TRANSFORMER STABILITY TEST

Short Circuit Calculations


Transformer Data
S= 125 MVA 220
VLow = 66 kV
Z= 12.85 %
VAP = 380 V
VHigh = 220 kV At Center step of tap changer

IR = S / (3 * Vhigh)

ISC = IR / Z = S / (3 * VHigh * X)

IINJ = ISC * VAP / VHigh = S * VAP / (3 * VHigh2 * Z)

IR Rated Current
S Rated Power (ONAN)
VLow Rated Voltage of low voltage side (Injection Side)
ISC Short Circuit Current at Rated Voltage
Z Transformer Percentage Impedance
IINJ The Injected Current at The applied Voltage
VAP Voltage Applied (Test Voltage) at low voltage side

IHigh = 4.41 A
ILow = 14.70 A
3 1.7320508076
IR_High = 328.0399256759
ISC 2552.8398885286

N= 3.3333333333