Supply Air Diffuser Selection - Telecom Room at Upstream Building

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

Linear Slot Diffusers

air master

Chapter 7

INDEX
A. Linear slot diffusers:
1. Supply linear slot diffusers ...........:ASLD...........7.1
2. Return linear slot diffusers............:ARLD...........7.2
3. Curved supply linear slot diffusers ..:ASLD (C).......7.3

Slots Vs Diffuser dimensions............................7.4


Possible air deliveries....................................7.4
Optional mitered corners.................................7.5
Optional profiles...........................................7.6
Fixing details ..............................................7.6
Flange models.............................................7.7
How to order ...............................................7.7

B.Air flow data.


1. Supply linear slot diffuser - 20 mm .: Tab:7.1........7.8
2. Supply linear slot diffuser - 25 mm .: Tab:7.2........7.10
3. Supply linear slot diffuser - 16 mm .: Tab:7.3........7.12
4. Return linear slot diffusers - 20 mm: Tab:7.4........7.14
5. Return linear slot diffuser - 25 mm .: Tab:7.5........7.15
6. Return linear slot diffuser - 16 mm .: Tab:7.6........7.16

Copyright reserved. Specifications subject to change without notice.

ISO 9002 certified company


Linear Slot Diffusers

air master Supply air linear slot diffuser


Model: ASLD

Construction:
Frame & Blades: High quality extruded alumini-
um profiles.
Damper: Hit and miss damper.
Slot width: 20 mm as standard. 16 mm, 25 mm
and non standard sizes available as option.
Number of slots available: 1,2,3,4,5,6,7,8
1.5 mt.
Length: Up to 5.8 mt available in a single piece.
Optional accessories: Plenum box either
unlined, internally insulated or externally insulated.
Foam gasket is sealed around the back of the
Description: frame as option to avoid air leakage.
Frame and deflection blades are made of high
quality extruded aluminium profiled construction Suitable for installation for ceiling and sills.
with the advantages of corrosion resistance and
rigidity. Standard finishes:
Natural anodized aluminium finish.
Air distribution can be changed vertically or hor-
Powder coated colour finish as per RAL colour
izontally by means of deflection blades with out
code.
changing the air flow rate. These blades can be
Flexibility of finish available.
fully adjusted from face opening.

Air flow rate can be adjusted by fixing hit and


miss damper at the rear side of the diffuser.
Damper blades are adjusted from the face open-
ing.

Dampers are designed in a unique way that it


can be used as an equalizing grid.

Positive alignment of adjacent sections can be


made by using alignment strips.

Copyright reserved. Specifications subject to change without notice.

7.1
ISO 9002 certified company
Linear Slot Diffusers

air master Return air linear slot diffuser


Model: ARLD

Construction:
Frame and blades: High quality extruded alu-
minium profiles.
Optional Damper: Hit and miss damper.
Slot width: 20 mm as standard. 16 mm, 25 mm
and non standard sizes available as option.
Number of slots available: 1,2,3,4,5,6,7,8.
Length: Upto 5.8 mt available in a single piece.
Optional accessories: Plenum box either
unlined, internally insulated or externally insulat- Foam gasket is sealed around the back of the
ed. frame as option to avoid air leakage.

Suitable for installation into ceiling and sills.


Description:
Frame and deflection blades are made of high
Standard finishes:
quality extruded aluminium profiled construction
with the advantages of corrosion resistance and Natural anodized aluminium finish.
rigidity. Powder coated colour finish as per RAL colour
code.
Positive alignment of adjacent sections can be Flexibility of finish available.
made by using alignment strips that are provid-
ed with each diffuser.

Structure is manufactured by mechanical


assembly to ensure rigidity and maintain
straight line appearance.

Available with out hit and miss damper as stan-


dard. Damper will be provided as option.

Copyright reserved. Specifications subject to change without notice.


7.2
ISO 9002 certified company
Linear Slot Diffusers

air master Curved supply air linear slot diffuser


Model: ASLD(C)

Construction:
Frame & Blades: High quality extruded alumini-
um profiles.
Damper: Hit and miss damper.
Slot width: 20 mm as standard. 16 mm, 25 mm
and non standard sizes available as option.
Number of slots available: 1,2,3,4,5,6,7,8
Length: Up to 3 meters are available in a single
piece.

Description:
Frame and deflection blades are made of high Model: ARLD(C): Same as ASLD(C), without hit
quality extruded aluminium profiled construction and miss damper.
with the advantages of corrosion resistance and
rigidity. Standard finishes:
Natural anodized aluminium finish.
Hit and miss damper will be fixed rigidly at the Powder coated colour finish as per RAL colour
rear side of the diffuser as option. code.
Flexibility of finish available.
Positive alignment of adjacent sections can be
made by using alignment strips.

Foam gasket is sealed around the back of the


frame as option to avoid air leakage.

Suitable for installation in ceiling and sills.

Supply and return air curved linear slot diffusers


are available up to a length of 3 meters with a
minimum radius of curvature of 1 meter.

Copyright reserved. Specifications subject to change without notice.

7.3
ISO 9002 certified company
Linear Slot Diffusers

air master Slots Vs Diffuser dimensions in mm.

16 mm slot opening

No of slots 1 2 3 4 5 6 7 8
N=Neck size in mm 38 68 98 128 158 188 218 248
Duct size in mm 48 78 108 138 168 198 228 258
A in mm 31 61 91 121 151 181 211 241
B in mm 79 109 139 169 199 229 259 289
False ceiling opening size 59 89 119 149 179 209 239 269

20 mm slot opening

No of slots 1 2 3 4 5 6 7 8
N=Neck size in mm 42 76 110 144 178 212 246 280
Duct size in mm 52 86 120 154 188 222 256 290
A in mm 35 69 103 137 171 205 239 273
B in mm 83 117 151 185 219 253 287 321
False ceiling opening size 63 97 131 165 199 233 267 301

25mm slot opening

No of slots 1 2 3 4 5 6 7 8
N=Neck size in mm 47 86 125 164 203 242 281 320
Duct size in mm 57 96 136 174 213 252 291 330
A in mm 40 79 118 157 196 235 274 313
B in mm 88 127 166 205 244 283 322 361
False ceiling opening size 68 107 146 185 224 263 302 341

Possible air deliveries:

Copyright reserved. Specifications subject to change without notice.

7.4
ISO 9002 certified company
Linear Slot Diffusers

air master

Optional mitered corners

Standard 900 horizontal mitered corners available


for floor, sill and ceiling applications.

7 a. 90 Mitred corner

Special horizontal mitered corners selection avail-


able for floor, sill and ceiling applications includes
an angle greater than 90 0 and less than 180 0.

7 b. Variable Mitred corner

Vertical outside mitered corners are available for


wall application at the junction of two outside walls
with a standard angle of 900.

7 C. Side wall - outside corner

Vertical inside mitered corners are available for


wall application at the junction of two inside walls
with a standard angle of 900.

7 d. Side wall - inside corner

Copyright reserved. Specifications subject to change without notice.

7.5
ISO 9002 certified company
Linear Slot Diffusers

air master

Optional profiles

Fixing details
C-Clamp fixing:

Fixing to the plenum box:

Copyright reserved. Specifications subject to change without notice.

7.6
ISO 9002 certified company
Linear Slot Diffusers

air master

Flange models:

How to order:

Optional
Model No of slots Length End flange details Qty Finish
Slot width
1 5 A). With open ends A). Natural anodized
16 mm 6 No.
ASLD Aluminium finish
2 6 1.5 mt. B). One side end flange
Specify
Specify in
25 mm in B). RAL 9010
3 7 meters C). One side end cap
numbers
ARLD
Other size With both sides C). Other colours
4 8
D). Flange (or) E) caps

Tick the required item.

Ordering example:
To select supply linear slot diffuser, 4 slots with a slot width of 20 mm of length 2.5 meters with open
ends. Quantity 50 numbers with RAL9010 colour finish.
Order as : ASLD-4-2.5- A -50-B.
ASLD-25-8-1.5-D-6-C

Copyright reserved. Specifications subject to change without notice.


7.7
ISO 9002 certified company
Linear Slot Diffusers

air master Supply linear slot diffuser


20 mm slot width Model: ASLD

Table 7.1 Air flow data


Number Air flow rate per meter Face Throw Ps in Noise
of slots length Velocity Criteria
Ak in m 2
Cfm m /sec
3
m/sec In meters mm H2O (NC)
50 0.024 2.79 3.6 - 2.1 - 0.6 0.69 <15
1 75 0.035 4.07 4.9 - 3.0 - 1.8 1.55 24
100 0.047 5.46 6.1 - 4.3 - 2.7 2.74 32
125 0.059 6.86 7.0 - 4.9 - 3.7 4.32 38
0.0086 150 0.071 8.26 7.6 - 5.8 - 4.6 6.22 43
175 0.083 9.65 8.5 - 6.7 - 5.2 8.38 46
100 0.047 4.47 4.3 - 1.8 - 0.6 1.02 16
2 125 0.059 5.36 5.2 - 3.0 - 1.5 1.57 22
150 0.071 6.45 6.1 - 3.9 - 2.1 2.28 30
175 0.083 7.55 6.7 - 4.6 - 3.0 3.09 33
0.011 200 0.094 8.55 7.0 - 5.2 - 4.3 4.06 36
250 0.118 10.73 7.9 - 6.1 - 4.9 6.35 43
125 0.059 3.99 4.0 - 2.1 - 0.6 0.91 <15
3 150 0.071 4.80 4.6 - 2.7 - 1.2 1.29 23
200 0.094 6.35 5.2 - 3.4 - 2.1 2.31 29
225 0.106 7.16 6.1 - 4.0 - 3.1 2.94 33
0.0148 250 0.118 7.97 7.0 - 4.9 - 3.7 3.63 36
300 0.142 9.59 7.9 - 5.8 - 4.3 5.21 41
150 0.071 3.74 4.3 - 2.4 - 0.9 0.76 <15
4 200 0.094 4.95 5.2 - 3.4 - 1.8 1.37 20
250 0.118 6.21 5.8 - 4.0 - 2.7 2.13 27
300 0.142 7.47 6.4 - 4.6 - 3.4 3.07 33
0.019 350 0.165 8.68 7.3 - 5.5 - 4.0 4.17 36
400 0.189 9.95 7.9 - 6.1 - 4.6 5.46 40

Data based on one meter length of the diffuser with damper fully opened.
Face velocity is measured in m/sec.
Ps: Static pressure loss is in mm of H2O. Area factor in square meters.
Throw (meters) is measured for a terminal velocities of 0.25, 0.5 and 0.75 m/sec.
NC based on a room attenuation of 10 dB.
Above data is tested & certified by ETL.

Copyright reserved. Specifications subject to change without notice.

7.8
ISO 9002 certified company
Linear Slot Diffusers

air master Supply linear slot diffuser


20 mm slot width Model: ASLD

Table 7.1 (Cont.) Air flow data


Number Air flow rate per meter Face Throw Ps in Noise
of slots length Velocity Criteria
Ak in m 2
Cfm m /sec
3
m/sec In meters mm H 2O (NC)
250 0.118 4.72 5.5 - 4.0 - 2.4 1.42 18
5 300 0.142 5.68 6.1 - 4.6 - 3.4 2.03 24
350 0.165 6.60 6.4 - 4.6 - 3.4 2.79 30
400 0.189 7.55 6.7 - 4.9 - 3.7 3.66 34
0.025 450 0.213 8.51 7.3 - 5.5 - 4.3 4.62 37
500 0.236 9.44 7.9 - 6.1 - 4.9 5.71 40
300 0.142 4.58 5.2 - 4.0 - 2.7 1.14 15
6 350 0.165 5.32 6.4 - 4.9 - 3.7 1.75 20
400 0.189 6.09 7.0 - 5.2 - 4.0 2.51 24
450 0.213 6.87 7.3 - 5.5 - 4.3 3.15 29
0.031 500 0.236 7.61 7.9 - 5.5 - 4.3 4.06 33
600 0.283 9.13 8.2 - 6.4 - 4.9 5.18 39
350 0.165 4.58 5.8 - 4.0 - 2.7 0.76 15
7 400 0.189 5.25 6.4 - 4.6 - 3.4 1.37 20
450 0.213 5.92 6.7 - 4.9 - 3.7 2.16 26
500 0.236 6.56 7.0 - 5.8 - 4.3 3.18 30
0.036 600 0.283 7.86 7.6 - 5.8 - 4.6 4.19 34
700 0.331 9.19 8.2 - 6.4 - 4.9 5.33 39
400 0.189 4.5 5.5 - 4.6 - 3.7 0.64 16
8 450 0.213 5.07 6.1 - 4.6 - 3.7 1.29 20
500 0.236 5.62 6.4 - 5.2 - 4.0 2.16 25
600 0.283 6.74 7.0 - 5.2 - 4.0 3.05 31
0.042 700 0.331 7.88 7.6 - 6.7 - 4.9 3.94 34
800 0.378 9.00 8.5 - 7.0 - 5.2 5.08 39

Data based on one meter length of the diffuser with damper fully opened.
Face velocity is measured in m/sec.
Ps: Static pressure loss is in mm of H2O. Area factor in square meters.
Throw (meters) is measured for a terminal velocities of 0.25, 0.5 and 0.75 m/sec.
NC based on a room attenuation of 10 dB.
Above data is tested & certified by ETL.

Copyright reserved. Specifications subject to change without notice.

7.9
ISO 9002 certified company
Linear Slot Diffusers

air master Supply linear slot diffuser


25 mm slot width Model: ASLD-25

Table 7.2 Air flow data


Number Air flow rate per meter Face Throw Ps in Noise
of slots length Velocity Criteria
Ak in m 2
Cfm m /sec
3
m/sec In meters mm H2O (NC)
50 0.024 2.26 3.1 - 1.9 - 0.6 0.62 <15
1 75 0.035 3.30 4.3 - 2.7 - 1.6 1.39 22
100 0.047 4.43 5.3 - 3.8 - 2.4 2.46 30
125 0.059 5.57 6.1 - 4.3 - 3.3 3.73 36
0.0106 150 0.071 6.69 6.6 - 5.1 - 4.1 4.51 40
175 0.083 7.83 7.4 - 5.9 - 4.6 6.87 44
100 0.047 3.48 3.7 - 1.6 - 0.6 0.92 15
2 125 0.059 4.37 4.4 - 2.7 - 1.4 1.42 20
150 0.071 5.26 5.2 - 3.4 - 1.9 2.05 28
175 0.083 6.15 5.7 - 4.0 - 2.8 2.67 30
0.0135 200 0.094 6.96 6.0 - 4.5 - 3.8 2.95 34
250 0.118 8.74 6.8 - 5.3 - 4.4 5.2 40
125 0.059 3.28 3.3 - 1.8 - 0.6 0.82 <15
3 150 0.071 3.94 3.8 - 2.3 - 1.0 1.16 22
200 0.094 5.22 4.3 - 2.9 - 1.8 2.08 27
225 0.106 5.89 5.1 - 3.4 - 2.7 2.53 31
0.018 250 0.118 6.56 5.8 - 4.2 - 3.2 2.63 34
300 0.142 7.89 6.6 - 5.0 - 3.7 4.27 39
150 0.071 3.09 3.5 - 2.0 - 0.9 0.68 <15
4 200 0.094 4.09 4.3 - 2.9 - 1.6 1.23 20
250 0.118 5.13 4.8 - 3.4 - 2.3 1.92 26
300 0.142 6.17 5.3 - 3.9 - 2.9 2.65 31
0.023 350 0.165 7.17 6.0 - 4.6 - 3.5 3.02 34
400 0.189 8.22 6.5 - 5.2 - 4.0 4.48 37

Data based on one meter length of the diffuser with damper fully opened.
Face velocity is measured in m/sec.
Ps: Static pressure loss is in mm of H2O. Area factor in square meters.
Throw (meters) is measured for a terminal velocities of 0.25, 0.5 and 0.75 m/sec.
NC based on a room attenuation of 10 dB.
Above data is tested & certified by ETL.

Copyright reserved. Specifications subject to change without notice.

7.10
ISO 9002 certified company
Linear Slot Diffusers

air master Supply linear slot diffuser


25 mm slot width Model: ASLD-25

Table 7.2 (Cont.) Air flow data


Number Air flow rate per meter Face Throw Ps in Noise
of slots length Velocity Criteria
Ak in m 2
Cfm m /sec
3
m/sec In meters mm H 2O (NC)
250 0.118 3.81 4.5 - 3.3 - 2.0 1.28 17
5 300 0.142 4.58 5.0 - 3.8 - 2.9 1.8 23
350 0.165 5.32 5.2 - 3.8 - 2.9 2.45 29
400 0.189 6.09 5.5 - 4.0 - 3.1 3.16 32
0.031 450 0.213 6.87 5.9 - 4.6 - 3.6 3.88 35
500 0.236 7.61 6.4 - 5.1 - 4.2 4.68 37
300 0.142 3.64 4.2 - 3.3 - 2.3 1.03 15
350 0.165 4.23 5.1 - 4.1 - 3.1 1.54 20
6 400 0.189 4.85 5.6 - 4.3 - 3.3 2.20 23
450 0.213 5.46 5.8 - 4.5 - 3.6 2.72 28
500 0.236 6.05 6.3 - 4.5 - 3.6 3.41 31
0.039
600 0.283 7.26 6.6 - 5.3 - 4.1 4.25 35
700 0.331 8.49 7.2 - 5.9 - 4.7 5.1 39
350 0.165 3.67 4.6 - 3.2 - 2.3 0.69 <15
400 0.189 4.20 5.1 - 3.7 - 2.8 1.22 20
7 450 0.213 4.73 5.3 - 3.9 - 3.1 1.89 25
500 0.236 5.24 5.5 - 4.7 - 3.6 2.74 30
0.045 600 0.283 6.29 6.0 - 4.7 - 3.8 3.52 32
700 0.331 7.36 6.5 - 5.3 - 4.1 4.37 35
800 0.378 8.40 7.1 - 5.9 - 4.8 5.22 40
400 0.189 3.57 4.3 - 3.8 - 3.0 0.58 16
500 0.236 4.45 5.0 - 4.2 - 3.3 1.89 23
8 600 0.283 5.34 5.5 - 4.2 - 3.3 2.63 30
700 0.331 6.24 6.0 - 5.4 - 4.0 3.31 32
0.053 800 0.378 7.13 6.5 - 5.7 - 4.2 4.2 35
900 0.425 8.00 7.2 - 6.3 - 4.6 4.9 38
1000 0.378 8.90 8.1 - 6.9 - 5.2 5.6 41

Data based on one meter length of the diffuser with damper fully opened.
Face velocity is measured in m/sec.
Ps: Static pressure loss is in mm of H2O. Area factor in square meters.
Throw (meters) is measured for a terminal velocities of 0.25, 0.5 and 0.75 m/sec.
NC based on a room attenuation of 10 dB.
Above data is tested & certified by ETL.

Copyright reserved. Specifications subject to change without notice.

7.11
ISO 9002 certified company
Linear Slot Diffusers

air master Supply linear slot diffuser


16 mm slot width Model: ASLD-16

Table 7.3 Air flow data


Number Air flow rate per meter Face Throw Ps in Noise
of slots length Velocity Criteria
Ak in m 2
Cfm m /sec
3
m/sec In meters mm H2O (NC)
30 0.014 2.00 3.0 - 1.6 - 0.6 1.54 16
1 50 0.024 3.42 4.0 - 2.1 - 1.5 2.25 20
75 0.035 5.00 5.1 - 4.0 - 2.5 3.15 30
100 0.047 6.71 6.2 - 4.8 - 3.4 4.21 37
0.007 125 0.059 8.43 7.7 - 5.2 - 4.0 5.45 43
150 0.071 10.1 9.0 - 6.9 - 5.5 6.91 45
50 0.024 2.69 3.0 - 1.6 - 0.6 1.24 15
2 75 0.035 3.93 4.3 - 1.7 - 0.9 1.94 20
100 0.047 5.28 5.1 - 3.0 - 1.3 2.83 24
125 0.059 6.63 6.0 - 3.7 - 1.8 3.62 30
0.0089 150 0.071 7.98 6.3 - 4.1 - 2.5 4.79 38
175 0.083 9.32 7.2 - 5.6 - 4.0 6.27 42
100 0.047 3.92 3.7 - 1.8 - 0.6 0.83 18
3 125 0.059 4.92 4.6 - 2.7 - 1.2 1.52 23
150 0.071 5.92 5.1 - 3.1 - 1.9 2.44 28
175 0.083 6.92 59 - 3.7 - 2.6 3.66 32
0.012 200 0.094 7.83 6.7 - 4.5 - 3.2 4.94 36
250 0.118 9.83 7.6 - 5.2 - 3.9 6.45 43
125 0.059 3.93 4.3 - 2.1 - 0.8 0.70 15
4 150 0.071 4.73 5.0 - 3.1 - 1.5 1.43 18
175 0.083 5.53 5.3 - 3.8 - 2.4 2.44 24
200 0.094 6.27 5.9 - 4.5 - 3.0 3.51 30
0.015 250 0.120 8.00 6.8 - 5.1 - 3.7 4.65 34
300 0.142 9.47 7.4 - 6.0 - 4.3 6.15 41

Data based on one meter length of the diffuser with damper fully opened.
Face velocity is measured in m/sec.
Ps: Static pressure loss is in mm of H2O. Area factor in square meters.
Throw (meters) is measured for a terminal velocities of 0.25, 0.5 and 0.75 m/sec.
NC based on a room attenuation of 10 dB.
Above data is tested & certified by ETL.

Copyright reserved. Specifications subject to change without notice.

7.12
ISO 9002 certified company
Linear Slot Diffusers

air master Supply linear slot diffuser


16 mm slot width Model: ASLD-16

Table 7.3 (Cont.) Air flow data


Number Air flow rate per meter Face Throw Ps in Noise
of slots length Velocity Criteria
Ak in m 2
Cfm m /sec
3
m/sec In meters mm H2O (NC)
150 0.071 3.55 4.0 - 3.1 - 1.8 0.75 16
5 200 0.094 4.70 5.4 - 3.9 - 2.3 1.72 23
250 0.118 5.90 6.0 - 4.6 - 3.4 3.00 28
300 0.142 7.10 6.4 - 4.9 - 3.6 4.97 31
0.02 350 0.165 8.25 7.0 - 5.3 - 4.2 7.34 37
400 0.189 9.45 7.6 - 5.8 - 4.9 10.13 41
200 0.094 3.76 4.1 - 3.3 - 2.0 1.12 20
6 250 0.118 4.72 5.2 - 4.0 - 2.6 1.74 25
300 0.142 5.68 5.9 - 4.8 - 3.2 2.58 29
350 0.165 6.60 7.0 - 5.3 - 4.1 3.55 34
0.025 400 0.189 7.56 7.9 - 5.8 - 4.5 4.79 38
500 0.236 9.44 8.4 - 6.5 - 5.1 7.68 43
250 0.118 4.07 5.0 - 3.2 - 2.1 0.99 19
7 300 0.142 4.89 5.8 - 4.0 - 2.7 1.43 24
350 0.165 5.69 6.4 - 4.4 - 3.1 2.61 28
400 0.189 6.52 7.0 - 5.8 - 4.3 3.38 33
0.029 500 0.236 8.14 7.5 - 5.8 - 4.7 4.28 39
600 0.283 9.76 8.1 - 6.5 - 5.3 6.30 42
350 0.165 5.00 5.0 - 4.2 - 3.4 0.83 17
8 400 0.189 5.73 6.3 - 4.9 - 4.0 1.52 22
450 0.213 6.45 7.0 - 5.2 - 4.5 2.41 27
500 0.236 7.15 7.3 - 5.6 - 4.8 3.53 30
0.033 600 0.283 8.58 7.9 - 6.2 - 5.3 4.92 35
700 0.331 10.03 9.0 - 7.5 - 5.8 6.61 39

Data based on one meter length of the diffuser with damper fully opened.
Face velocity is measured in m/sec.
Ps: Static pressure loss is in mm of H2O. Area factor in square meters.
Throw (meters) is measured for a terminal velocities of 0.25, 0.5 and 0.75 m/sec.
NC based on a room attenuation of 10 dB.
Above data is tested & certified by ETL.

Copyright reserved. Specifications subject to change without notice.

7.13
ISO 9002 certified company
Linear Slot Diffusers

air master Return linear slot diffuser


20 mm slot width Model: ARLD

Table 7.4 Air flow data


No of
slots
CFM/m 100 150 200 250 300 350
M3/sec/m 0.047 0.071 0.094 0.118 0.142 0.165
1 Neg Ps 0.61 1.37 2.41 3.81 5.46 7.37
NC <15 19 28 36 42 48
CFM/m 250 300 350 400 450 500
M3/sec/m 0.118 0.142 0.165 0.189 0.212 0.236
2 Neg Ps 1.02 1.47 2.03 2.62 3.30 4.06
NC 17 22 27 32 36 40
CFM/m 350 400 450 500 600 700
M3/sec/m 0.165 0.189 0.212 0.236 0.283 0.331
3
Neg Ps 1.04 1.35 1.68 2.08 2.97 4.01
NC 17 22 25 30 34 40
CFM/m 400 500 600 700 800 900
M3/sec/m 0.189 0.236 0.283 0.331 0.378 0.425
4 Neg Ps 0.76 1.19 1.73 2.36 3.25 4.06
NC 15 21 26 30 35 40
CFM/m 500 600 700 800 1000 1200
M3/sec/m 0.236 0.283 0.331 0.378 0.472 0.567
5 Neg Ps 0.76 1.12 1.52 1.96 3.05 4.37
NC 15 22 27 30 35 42
CFM/m 600 700 800 1000 1200 1400
M3/sec/m 0.283 0.331 0.378 0.472 0.567 0.66
6 Neg Ps 0.83 1.08 1.78 2.18 3.53 4.75
NC 17 24 29 31 37 43
CFM/m 700 800 1000 1200 1400 1600
M3/sec/m 0.331 0.378 0.472 0.567 0.66 0.76
7 Neg Ps 0.93 1.13 1.83 2.36 3.66 4.75
NC 18 25 30 33 38 43
CFM/m 800 900 1100 1300 1500 1700
M3/sec/m 0.378 0.425 0.52 0.61 0.71 0.8
8 Neg Ps 1.02 1.13 1.96 2.45 3.87 4.93
NC 18 25 32 35 40 45

Data based on one meter length of the diffuser.


NC based on a room attenuation of 10 dB.
Ps: Static pressure loss is in mm of water.

Copyright reserved. Specifications subject to change without notice.

7.14
ISO 9002 certified company
Linear Slot Diffusers

air master Return linear slot diffuser


25 mm slot width Model: ARLD - 25

Table 7.5 Air flow data


No of
slots
CFM/m 100 150 200 250 300 350
M3/sec/m 0.047 0.071 0.094 0.118 0.142 0.165
1
Neg Ps 0.51 1.13 1.98 3.09 4.4 5.89
NC <15 18 26 33 38 45
CFM/m 250 300 350 400 450 500
M3/sec/m 0.118 0.142 0.165 0.189 0.213 0.236
2
Neg Ps 0.85 1.22 1.67 2.13 2.66 3.25
NC <15 21 25 29 33 37
CFM/m 350 400 450 500 600 700
M3/sec/m 0.165 0.189 0.213 0.236 0.283 0.331
3
Neg Ps 0.87 1.11 1.37 1.69 2.39 3.21
NC 16 21 23 28 31 37
CFM/m 400 500 600 700 800 900
M3/sec/m 0.189 0.236 0.283 0.331 0.378 0.425
4
Neg Ps 0.64 0.99 1.42 1.92 2.62 3.25
NC <15 20 24 28 32 37
CFM/m 500 600 700 800 1000 1200
M3/sec/m 0.236 0.283 0.331 0.378 0.472 0.567
5
Neg Ps 0.64 0.92 1.25 1.59 2.46 3.49
NC <15 21 25 27 32 39
CFM/m 600 700 800 1000 1200 1400
M3/sec/m 0.283 0.331 0.378 0.472 0.567 0.66
6
Neg Ps 0.67 0.83 1.39 1.77 3.85 3.8
NC 16 23 27 28 34 40
CFM/m 700 800 1000 1200 1400 1600
M3/sec/m 0.331 0.378 0.472 0.567 0.66 0.76
7
Neg Ps 0.75 0.91 1.48 1.92 2.95 3.8
NC 17 24 28 29 35 40
CFM/m 800 900 1100 1300 1500 1700
M3/sec/m 0.378 0.425 0.52 0.61 0.71 0.8
8
Neg Ps 0.83 0.91 1.56 1.99 3.12 3.94
NC 17 24 30 32 37 42

Data based on one meter length of the diffuser.


NC based on a room attenuation of 10 dB.
Ps: Static pressure loss is in mm of water.

Copyright reserved. Specifications subject to change without notice.

7.15
ISO 9002 certified company
Linear Slot Diffusers

air master Return linear slot diffuser


16 mm slot width Model: ARLD - 16

Table 7.6 Air flow data


No of
slots
CFM/m 100 150 200 250 300 350
M3/sec/m 0.047 0.071 0.094 0.118 0.142 0.165
1
Neg Ps 0.7 1.59 2.82 4.49 6.49 8.84
NC 17 21 30 38 45 52
CFM/m 250 300 350 400 450 500
M3/sec/m 0.118 0.142 0.165 0.189 0.213 0.236
2
Neg Ps 1.17 1.71 2.38 3.09 3.93 4.88
NC 20 26 31 37 42 46
CFM/m 350 400 450 500 600 700
M3/sec/m 0.165 0.189 0.213 0.236 0.283 0.331
3
Neg Ps 1.19 1.56 1.96 2.42 3.54 4.82
NC 20 26 29 34 40 46
CFM/m 400 500 600 700 800 900
M3/sec/m 0.189 0.236 0.283 0.331 0.378 0.425
4
Neg Ps 0.88 1.38 2.02 2.78 3.87 4.88
NC 17 25 30 35 41 47
CFM/m 500 600 700 800 1000 1200
M3/sec/m 0.236 0.283 0.331 0.378 0.472 0.567
5
Neg Ps 0.88 1.29 1.78 2.31 3.63 5.24
NC 17 26 29 35 41 48
CFM/m 600 700 800 1000 1200 1400
M3/sec/m 0.283 0.331 0.378 0.472 0.567 0.66
6
Neg Ps 0.96 1.25 2.08 2.57 4.20 5.7
NC 19 28 34 37 40 49
CFM/m 700 800 1000 1200 1400 1600
M3/sec/m 0.331 0.378 0.472 0.567 0.66 0.76
7
Neg Ps 1.07 1.38 2.14 2.78 4.36 5.7
NC 20 28 33 39 43 50
CFM/m 800 900 1100 1300 1500 1700
M3/sec/m 0.378 0.425 0.52 0.61 0.71 0.8
8
Neg Ps 1.17 1.31 2.29 2.89 4.61 5.9
NC 22 31 37 40 45 50

Data based on one meter length of the diffuser.


NC based on a room attenuation of 10 dB.
Ps: Static pressure loss is in mm of water.
Above data is tested & certified by ETL.

Copyright reserved. Specifications subject to change without notice.

7.16
ISO 9002 certified company

You might also like