Multi Air Conditioner


SVC MANUAL(Exploded View)
MODEL : L8UC100BFA3
L8UC100BFE3

CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
1. Specification
Outdoor Unit L8UC100BFA3/ L8UC100BFE3
Nominal Capacity Cooling kW 3.52~28.72
(Min~Rating~Max) Btu/h 12,000~98,000
Heating kW -
Btu/h -
Nominal Input Cooling kW 2.5~9.75
(Min~Rating~Max) Heating kW -
Testing Combination Cycle 1 : LMNC122D4A0 + LMNC36GTNA0
Cycle 2 : LMNC24GTPA0 + LMNC242D5A0
Running Current(Rating) Cooling A 8.5~30.5
Heating A -
Starting Current Cooling/Heating A -
Power Supply / V / Hz 3/220/60
Power Supply Cable(Outdoor) No. x mm2 4 x 13.3 (Including Earth)
Power and Transmission Cable(Outdoor to Indoor or Outdoor to BD) No. x mm2 4 x 0.75 (Including Earth)
Power and Transmission Cable(BD to Indoor) No. x mm2 4 x 0.75 (Including Earth)
Dimensions WxHxD mm(inch) 1,280 x 1,520 x 730 (50.4 x 59.8 x 28.7)
Net Weight kg(lbs) 260 (551)
Max. Number of Connectable Indoor Units 8
Compressor (#1) Type Rotary
Qty x Model 2 x QP348RAA
Motor type Single Phase Induction Motor
Oil charge volume cc 1,130
Oil Type NM56 or SUNISO 4GSI
Compressor (#2) Type Rotary
Qty x Model 2 x QP348RAA
Motor type Single Phase Induction Motor
Oil charge volume cc 1,130
Oil type NM56 or SUNISO 4GSI
Compressor (#3) Type -
Qty x Model -
Motor type -
Oil charge volume cc -
Oil type -
Refrigerant Cycle A Charge (at 7,5m) g(oz) 4,300 (151.9)
Cycle B Charge (at 7,5m) g(oz) 4,300 (151.9)
Type R22
Control EEV / Short tube
Additional Refrigerant Charge g/m(oz/ft) 12.7 : 20(0.2) / 15.88 : 30(0.3) / 19.05 : 50(0.5)
Heat Exchanger (Rows x Column x FPI) No. (2R x 14C x 17) x 2 + (1R x 28C x 17) x 2
Defrosting Method Reversing Cycle
Fan Capacitor F/Vac 10/370
Drive Direct Drive
Discharge Direction(Side/Top) Top
Air Flow RateNo. of Fan CMM(cfm) 53x2 (3,179)
Sound Level(H/L) Sound Pressure dB(A)+3 60/60
Piping Connections Liquid(Cycle A) mm(inch) 9.52(3/8)
Gas(Cycle A) mm(inch) 19.05(3/4)
Liquid(Cycle B) mm(inch) 9.52(3/8)
Gas(Cycle B) mm(inch) 19.05(3/4)
High Pressure Gas mm(inch) -
Max. Interunit Total Piping m 110
Piping Length Main Piping m 50
Total Branch Piping m 60
Each Branch Piping m 15
Max. Elevation Outdoor Unit~Indoor Unit m 45
Difference Indoor Unit~Indoor Unit m 10
Operation Range Cooling C(F) 21 (69.8) ~ 54 (129.2)
(Outdoor) Heating C(F) -
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27C(80,6F) DB/19C(66,2F) WB Conversion Formula
- Outdoor Temperature 35C(95F) DB/24C(75,2F) WB kW = Btu/h 0.0002931
Heating: - Indoor Temperature 20C(68F) DB/15C(59F) WB
- Outdoor Temperature 7C(44,6F) DB/6C(42,8F) WB cfm = CMM 35.3
Piping Length - Interconnecting Piping Length 7,5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.

Copyright 2014 LG Electronics. Inc. All right reserved. -2-


LGE Internal Use Only
Only for training and service purposes
2. List of Functions
L8UC100BFA3
Category Function
L8UC100BFE3
Defrost / deicing X
High pressure switch X
Low pressure switch X
Phase reverse O
Reliability Phase failure protection O
Restart delay (3-minutes) O
Self diagnosis O
Soft start X
Test function O
Auto operation(Artificial intelligence) O
Convenience
Auto restart operation O
Central control(LGAP) O
CAC Network
PDI(Power Distribution Indicator) PQNUD1S00
Function
PI485 PMNFP14A0 / PMNFP14A1
Special Function Kit Low Ambient Kit X
Others Thermistor -

O : Applied X : Not applied - : No relation


Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied
with separate package
H : These safety switcher are standard or optional features defending on region & country.

Copyright 2014 LG Electronics. Inc. All right reserved. -3-


LGE Internal Use Only
Only for training and service purposes
3. Piping Diagrams
OUTDOOR UNIT

Field Piping Oil seperator


Gas (19.05)

TH4
Solenoid
TH1
Valve
Field Piping
Liquid (9.52) Heat
Check Exchanger
Check
Valve Valve

Accumulator

Compressor A Compressor B

TH2

Field Piping Oil seperator


Gas (19.05)

TH5
Field Piping Solenoid
Liquid (9.52) Valve

Heat
Check Exchanger
Check
Valve Valve

Accumulator

Refrigerant Flow
Cooling

Compressor C Compressor D

TH3

LOC. Description PCB Connector


TH1 Thermistor for outdoor air temperature CN_TH1
TH2 Thermistor for condensing temperature CN_TH1
TH3 Thermistor for condensing temperature CN_TH2
TH4 Thermistor for discharge temperature CN_TH2
TH5 Thermistor for discharge temperature CN_TH3

Copyright 2014 LG Electronics. Inc. All right reserved. -4-


LGE Internal Use Only
Only for training and service purposes
4. Wiring Diagrams
1.Wiring Diagram

2.PCB CN_PRESS1 CN_COMP


CN_FAN1
CN_FAN2
CN_SV
CN_PRESS2

CN_POWER

CN_COM
CN_TH1
CN_TH2
CN_TH3

CN_3PHASE

Copyright 2014 LG Electronics. Inc. All right reserved. -5-


LGE Internal Use Only
Only for training and service purposes
5. Exploded View

435512
435512

549610

137213A 559010 559010


546810
552113B 549610
435312
263230A
554030A Air/Defrost
CN_TH1 546810
W4811A

W4811B

552113A W4811F 263230B 554030B


Defrost/Dis
CN_TH2 552112C
552112D 552112A

W4811D
W49810C
554030D

552112B W49810E
435310 137213B
447910A
330871
559990A
447910B
554030C W49810B

W4811C
Dis
CN_TH3
W4811A
437211 263230C
W4811E
W49810A
W49810D
552203B 552117A
552114A 148000

566001 749750

W0CZZ 552203A
W6640C 552114B
552117B
552204
437212
435511
W6640A 561410A 561410B
430410
268711 649950 554160 MPS_A
W6920 559990B MPS_A S/V Coil
W6640B S/V Coil

Note) * Please ensure GCSC since the replacement parts may be changed depending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List) on GCSC.
(GCSC Website http://biz.Lgservice.com,)

Copyright 2014 LG Electronics. Inc. All right reserved. -6-


LGE Internal Use Only
Only for training and service purposes
P/NO : MFL56755302 MAY, 2014