Professional Documents
Culture Documents
05442777
05442777
Abstract— This paper presents a unique method to determine the effectively used for the load flow analysis of radial
weakest branch or the overstressed branch in a distribution distribution systems.
network. This radial feature of the network has been fully All the 11 KV rural distribution feeders are radial in nature
exploited to establish the concept of local voltage stability and longitudinal in behavior due to vastness of our country
indicator in terms of reactive power. The effectiveness of the
like India. The voltages at the distant end of many such radial
proposed method has been successfully tested in 12 bus radial
distribution system and the results are found to be in very good feeders are very low which demands high voltage regulation.
agreement. The current article develops a novel and simple voltage
Keywords- Local voltage stability indicator; radial stability indicator (VSI) [11-12] to identify the weakest branch
distribution system; voltage collapse; weakest branch. of a radial distribution system. This VSI can be either referred
to a node or a line but in this paper it refers to a distribution
I. INTRODUCTION line. The effectiveness of the proposed VSI is then tested on
12 node radial distribution feeder [6].
Hence,VSI= 4Q (i + 1) {R 2 (i ) + X 2 (i )} (10)
Equating real and imaginary part of (4), we get
V (i ) X (i )
2
[R(i )P(i + 1) + X (i )Q(i + 1)] = (5)
V (i ) V (i + 1) cos (δ (i ) − δ (i + 1)) − V (i + 1)
2
In radial distribution system the power flow problem can be
and solved by distflow technique. The active and reactive power
[X (i )P(i + 1) − R(i )Q(i + 1)] = (6) flow through the branch near bus i is P (i ) and
V (i ) V (i + 1) sin (δ (i ) − δ (i + 1)) Q (i ) respectively and the active and reactive power flow
through the branch near bus (i+1) is P (i + 1 ) and
From (5) and (6), we get Q (i + 1 ) respectively.
Hence we can write
V (i ) V (i + 1) cos(δ (i ) − δ (i + 1)) − V (i + 1) =
2
P (i ) = P (i + 1 ) +
⎡ V (i ) V (i + 1) sin (δ (i ) − δ (i + 1)) + R(i )Q(i + 1) ⎤ (11)
P 2 (i + 1 ) + Q 2 (i + 1 )
R(i )⎢ ⎥ R (i )
⎣ X (i ) ⎦ V (i + 1 )
2
+ X (i )Q(i + 1)
Q (i ) = Q (i + 1 ) +
⎡ ⎧ R (i ) ⎫ (12)
⎢⎨
⎤
⎬ sin (δ (i ) − δ (i + 1))⎥ P 2
(i + 1 ) + Q 2 (i + 1 ) X (i )
V (i + 1) + V (i ) V (i + 1) ⎢ ⎩ X (i )⎭
2
⎥ V 2 (i + 1 )
⎢⎣ − cos (δ (i ) − δ (i + 1)) ⎥⎦
(7)
⎡ R (i ) ⎤
Here, ( P (i + 1 ) + jQ (i + 1 )) is the sum of complex load
2
+ Q (i + 1)⎢ + X (i )⎥ = 0
⎣ X (i ) ⎦
at bus (i+1) and all the complex power flow through the
downstream branches of bus (i+1).
The equation (7) is quadratic in nature and to have real roots,
the discriminate must be greater than or equal to zero. Now, the voltage magnitude at bus (i+1) is given by
From (7), we get
2
2 ⎡ ⎧ R (i ) ⎫ ⎤
V (i ) ⎢ ⎨ ⎬ sin (δ (i ) − δ (i + 1)) − cos (δ (i ) − δ (i + 1))⎥ V (i + 1 ) = V 2 (i ) − 2 ( P (i )R (i ) +
2
Q (i ) X (i )) +
⎣⎩ X (i ) ⎭ ⎦ (13)
(8) ( P 2 (i ) + Q 2 (i ))( R 2 (i ) + X 2 (i ))
⎡ R 2 (i ) ⎤
− 4Q (i + 1)⎢ + X (i )⎥ ≥ 0 V 2 (i )
⎣ X (i ) ⎦
⎣ X (i ) ⎦
.. . . . . . . . . .
b3 0.0635
1 2 3 4 5 6 7 8 9 10 11 12 b4 0.0808
b1 b2 b3 b4 b5 b6 b7 b8 b9 b10 b11 b5 0.0250
k j i h g f e d c b a b6 0.0216
SS b7 0.0981
b8 0.0897
Figure 1 Single line diagram of a main feeder.
b9 0.0304
We have determined active and reactive power at different b10 0.0096
node points of the main feeder (node points a to k) from (11) b11 0.0026
and (12) respectively (see Table 1) and the voltage magnitude
of all nodes through (13) (see Table 2). Then we have
determined the VSI of all branches of the feeder through (10) 100% load
(see Table 3). From Fig. 2, the investigation reveals that the
value of the VSI to be maximum in the branch b7 (connected
between buses 7 and 8). Thus branch b7 can be considered as 0.12
the weakest branch or heavily loaded branch of the system. Voltage stability indicator
0.1
TABLE I POWER AT DIFFERENT NODE POINTS (A TO K) OF THE FEEDER.
0.08
Node point Power at different node points of the main
feeder
Active power in Reactive power in 0.06
KW KVAR
a 55.0051 45.0014 0.04
b7 0.1197 0.1536 0.2143 weakest bus of the 12 bus radial distribution system. Hence,
b8 0.1099 0.1418 0.1999 once the voltage stability indicator is achieved, the operating
b9 0.0374 0.0486 0.0692 personnel can have a sufficient knowledge regarding the
b10 0.0118 0.0154 0.0220
overstressed or weakest branch of the power network.
b11 0.0032 0.0042 0.0060
V. PROPOSED WORK
As an extension of the work, we can increase the load
120% load 150% load 200% load
multiplier factor until the system finally collapse and at that
point the operating personal can decide the critical juncture of
Voltage stability indicator
0.15 REFERENCES
0.1 [1] H. K. Clark, “ New challenges: Voltage stability ” IEEE Power Engg
Rev, April 1990, pp. 33-37.
0.05 [2] T. Van Cutsem: “ A method to compute reactive power margins with
respect to voltage collapse”, IEEE Trans. on Power Systems, No. 1, 1991.
0 [3] Ph.D thesis of Dr. C.K. Chanda on “Global voltage stability indicator
1 2 3 4 5 6 7 8 9 10 11 index” in 2003,BESU.
[4] R. Ranjan, B. Venkatesh, D. Das, “Voltage stability analysis of radial
Branch num ber distribution networks”, Electric Power Components and Systems,Vol.
31, pp. 501-511, 2003.
[5] M. Chakravorty, D. Das, “ Voltage stability analysis of radial distribution
Figure 3 Voltage stability indicator of all branches of the main feeder at
networks”, Electric Power and Energy Systems,Vol. 23, pp. 129-135,
120%, 150% and 200% of increased load of all the nodes.
2001.
[6] Das, D., Nagi, H. S., and Kothari, D. P., “ Novel method for solving radial
Therefore branch b7 has the smallest value and it remains distribution networks”, IEE Proc. C, 1994, (4), pp. 291-298.
smallest for all the load levels. Figure 4 shows the voltage [7] J.F. Chen, W. M. Wang, “ Steady state stability criteria and uniqueness of
stability indicator (VSI) at various load levels of the weakest load flow solutions for radial distribution systems”, Electric Power and
Energy Systems,Vol. 28, pp. 81-87, 1993.
branch of the system (branch b7). [8] D. Das, D.P. Kothari, A. Kalam, “ Simple and efficient method for load
solution of radial distribution networks”, Electric Power and Energy
Systems,Vol. 17, pp. 335-346, 1995.
[9] Goswami, S. K., and Basu, S. K., “ Direct solution of distribution
systems”, IEE Proc. C, 1991, 138, (1), pp. 78-88.
[10] F. Gubina and B. Strmcnik, “A simple approach to voltage stability
assessment in radial network”, IEEE Trans. on PS, Vol. 12, No. 3, 1997,
pp. 1121-1128.
[11]C.K. Chanda, A. Chakraborti,S.Dey, “Development of global voltage
security indicator(VSI) and role of SVC on it in longitudinal power
supply(LPS) system”, ELSEVIER(Electrical Power System Research
68),2004, pp.1-9.
[12] K. Vu, M.M. Begovic, D. Novosel and M.M. Saha, “Use of local
measurements to estimate voltage-stability margin”,IEEE Trans. on PS,
Vol. 14, No. 3,1999, pp. 1029-1035.
IV. CONCLUSIONS
From the above simulation result, it is observed that branch b7
(see Tables 3 and 4) has shown the lowest value, which is far
away from unity (Fig.4) and this bus can be identified as a