly Monthly Quarterly Half Yearly
Temperature
(Body/Bearing/TB)
Vibration Half yearly Quarterly Half yearly Fortnightly Yearly Yearly Yearly Yearly
TBM Greasing Not Applicable As per motor name As per motor As per motor As per motor As per As per As per motor
plate name plate name plate name plate motor motor name plate
name plate name plate
O/H Overhauling 3 Years 5 years 5 Years 2 years 5 Years (to 5 Years (to 8 Years (to 8 Years (to
start with) start with) start with) start with)
A+ = Very critical (Hot metal crane in Steel Making area) , A = Critical (Down time leads to plant outage) , B = Important (Down time may /may not lead to plant outage)
C & D = General Purpose cranes (Ref: Internal to Tata Steel based on NSC learning)