Product Description
Re li able Mod els F1FR and F1FR Re cessed Sprin klers are
quick response sprinklers which combine the durability of a
stan dard sprin kler with the at trac tive low pro file of a deco ra-
tive sprinkler. Vertical Sidewall Conventional
The Models F1FR and F1FR Recessed automatic sprin-
klers utilize a 3.0 mm frangible glass bulb. These sprinklers
have dem on strated re sponse times in labo ra tory tests which
are five to ten times faster than standard response sprin-
klers. This quick response enables the Model F1FR and
F1FR Recessed sprinklers to apply water to a fire much
faster than standard sprinklers of the same temperature rat -
ing.
The glass bulb consists of an accurately controlled
amount of special fluid hermetically sealed inside a pre-
cisely manufactured glass capsule. This glass bulb is spe-
cially constructed to provide fast thermal response. The
balance of parts are made of brass, copper and beryllium Horizontal Sidewall
HSW 1 Deflector Recessed Pendent
nickel.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can Application
be seen as a small bub ble. As heat is ap plied, the liq uid ex - Quick response sprinklers are used in fixed fire protec-
pands, forcing the bubble smaller and smaller as the liquid tion sys tems: Wet, Dry, Del uge or Preaction. Care must be
pressure increases. Continued heating forces the liquid to ex er cised that the ori fice size, tem pera ture rat ing, de flec tor
push out against the bulb, causing the glass to shatter, style and sprinkler type are in accordance with the latest
opening the waterway and allowing the deflector to distrib- published standards of the National Fire Protection Asso-
ute the discharging water. ciation or the approving Authority Having Jurisdiction.
The temperature rating of the sprinkler is identified by the Quick response sprinklers are intended for installation as
color of the glass bulb. speci fied in NFPA 13. Quick re sponse sprin klers and stan-
dard response sprinklers should not be intermixed.

The Re li able Auto matic Sprin kler Co., Inc. 525 North MacQuesten Park way, Mount Ver non, New York 10552
Model F1FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:

Sprin kler Type K Fac tor Sprinkler Identification


Stan dardUp right (SSU) and Pen dent ( SSP) Sprinkler Approval Num ber (SIN)
US Metric Height Organization
De flec tors Marked to In di cate Po si tion SSU SSP
1
(15mm) Stan dard Or i fice with 2 NPT (R 2) Thread
2
1 1
5.62 81.0 2.2 (56mm) 1,2,3,4,5,6,7 R3625 R3615
32 (20mm) Large Or i fice with 4 NPT (R)Thread 8.0 115.3 2.3 (58mm) 1,2,3,4,7,8 R3622 R3612
17 3

(1)
16 (17mm) Small Or i fice with 2 NPT (R 2) Thread
1
7 1
4.24 61.0 2.54 (65mm) 1,2,8 R3623 R3613
(1)
8 (10mm) Small Or i fice with 2 NPT (R 2) Thread
1
3 1
2.82 40.6 2.54 (65mm) 1,2,8 R3621 R3611
10mmOrifice XLH with R38 Thread 4.10 59.1 56.1mm 4,6,7 R3624 R3614
Con ven tionalIn stall in Up right or Pen dent Po si tion
10mmOrifice XLH with R38 Thread 4.10 59.1 56.1mm R3674
15mm Stan dard Or i fice with 12 NPT (R1 2) Thread 5.6 81.0 56.1mm 4,6,7 R3675
20mm Large Or i fice with NPT (R)Thread 8.0 115.3 58.4mm 4,7 R3672
(1)
Iden tified by a pintle ex tend ing be yond the de flec tor.

Upright Pendent Upright (1) Conventional

Model F1FR Quick Response Recessed Pendent Sprinkler


Installation Wrench: Model RC1 Sprinkler Wrench
Installation Data:
Nominal Thread K Fac tor Sprin kler Approval (2) Sprinkler Identification
Orifice Size US Metric Height Organizations Number (SIN)
1
2 (15mm) 1 NPT (R)
2 5.62 81.0 2.2 (56mm) 1,2,3,4,5,7,8 R3615
17
32 (20mm) 3
4 NPT (R) 8.0 115.3 2.3 (58mm) 1,2,3 R3612
7
16 (1) (11mm) 1
NPT (R)
2 4.24 61.0 2.54 (65mm) 1,2,8 R3613
3
8 (1) (10mm) 1
NPT (R)
2 2.82 40.6 2.54 (65mm) 1,2,8 R3611
10mm R3 8 4.10 59.1 56.1mm 4,7 R3614
(1)
Identified by a pintle extending beyond the deflector.
(2)
Re fer to es cutch eon data ta ble for ap prov als and di men sions.

2.
Model F1FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
K Factor Approval Sprinkler Identification
Nominal Orifice Thread Size Sprinkler Height Organizations Number (SIN)
US Metric

NPT (R) 5.62 81.0 2.2 (56mm) 1, 2, 3, 6, 8


R3685
15mm NPT (R) 5.62 81.0 2.2 (56mm) 4 (1)
(1)
LPC Ap proval is Pen dent only.

Orientation Deflector to Ceil ing


Dimension (Min. - Max.)
Upright 4 - 12 (102mm - 305mm)
Pendent 6 - 12 (152mm - 305mm)

Vertical Sidewall

Model F1FR Quick Response Horizontal Sidewall Sprinkler


Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:

ApprovalOrganizations Sprin kler


K Factor and Type of Ap proval Identification
Nominal Thread Sprinkler Light Ordinary Num ber
Orifice Size US Metric Length (SIN)
Hazard Hazard
1
(15mm)
2
1
NPT(R)
2 5.62 81.0 2.63 (67mm) 1,2,3,5,8 1,2,5,8 R3635
NOTE: UL and ULC Listing permits use with F1 or F2 recessed escutcheon.

Horizontal Sidewall

3.
Installation Maintenance
Quick response sprinklers are intended for installation The Models F1FR and F1FR Recessed Sprinklers
as specified in NFPA 13. Quick response sprinklers and should be inspected quarterly and the sprinkler system
standard response sprinklers should not be intermixed. maintained in accordance with NFPA 25. Do not clean
The Model F1FR Recessed Quick Response Sprinklers sprinklers with soap and water, ammonia or any other
are to be installed as shown. The Model F1 or F2 Escutch- clean ing flu ids. Re move dust by us ing a soft brush or gen-
eons illustrated are the only recessed escutcheons to be tle vacuuming. Remove any sprinkler which has been
used with the Model F1FR Sprinklers. The use of any other painted (other than factory applied) or damaged in any
re cessed es cutch eon will void all ap prov als and ne gate all way. A stock of spare sprinklers should be maintained to
warranties. allow quick replacement of damaged or operated sprin-
When in stall ing Model F1FR Sprin klers, use the Model D klers. Prior to installation, sprinklers should be maintained
Sprinkler Wrench. When installing Model F1FR Recessed in the original cartons and packaging until used to mini-
Sidewall Sprinklers, use the Model GFR1 Sprinkler mize the potential for damage to sprinklers that would
Wrench. Use the Model RC1 Wrench for installing F1FR cause improper operation or non-operation.
Recessed Pendent Sprinklers. Any other type of wrench
may damage these sprinklers.
Approval Organizations Sprinkler Types
1. Underwriters Laboratories, Inc. Standard Upright
2. Underwriters Laboratories of Canada Standard Pendent
3. Factory Mutual Research Corporation Conventional
4. Loss Prevention Council Sidewall (Vertical, Horizontal HSW1)
5. NYC BS&A No. 587-75-SA Recessed Pendent
6. Meets MIL-S-901C and MIL-STD 167-1 Recessed Horizontal Sidewall HSW1
7. Verband der Schadenversicherer (1) (2)
8. NYC MEA 258-93-E Finishes
ULI Listing Category Standard Finishes
Sprinklers, Automatic & Open Sprinkler Escutcheon
Quick Response Sprinkler Bronze Brass
ULI Guide Number Chrome Plated Chrome Plated
VNIV White Polyester Coated White Painted
Special Application Finishes
Temperature Ratings Sprinkler Escutcheon
Sprinkler Bright Brass Bright Brass
Temperature Max. Ambient Bulb
Classification Temp. Color Black Plated Black Plated
C F
Black Paint Black Paint
Ordinary 57 135 100F (38C) Orange Off White Off White
Ordinary 68 155 100F (38C) Red
Intermediate 79 175 150F (66C) Yellow Satin Chrome Satin Chrome
Intermediate 93 200 150F (66C) Green (1)
High (1) 141 286 225F (107C) Blue Other fin ishes and col ors are avail able on spe cial or der.
Consult the factory for details.
(1) (2)
Not available for recessed sprinklers. FM Approval is lim ited to bronze and brass, chrome or black
plated finishes only.
Escutcheon Data
Escutcheon A
Face of Fitting Ordering Information
Approvals Adjustment to Ceiling or Specify:
Model Dimension
Wall Dimension 1. Sprinkler Model
3
4
3
4
3 - 15
16 16
2. Sprinkler Type
F1 1,2,4
(19mm) (19mm) (5mm - 24mm) 3. Orifice Size
3 - 11
4. Deflector Type
2
1
F2 1,2,3,4,5,7,8 1 16 16
5. Temperature Rating
(13mm) (25mm) (5mm - 24mm)
6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
Note: When Model F1FR Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
The equip ment pre sented in this bul le tin is to be in stalled in ac cor dance with the lat est per ti nent Stan dards of the Na tional Fire Pro tec tion As so ci a tion, Fac tory Mu tual Re search
Cor po ra tion, or other sim i lar or ga ni za tions and also with the pro vi sions of gov ern men tal codes or or di nances when ever ap pli ca ble.

Prod ucts man u fac tured and dis trib uted by Re li able have been pro tect ing life and prop erty for over 80 years, and are in stalled and ser viced by the most highly qual i fied and rep u ta -
ble sprin kler con trac tors lo cated through out the United States, Can ada and for eign coun tries.

Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
(800)4311588 Sales Offices
(800)8486051 Sales Fax Revision lines indicate updated or new data
(914)6683470 Corporate Offices
www.reliablesprinkler .com Internet Address EG. Printed in U.S.A. 12/00 P/N9999970027