TELECOM SERVICES
1. Provide secondary containment in basement for GSM services.
2. As mentioned earlier the containment cannot run in enclosed areas. Please refer
containment in GF where containment pass thru garbage and recycle areas.
3. 3 Nos. of dual RJ45 points shown in Studio apartment shall be rationalized and shall be as per the
furniture layout in apartments.
4. Provide GSM containment and racks in Main Tel rm.
5. Provide the minimum two sectional detail of Main tel rm.
6. Main tel rm shall have the raised floor.
7. Containment to GSM room from level 6 cannot pass thru the garbage room.