Design Calculation For Wall

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Design Calculation for Wall:

Reference Code: IS: 875 Part 1 & 2 for Dead Load and Live Load on the structures
IS: 875 Part 3 for Wind Load Calculation
IS:800
Design Consideration :
The Structure is temporary structure with structural steel framing and RCC block foundation.

1. Dead Load (DL)

3 sp @ 5.0 m = 15.0 m
2 sp @ 6.0 m = 12 m

X
Axis of reference

a) Self weight of structure = Considered in staad


b) Weight of sheeting with fixtures etc. = 8 Kg/ sqm

Influence Length along Z axis = 6m


Load from sheeting as UDL on col along Z axis = 8x6
= 48 Kg/m
= 0.048 t/m

Influence Length along X axis = 5m


Load from sheeting as UDL on col along Z axis = 8x5
= 40 Kg/m
= 0.04 t/m

2. Live Load (LL)


a) LL as UDL = 20 Kg/m
= 0.02 t/m

3. Wind Load (WL)


a) Basic Wind Speed,Vb = 44 m/s
Height of structure,H = 8.2 m
Class of structure = A
Terrain category = II

K1 (Temporaray Str) = 0.71 (As per IS : 875 Table 1)


K2 = 1
K3 = 1

Vz = Vb x K1 x K2 X k3
= 44 x0.71 x 1 x 1
= 31.24 m/s

1
Pressure, Pz = 0.6 x Vz^2
2
= 59.71 kg/m

Wind directionality factor , Kd = 0.9


Area averaging factor , Ka = 1

2
Design Pressure, Pd = Pz x Kd x Ka = 53.739 kg/m

This pressure shall be reduced by 20% as the height of wall is less than 10 m

2
Hence Pd = 43 kg/m

b= 15 m

h = 8.2 m

b= 15 m
h= 8.2 m
b/h = 1.83

Force Co-efficient, Cf = 1.2 (From Table 24 of IS: 875 Part 3)


Solidity ratio , f 1

WL in X direction: WL X

WL on col = 43 x 1.2 x 6 x1
= 309.6 kg/m
= 0.310 t/m

WL in Z direction: WL Z

WL on col = 43 x 1.2 x 5x1


= 258 kg/m
= 0.258 t/m