127/220 v
RESIDENTIAL CUSTOMERS
Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
25 4 2.5 2 30 11.43 3 x 25 (100)
50 8 5.0 4
74 11 7.4 5.5
127/220 v
RESIDENTIAL CUSTOMERS
Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
675 96 67.5 48 300 114.32 C.T.
700 100 70.0 50 (See Note 1)
725 103 72.5 51.5
750 106 75.0 53
775 110 77.5 55
800 113 80.0 56.5
825 116 82.5 58
850 120 85.0 60
875 123 87.5 61.5
900 126 90.0 63
925 130 92.5 65
950 133 95.0 66.5
127/220 v
COMMERCIAL CUSTOMERS
Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
25 6 3.0 3.6 30 11.43 3 x 25 (100)
50 10 6.0 6
55 11 6.6 6.6
127/220 v
COMMERCIAL CUSTOMERS
Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
Note 1 : Use 400 A fuses in place of 300 A fuses.
712 153 85.4 91.8 500 190.5 C.T.
725 155 87.0 93
750 160 90.0 96
775 166 93.0 99.6
800 171 96.0 102.6
825 176 99.0 105.6
850 182 102.0 109.2
875 187 105.0 112.2
893 190 107.16 114
220/380 v
RESIDENTIAL CUSTOMERS
Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
25 4 2.5 2 30 19.74 3 x 25 (100)
50 8 5.0 4
75 12 7.5 6
100 16 10.0 8
124 19 12.4 9.5
220/380 v
RESIDENTIAL CUSTOMERS
Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
931 131 93.1 65.35 200 131.6 C.T.
950 133 95.0 66.5
975 136 97.5 68
1000 140 100.0 70
1025 143 102.5 71.5
1050 146 105.0 73
1075 150 107.5 75
1100 152 110.0 76
1125 156 112.5 78
1150 160 115.0 80
1175 163 117.5 81.5
1188 164 118.8 82
220/380 v
COMMERCIAL CUSTOMERS
Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
25 6 3.0 3.6 30 19.74 3 x 25 (100)
50 10 6.0 6
75 16 9.0 9.6
92 19 11.0 11.4
220/380 v
COMMERCIAL CUSTOMERS
Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
No. Connected Amps. Range C.B. Size Customer Cable Size (Cu) , Sq. mm
1 00 29 30 1x(4x25) 1x(4x25)
2 29 72 60 1x(4x35) 1x(4x50)
Note : Customer cable size shall be determined by Engineering Units for loads exceeding 800 Amps.