Professional Documents
Culture Documents
Ieee 181
Ieee 181
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
An American National Standard
IEEE Recommended Practice for
Determining the Electric Power Station
Ground Potential Rise and Induced
Voltage from a Power Fault
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987
(Revision of IEEE
Std 367-1979)
Sponsor
Transmission Systems Committee
of the
IEEE Communications Society
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ISBN 0-471-61599-4
0 Copyright 1988 by
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Foreword
(This Foreword is not a part of ANSI/IEEE Std 367-1987, IEEE Recommended Practice for De-
termining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power
Fault.)
Wire-line telecommunication facilities serving electric power stations often
require that extraordinary protection measures be taken to protect against the
effects of fault-produced ground potential rise (GPR) or induced voltages, or both.
In the presence of a hostile electromagnetic environment, suitably rated pro-
tection equipment is required at the power station for personnel safety, for the
protection of the serving telecommunication facilities, and to help ensure the
desired continuity of telecommunication transmission at times of power system
faults. There is a fundamental need, therefore, to determine the appropriate
values of fault-produced GPR and induction, including considerations of their
probability and duration, to be used in developing the specifications and ratings
for the protection equipment to be used in any given application.
This guide provides information for the determination of the appropriate val-
ues of fault-produced power station GPR and induction for use in the design of
protection systems. Included are:
(1) The determination of the appropriate value of fault current to be used in
the GPR calculation;
(2) Taking into account the waveform, probability, and duration of the fault
current;
(3) The determination of inducing currents, the mutual impedance between
power and telephone facilities, and shield factors;
(4) The vectorial summation of GPR and induction;
(5) Considerations regarding the power station GPR zone of influence;
(6) Communications channel time requirements for noninterruptible services.
Members of the Inductive Coordination and Electrical Protection Subcom-
mittee who participated directly in the preparation of this standard were:
Members of the Joint High Voltage Interface Working Group (JHVIWG), the
Power Systems Communication Committee (PSCC), or other IEEE members who
also contributed directly to the development of this standard were:
P. Eichin F. B. Hunt R. M. Shier
C. L. Griffin A. Klopfenstein R. K. Sullivan
J. W. Hagge G. D. Rockefeller 0. Veraas
P. R. Hanson J . R. Shier D.R. Volzka
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Recognition of the Power System Relaying Committee in the review of Section
10 of this standard is acknowledged.
Members of the Inductive Coordination and Electrical Protection Subcom-
mittee who approved this standard on behalf of the Transmission Systems Com-
mittee of the IEEE Communications Society were:
The following persons were on the balloting committee that approved this doc-
ument for submission to the IEEE Standards Board
G. Y. R. Allen I. E. Faber E. Lee
M. J . Anna R. F. Gundrum S. Meliopoulos
G. L. Atyeo S. Guzik S. C. Merriman
W. L. Bacon C. D. Hansell H. E. Nerhood
A. H. Badger R. Harrison S. D. Overby
D. V. Batorsky D. P. Hartman C. A. Parker
G. W. Benj W. M. Haynes L. J. Perfecky
D. L. Boneau H. C. Held S. A. Potocny
J. Bringham L. M. Himmel M. A. Street
G . E. Burridge W. W. Hines B. Szadodos
D. P. Callaghan F. B. Hunt J . M. Thorson
L. S. Chmielcwicz P. Jackson M. S. Tibensky
W. Dabisza A. K. Knowles A. R. Valentino
L. A. Day J . F. Laidig S. D. Vasdev
D. A. Duckett S. L. Larsen 0. Wanaselja
I. N. El-Behery A. B. Wilkens
When the IEEE Standards Board approved this standard on June 11, 1987, it
had the following membership:
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
IEEE Standards documents are developed within the Technical Com-
mittees of the IEEE Societies and the Standards Coordinating Committees
of the IEEE Standards Board. Members of the committees serve volun-
tarily and without compensation. They are not necessarily members of the
Institute. The standards developed within IEEE represent a consensus of
the broad expertise on the subject within the Institute as well as those
activities outside of IEEE which have expressed an interest in participating
in the development of the standard.
Use of an IEEE Standard is wholly voluntary. The existence of an IEEE
Standard does not imply that there are no other ways to produce, test,
measure, purchase, market, or provide other goods and services related to
the scope of the IEEE Standard. Furthermore, the viewpoint expressed at
the time a standard is approved and issued is subject to change brought
about through developments in the state of the art and comments received
from users of the standard. Every IEEE Standard is subjected to review at
least once every five years for revision or reaffirmation. When a document
is more than five years old, and has not been reaffirmed, it is reasonable to
conclude that its contents, although still of some value, do not wholly
reflect the present state of the art. Users are cautioned to check to deter-
mine that they have the latest edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any inter-
ested party, regardless of membership affiliation with IEEE. Suggestions
for changes in documents should be in the form of a proposed change of
text, together with appropriate supporting comments.
Interpretations: Occasionallyquestions may arise regarding the meaning
of portions of standards as they relate to specific applications. When the
need for interpretations is brought to the attention of IEEE, the Institute
will initiate action to prepare appropriate responses. Since IEEE Standards
represent a consensus of all concerned interests, it is important to ensure
that any interpretation has also received the concurrence of a balance of
interests. For this reason IEEE and the members of its technical commit-
tees are not able to provide an instant response to interpretation requests
except in those cases where the matter has previously received formal
considerat ion.
Comments on standards and requests for interpretations should be
addressed to:
Secretary, IEEE Standards Board
345 East 47th Street
New York, NY 10017
USA
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Contents
SECTION PAGE
1. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.1 Wire-Line Telecommunication Circuits ...................... 15
2.2 Faults on Power Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.3 Power Station Ground Impedance to Remote Earth ........... 16
2.4 Establishing Net Fault Current Values ...................... 18
2.5 Division of Fault Current ................................... 18
2.6 Calculating the Inducing Current ........................... 19
2.7 Ground Potential Rise (GPR) ............................... 19
2.8 Sources of Fault and Inducing Current Information and
Impedance to Remote Earth Information. and Related
Responsibilities of Power Utilities and Serving
Telecommunication Utilities ................................ 19
2.9 Transient Voltages Resulting from Power System Operation . . 20
2.10 The Types of Wire-Line Telecommunication Circuits Usually
Requested for Electric Power Stations as Defined by Power
Utilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.11 Service Types and Performance Objectives for
Telecommunications Services Provided at Power Stations as
Defined in ANSI/IEEE Std 487-1980 [51..................... 21
2.12 Summary of Introduction ................................... 21
3 . Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4. References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5. Electric Power Station Ground Potential Rise (GPR) . . . . . . . . . . . . . . . . 27
5.1 Statement of the Problem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.2 Determination of Appropriate Symmetrical GPR . . . . . . . . . . . . . 27
5.3 Duration of the Fault and its Relationship to Wire-Line
Telecommunication Requirements for Power System
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.4 Extraordinary Possibilities .................................. 51
5.5 Example of GPR Calculations and Volt Time Area Calculation 52
5.6 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
6. Calculation of Electromagnetic Induction Under Power Fault
Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
6.1 Statement of the Problem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
6.2 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
6.3 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
6.4 Example 1: Uniform Exposure .............................. 71
6.5 Evaluation of Mutual Impedance ............................ 74
6.6 Calculation of Mutual Impedance (Per Unit Length) . . . . . . . . . 77
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
SECTION PAGE
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
SECTION PAGE
FIGURES
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
FIGURES PAGE
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
TABLES PAGE
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
An American National Standard
1. Scope
13
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
2. Introduction
2.2 Faults on Power Systems. Power system faults can occur at any point on
a power line or in any type of power station at any voltage level. Each location
has different fault characteristics. Faults can be single line-to-ground (L-G), phase-
to-phase, open-phase, double line-to-ground (2L-G), or three-phase and can prog-
ress from one to the other. These faults can theoretically be initiated at any
point on the voltage or current waveform and the resulting fault currents can
attain values even higher than 100 kA. The resulting GPR or LI, or both, on
adjacent telecommunication facilities can be minimal or quite high. Values of
GPR as high as 25 kV rms are possible under unusual circumstances; however,
the usual values are less than 10 kV. The waveform of the GPR voltage can
vary from the symmetrical to the completely offset, as described in Section 4.
The decay time of the direct-current component (dc offset) of the fault current
may have a duration of several cycles.
Fault-current studies should be re-evaluated at least every five years and more
often, if required, due to the ever-increasing MVA capacity or configuration of
these power systems.
15
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
2.3 Power Station Ground Impedance to Remote Earth. The power station
ground grid impedance to remote earth, ZSGT,is required in the determination
of the inducing current and is used in both GPR and LI calculations.
The total power station ground grid impedance to remote earth, ZsGT,is the
total impedance between the power station ground and remote earth and con-
sists of the parallel combination of
(1) Power station ground grid impedance itself, ZSc.
(2) Combined impedance, Z L , of all high-voltage (HV) and low-voltage (LV)
ladder networks. These ladder networks are composed of overhead ground wires
or neutrals with multiple tower or pole footing grounds.
(3) Incidental impedances, 2,-rails, pipes, etc.
The total power station ground grid impedance, ZSGT,can be obtained by either
of two methods: Calculations based on measurement of earth resistivity only
(Method A); determinations based upon direct measurements (Method B).
The choice of method will depend upon a variety of circumstances as discussed
in the following.
Method A. Several mathematical models and computer methods are used by
power utilities to derive the station ground grid impedance, ZSG.For example,
a formula derived from the ANSI/IEEE Std 80-1986 [31, Eq 39, and good for
homogenous earth where the depth of burial is less than 0.25 m, is
zSc= p (i i)
+ (ohms)
where
pearth resistivity, in ohm-meters (obtained by field measurements)
=
requivalent radius of a power station ground grid (radius of a circle having
=
the same area as the station ground grid), in meters
L = total length of buried horizontal ground conductors, in meters
In GPR studies, calculations of the impedance of all connected overhead ground
wireltower ladder networks are required.
The impedance of a ladder for sufficiently long lines is
,
2, = -
2s 2
+ J: - +2,2,
16
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
17
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
SM 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
conductors are used for current injection. Similarly, the test voltages used in
Method B are usually too low to flashover the insulators of insulated overhead
ground wires; hence, the resulting GPR values will be higher (more conserva-
tive) where insulated overhead ground wire systems are in place because such
conductors do not form part of the measured circuit.
As discussed in a later section of this guide, the determination of the location
of a line fault producing the worst GPR requires many of the same calculations
as are used in Method A, so that Method A may be preferable including the
determination of worst-case line fault locations.
With the wide variation of conditions at different power stations, no one method
of determining ZsGT is best for all stations. Each power utility or substation
owner should choose the method or methods best suited to its needs and capa-
bilities. Larger power utilities, having more specialized engineering staffs and
adequate computer capabilities, may routinely use Method A supplemented by
Method B for special situations. Smaller power utilities and private substation
owners may find that Method B is more suitable considering their staff and
equipments. The relative costs of obtaining accurate measurements in Method
B, of purchasing and operating the necessary computers for Method A, and of
purchasing and operating any resulting telecommunication protection equip-
ment are all important considerations.
2.4 Establishing Net Fault Current Values. Power utilities, in their calcu-
lations of zero-sequencefault currents, usually do not take into account the con-
ductive effects of the transmission and distribution line grounding network
impedances (comprising overhead ground wires, neutrals, transmission tower
and distribution pole footing impedances, counterpoises, and station ground
impedances).
The net fault currents should be recalculated by including the effects of the
impedances of power line ladder networks, incidental paths (pipes, rails, etc),
telecommunications cable grounds, station ground impedance, and a judicious
value of fault impedance.
Additional reduction of the induced voltages caused by the net fault current
can be achieved by application of various shielding mechanisms available.
Care should be taken in recalculating positive sequence fault currents to in-
clude phase shifts in certain transformer windings. Substantial reduction of the
net fault current can thus be achieved. The amount of reduction will depend on
earth resistivity, towerlpole footing impedances, type and material of overhead
ground wire or neutral conductors, span length, transmission or distribution line
length, and whether or not overhead ground wire(s) are connected to the station
ground grid and whether or not counterpoises and bonds are present.
2.5 Division of Fault Current. Generally, fault current will, a t the point of
fault, divide between the metallic return paths and earth. The metallic return
paths will include overhead ground wires, neutrals, counterpoises, bonds, sta-
tion ground grids, commonly grounded telecommunication circuits, and inciden-
tal grounds such as rail and metallic pipes.
There are many factors controlling the division of power system fault current
18
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
into its several paths, and calculations are usually quite complex. The deter-
mination of an accurate division of fault current requires knowledge of the earth
return path impedance and the ground system including all other return path
impedances, as will be shown in Section 5.
2.6 Calculating the Inducing Current. The purpose for calculating inducing
current flowing in each transmission or distribution circuit connected to the
power station under study is twofold:
(1) To determine the amount of fault current induced in each overhead ground
wire or neutral. These currents do not cause any GPR.
(2) To determine the amount of voltage induction in nearby telecommuni-
cation circuit.
The inducing current which is used to determine the shielding action of over-
head ground wires is also used to determine the longitudinally induced voltage
in telecommunication networks.
NOTE: The terms overhead ground wire(s), shield wire(& static wire(& or skywire(s) are
synonymous.
2.7 Ground Potential Rise (GPR). This is essentially the product of:
(1) The total ground grid impedance (ZSGT)at the power system fundamental
frequency to a true or remote earthing point (must be outside the zone of in-
fluence of the GPR), and
(2) The total net fault current that flows through the ground grid impedance.
These values should be determined by the electric power utility; reference can
be made to ANSI/IEEE Std 80-1986 [31 and ANSI/IEEE Std 81-1983 E41.
2.8 Sources of Fault and Inducing Current Information and Impedance
to Remote Earth Information and Related Responsibilities of Power Util-
ities and Serving Telecommunication Utilities. In some power utilities the
necessary fault current information can be obtained from a system planning or
protective relaying group. The group responsible for the determination of sta-
tion ground grid impedance will usually be different from the group responsible
for determining an overall impedance to a remote earthing point including any
telecommunications cable shields. Serving telecommunication utilities may be
involved in this latter determination. In any event, the power utility is essen-
tially responsible for assessing the validity of these parameters and to judge the
assessment of the assumed or appropriate net fault current value to be used
in the GPR calculation, its waveform and duration, and the magnitude of the
inducing current. The responsibility for assessing the magnitude of the GPR,
induced voltage, and their sum is that of the power utility with the cooperation
of the associated telecommunication utility.
Since the electric power utility system originates the fault-produced interfer-
ing voltages into the wire-line telecommunications facilities serving the power
station, the power utility is responsible for the accurate determination of GPR
and induced voltage by considering
(1) The impedance of the power station ground grid to remote earth.
(2) The earth return fault current (its waveform and duration) that flows
through the grid and produces the GPR.
19
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
(3) The effective X / R ratio of the power system at the fault location.
(4)The extent of the power station zone of influence along the route of the
serving telecommunications cable.
(5) Fault current values and maps of the relevant power feed routes as re-
quired by a serving telecommunications utility for the computation of fault-pro-
duced induction on the serving telecommunications cables.
(6) The required non-interruptible channel time should be the responsibility
of the power utility relay engineer.
Since the telecommunications facilities extend into the power station to pro-
vide telecommunications service, the power utility or substation owner should
advise a serving telecommunications utility of the fault-produced environment.
This provision of fault-related data applies even to those cases in which the
power utility or substation owner, rather than the serving telecommunications
utility, provides the telecommunications protection equipment at the power sta-
tion.
The telecommunications company and the power utility should cooperate closely
in determining the sum of the GPR and induced voltage. Obviously a great deal
of cooperation and trust should exist between the power utility or substation
owner and the serving telecommunication company representatives, as well as
with individuals within these organizations, in order to satisfactorily determine
the nature of the hostile environment of the power station.
20
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
21
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
(3) The characteristics (impedances, inductances, and capacitances) of the
power system and related time constants.
(4) The characteristics (impedance, susceptibility, etc) of the affected wire-
line telecommunication systems.
(5) The determination of the value of impedance to remote or true earth.
(6) The determination of appropriate values of GPR and LI and their sum-
mation and duration under varying conditions.
(7) The application of probability and mitigating factors to provide more re-
alistic and acceptable values consistent with required reliability and safety, which
could affect economic decisions and tradeoffs.
(8) The zone of influence of the GPR.
(9) The rise, duration, and decay of both symmetric and asymmetric fault
currents.
(10) The time requirements for telecommunication channels when used for
protective relaying.
(11) The effects of high-voltage, direct-current (HVDC), telluric, or auroral
currents, or all, as well as dc power system neutral currents that can affect wire-
line facilities or protective devices.
(12) A few typical examples of GPR and induced voltage calculations.
22
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
3. Definitions
23
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
24
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
4. References
ANSI/IEEE publications can be obtained from the Sales Department, American National Stan-
dards Institute, 1430 Broadway, New York, NY 10018, or from the Service Center, Institute of Elec-
trical and Electronics Engineers, 445 Hoes Lane, PO Box 1331, Piscataway, NJ 08855-1331.
25
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
[ l l l OLSEN, R. G. and JAFFA, K. C. Electromagnetic Coupling from Power
Lines and Magnetic Field Safety Analysis, ZEEE Transactions on Power Ap-
paratus and Systems, Vol PAS-103, No 12, Dec 1984, pp 3595-3607.
[121 OLSEN, R. G. and PANKASKIE, T. A. On the Exact, Carson and Image
Theories for Wires at or Above the Earths Interface, ZEEE Transactions on Power
Apparatus and Systems, Vol PAS-102, Apr 1983, pp 769-778.
[131 PARKER, Jr., J. C. Hand Held Calculator Program for Evaluating Exter-
nal Mutual Impedance, Bell Laboratories Technical Memorandum, Feb 1980.
26
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
5. Electrical Power Station
Ground Potential Rise (GPR)
27
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
shunt capacitors, frequency changers, etc. The GPR is equal to the product of
the station ground grid impedance and that portion of the total fault current
that flows through it. Also, the GPR is equal to the product of the alternate
path impedance and that portion of the conductively coupled fault current that
flows through it. The volt-time area of GPR to be determined is given in volt-
seconds for the duration of the fault.
5.2.2 Since the station ground grid impedance to remote earth is needed to
calculate the GPR, the ground grid impedance must be obtained either by the
calculation or measurement methods described in 2.3.
5.2.3 A study is made of various ground faults in order to determine that the
one that produces the highest GPR and volt-second area (see 5.5.4).The station
ground grid impedance as well as power overhead ground wire and telecom-
munication grounding networks tend to limit the fault current and should be
included in the calculations.
5.2.4 In the study of 5.2.3, the power system generators are usually repre-
sented by their subtransient reactances. As the time progresses until fault clear-
ing, their reactances increase to their transient values and possibly to the steady-
state synchronous reactances. This change can be neglected in most cases and
the initial subtransient reactance retained. All significant impedances should
be included, such as for transmission lines.
5.2.5 The initial magnitude of the dc offset should be calculated as a function
of the voltage magnitude a t the time the fault is initiated. The highest dc offset
occurs when the change in current, from just before fault initiation to just after
fault initiation, is maximum. Since the alternating current cannot change state
instantaneously due to the inductance of the circuit, initially the dc offset coun-
terbalances the change in alternating current. The dc offset then decreases to
zero at a rate determined from the effective reactance-impedance ratio ( X / R
eff) of the power circuit at the fault. With a highly inductive circuit the max-
imum dc offset will occur when the fault is initiated close to voltage zero, a
condition that is most unlikely for faults resulting from insulation breakdown.
Also, a highly inductive circuit will have a prolonged dc offset. For the appli-
cation of a multiplication factor for dc offset, refer to Section 10.
5.2.6 There are four possible combinations of circumstances involving power
faults that should be considered in determining the worst-case GPR a t a power
station. With reference to Fig 1, four different ground fault conditions causing
GPR at the local power station (local ground source) will be described. For sim-
plicity, a single-circuit three-phase power line with two ground sources is illus-
trated. A ground source at a power station is a component that can supply cur-
rent to a fault and to which current returns by way of the earth and all available
metallic conducting paths. Ground sources include wye-connected transformers
with grounded neutrals, grounded autotransformers, and grounded generators.
(1) Figure l(a) illustrates the situation involving a fault to the local ground
grid where the remote source provides a greater amount of fault current than
the local source (the remote source predominates). In this case, the current
supplied by the local source simply circulates on the metallic grid (it does not
flow into the earth), therefore not producing any GPR. However, the relatively
large current from the remote source returns to that source by way of the earth
28
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
------
overhead
............
. or other external
grounded conductors
J:TI:Tz
------
wires
--
LOCAL
GROUND
SOURCE
-
- --1
. 1
*
-
-.
*=4
1 1
* -
-
GROUND
SOURCE
- .
G
LOCAL F -2 wires : - : * I .
REMOTE
GROUND
SOURCE SOURCE
-
-L -+
(d) Remote Source Predominates
NOTES: (1) For simplicity, a single line with only two ground sources is illustrated.
(2) Overhead ground wires can be insulated from the towers, resulting in different values.
(3) F-fault location.
Fig 1
Different Combinations of GPR Occurring at the Local Ground Source
29
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
and all available metallic conductors, thereby producing a relatively large GPR
at the local power station.
(2) Figure l(b) illustrates the situation involving a line fault to remote earth
(the fault location is outside the zone of influence of the local power station)
where the local source provides a greater amount of fault current than the re-
mote source (the local source predominates). In this case, the fault currents
return to their respective sources by way of the earth and all available con-
ductors. Since the local source supplies the high fault current, the GPR produced
at the local power station will be relatively large.
(3) Figure l(c) illustrates the situation involving a fault to the local ground
grid where the local ground source provides a greater amount of fault current
than the remote source (the local source predominates).The current supplied
by the local source does not flow into the earth and does not produce any GPR.
The relatively small current from the remote source returns to that source by
way of the earth and all variable metallic conductors, thereby producing a rel-
atively small GPR at the local station.
(4) Figure l(d) illustrates the situation involving a line fault to remote earth
where the remote source provides a greater amount of fault current than the
local source (the remote source predominates). The fault currents return to
their respective sources by way of the earth and all available conductors. How-
ever, since the local source provides a relatively small current, this GPR pro-
duced at the local power station will be relatively small.
NOTES (1)In the above examples, the cases described in 5.2.6 (1) and 5.2.6 (2) resulted in the
largest GPRs at the local power station. However, all four fault conditions must be evaluated to
determine the worst-case GPR at the power station of interest.
(2) Figure 1 shows a typical system in which the externally grounded metallic conductors (in-
cluding overhead ground wires) are indicated by dotted lines. Overhead ground wire systems are
constructed in various configurations and may be either directly bonded to the transmission line
towers or may be insulated from the towers. In addition, overhead ground wire systems may be
directly connected to the station ground grid or may be terminated one or more spans out from the
station. The externally grounded metallic conductors, including grounded wires, provide a n alter-
nate path for the fault current, reducing the earth return portion of the total fault current to as
little as 40% or less of the total fault current.
(3) Power stations without ground sources (for example, switchyards with transformers having
only delta connections) do not experience GPR from line faults occurring off the station grid when
the power line overhead ground wire is not connected to the station ground grid. However, such
stations do experience a GPR if a fault occurs directly to the grid, system connections on the other
end permitting, for example, the transformer at the other end has a grounded winding.
30
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
pacitors, frequency changers, etc), then at the voltage level for which the fault
current study is presently being examined, the bus fault will usually produce a
worse GPR than the line fault.
(2) If the reverse is true, that is, the vectorial sum of the line contributions
is smaller than the local ground source current sum, the line fault will produce
a greater GPR. This is because the local ground current-which in the bus fault
case merely circulates through the faulted transformer winding, the station ground
bus, and the fault impedance (if included)-will, in the case of the line fault,
return partially through the station ground impedance adding to the GPR caused
previously by the line current contribution.
Having determined the worst-fault location (bus versus out on the line), to
pick up that fault current study that shows the highest fault current is not ap-
propriate. Variances between grounding networks of lines with the various volt-
age levels may, for instance, cause the study showing lower zero-sequence fault
currents to result in a GPR greater than that caused by the higher currents.
Instead, all faults should be investigated for fault locations as determined above.
31
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
a function of voltage levels on which they occur and other parameters, see ref-
erence [91.
5.2.9 Notes on Modelling of Ladder Networks of Long and Short Lines.
As will become clear later, GPR work requires modelling of transmission and
multigrounded distribution line grounding networks. This becomes important
when determining the amount of fault current carried away from the fault by
the line's grounding network, conductively, by first calculating its impedance to
remote earth. This determines the amount of the GPR-causing current.
A modified transmission line theory can be used by modelling the ladder net-
works by the distributed parameter method. Care must be taken in correcting
the classical hyperbolic transmission line equations due to the fact that the se-
ries (overhead ground wire self-impedance) and shunt (tower footing impedance)
components of the overhead ground wire-tower ladder network are indeed very
discrete components. This modification should enable one to transform these
discrete components into a set of distributed ladder network parameters. This,
however, can only be done with lines sufficiently long. If the line is short, one
must resort to the nodal and mesh analysis which may require considerable
computing time, particularly with large R-0-Ws with a multitude of lines and
overhead ground wires. The presence of counterpoises and bonds can be ex-
tremely complicating, but should be considered.
5.2.10 H v Bus Fault GPR. By simulating the L-G and three-phase bus faults,
power utilities can generally calculate resulting zero- and positive-sequence fault
currents as shown in Fig 2,
Fig 2
L-G and Three-phase Fault Simulation
STATION 1
1 HV BUS
IT
-
- + -11 A -11 TRANSFORMER
TRANSFORMER ZERO / 111 STATION "S" +
SEQUENCE EQUIVALENT
LV BUS
R-0-W 2
STATION 2
31~0(1)2-)
lA1('1)2
32
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
where
3 1 A o ( J ) r = zero-sequence current in the J t h circuit on the rth R-0-W
ZA1Wr = positive-sequence currents in the J t h circuit on the rth R-0-W
31AOT= total zero-sequence fault current
I,,, = total positive-sequence fault current
IT = transformer neutral, generator, etc, current
and
NOTE: The fault currents shown in Fig 2 are the per circuit (as opposed to per phase) quantities;
that is, all three-phase currents are concentrated in a single equivalent conductor and, in the case
of zero-sequence currents, include the inductive effect of ground wires. To account for the conductive
effects of the presence of overhead ground wires, station ground impedance, incidental ground path
impedances, and phase wire zero-sequence impedances, the total zero-sequence current (3ZAOT)must
be reduced accordingly. A new circuit, valid for electrically long lines, is formed as shown in Fig 3.
then
V,= prefault voltage
2, = zero-sequence self-impedance of the phase conductor, between the source
and fault locations
Zsc = station ground impedance
ZxT = parallel combination of impedance of all ladder networks Z L and the
incidental impedances Zi
2, = system impedance
2, = fault impedance
The system impedance (2,) is the impedance seen between the fault termi-
nals, as determined by the power utility in fault calculations, and includes the
zero-sequence impedances of lines, transformers, etc.
The new zero-sequence fault current (3IAON) resulting from Fig 3 includes the
conductive effects of grounding. This new interfering current, however, must be
further reduced by the amount it induces into the overhead ground wires of the
tower (or pole) line that carries the faulted circuit. Because of the unequal spac-
ings between the phase wires and neutrals and because each phase carries dif-
ferent currents both in amplitude and phase (faulted phase, generally, depend-
ing on the corresponding positive-sequence current, carries the current toward
the fault location, whereas the remaining two unfaulted phases generally carry
currents away from the fault location), unequal currents are induced in the over-
head ground wires from each phase of the faulted circuit. Overhead ground wire
currents induced from the faulted phase will act as a shield, but those induced
from the unfaulted phases will subtract from the shielding current and act as
an antishield, as depicted in Fig 4.
33
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
I
ZSG
1+ REMOTE EARTH
-
REMOTE EARTH
Fig 3
Circuit for Total Zero-Sequence Current (3ZAOT)
Reduction
IC0
c-
1 - IEO
UN FAU LTE D
PHASES
I
- )A0
A
FAULTED
PHASE
INDUCED OVERHEAD
GROUND WIRE CURRENTS
Fig 4
Power Line Shielding
34
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
Fig 5
Circuit for L-G and Three-phase Fault Analysis
t
161 (112
POSITIVE SEQUENCE
-+ZERO SEQUENCE
35
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
S M 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
positive-sequence currents in Fig 5(a) have a superscript (' ) because these cur-
rents differ from those in Fig 5(b) since the voltage sources Vpl and Vp2 drive
two different circuits, 5(a) and 5(b).
Here
Next, mutual impedances between overhead ground wire(s) and each phase
conductor on the faulted R-O-W should be obtained by the use of the simplified
form of Carson's equation [71:
36
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
2160 -J'f
2, = 0.00159f + j0.004657 f log,, (R/mi) (Eq 16)
dab
where
f = frequency, in hertz
p = earth resistivity, in ohm-meters
dab = distance between each phase and overhead ground wire(s), in feet
2160 d' I-
f
2, = r, + 0.00159f + j0.004657 f log,, GMR
(W-4 (Eq 17)
where
r, = conductor impedance, in ohms/mile
GMR = geometric mean radius of the conductor, in feet
The total zero-sequence current induced in each overhead ground wire (Isk)is
the sum of the products of each phase current and the coupling factor r,
(Eq 18)
Conversely, for the current ZG flowing in the earth due to induction, the cou-
pling factor (1 - r) is
2,
(1 - r) = 1 - - (Eq 19)
2,
To assess the conductive effects, 2, must be determined next. 2, is defined as
an impedance looking into an overhead ground wire-tower (or neutral pole) lad-
der network from the fault terminals. The determination of 2, is complex and
can be done by either discrete or distributed parameter methods. In the case of
one electrically long line conforming to the inequality,
L W P > 2 (Eq 20)
where
L = length of the line, in miles
2, = series impedance of the overhead ground wires, in ohms/span
2, = tower (pole) footing impedance, in ohms/span
37
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
then
In this example, two such ladder network impedances, Z,, and Z X 2 are
, paral-
leled to obtain ZrT as in Fig 3. In the final analysis, the following situation
applies (Fig 6):
In Fig 6 it can be seen that for the fault on the HV bus (the situation is
reversible) the transformer ground current IT circulates through the faulted
winding and the fault itself. For simplicity it can be assumed that it does not
enter ground. The GPR causing zero-sequence current ZGpR is
ICPR = I G + ISKlc ISKZc (Eq 22)
and also
IGpR = 31,4077 - (IsKi +IT)
This current will enter the following impedance combination:
Fig 6
Complete Faulted Circuit
TO STATION 2
4
- ~ I A 12
o(~
FAULTED CIRCUIT
---
REMOTE EARTH
STAT10N
GROUND BUS
I S K ~= I s K ~+~I s K ~ ~ IsK,, and ISKzt = induced overhead ground wire fault currents (do not enter
ground)
ISKC = ISKlc + ISK2 I s K l c and I S K z c = conducted overhead ground wire fault currents (do not
enter grounding network)
38
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
(Eq 23)
5.2.11 Low Side Bus and Line Fault GPR. Theoretically, LV faults can be
handled in precisely the same manner as the HV faults. All differences between
HV and LV side construction (transformer connections, line conductors, length,
pole footing impedance, etc) will reflect in the calculation of zero- and positive-
sequence LV L-G and balanced fault currents. As opposed to HV systems, which
usually carry overhead ground wires, some LV lines, delta or wye connected,
carry no neutrals.
When neutrals are present on LV systems, LV bus fault calculations follow
the same method described in 5.2.10 and LV line faults will be the same as HV
line fault calculations, to be described later.
When neutrals are not present on LV system, both LV bus and line fault GPR
can be calculated using simplified method shown in 5.2.10. For a LV bus fault,
ZL will consist of the parallel combination of impedances-to-remote earth of all
HV overhead ground wire-tower ladder networks only. The rest of the method
still applies.
For LV line faults, assuming a radial LV line, a single fault infeed can be
assumed if no generation exists on the load side of the line. This assumption is
correct for most cases but it should be pointed out that, for instance, a large
induction motor can become a zero-sequence current generator at the instant of
the fault, due to the inertia of the rotor and the mechanical load. If this can be
neglected, though, the worst fault then occurs outside and near the station. The
HV bus fault method is then modified by inserting, in series with Z,, the self-
impedance of the faulted phase conductor, and inserting a faulted pole footing
impedance in series with 2, in Fig 3.
The methods described above can be used for hand calculation and estimation
purposes only.
For a more complicated network, that is, high number of rights-of-way, cir-
cuits, transformers, ground sources, and short lines such as could be found be-
tween generating and switching stations, hand calculations cannot be used for-
either exact or approximate solutions; a computer program must be used. In
such a program, the theoretical approach should include the effect of other forms
of grounding, such as rails, pipes, etc; the effect of the length of lines; the effect
of positive-sequence current phase shift in certain transformer windings; etc.
For the theoretical basis of such a program, see [71.
5.2.12 HV Line Fault GPR. The preceding theory is a simplified one. It can,
however, be used with confidence to obtain results within some 10-30% of true
figures, for estimating purposes.
The present topic is, by contrast, much more complicated not only by the com-
plexity of the problem itself, but also by the vast amount of data input required.
No hand calculation methods exist.
39
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
When a particular L-G HV bus fault current study indicates that the worst
fault is the line fault, there is no easy way to determine the exact location of
that fault. The only definite condition is that the fault will be at any one tower
carrying circuit(s) connected to the bus at the same voltage level for which the
aforementioned bus fault current study was produced. This necessitates placing
a fault at each tower for each circuit of each tower line of each R-0-W carrying
such circuit(s1 and calculating the GPR at the station under study for each of
these faults. Because of the tremendous multitude of line faults to be examined
(for complex stations with a number of R-0-Ws and long lines, the number of
faults to be examined may reach into the hundreds), to ask the utilitys planning
section for so many fault current studies would be impractical. A selective com-
puter program calculating GPR for line faults at all voltage levels must contain
its own short-circuit subprogram. Both positive- and zero-sequence short-circuit
current study sets will be required.
The system to be analyzed is modelled as a network consisting of left and
right voltage sources with impedances between them. The faulted R-0-W is the
path followed by the faulted circuit. A fault is defined to occur at a transmission
tower between a left source and a right source. Ground currents will then flow
through the ground network made up of overhead ground wires, towers, coun-
terpoises, and bond conductors. Because of inductive effects, all unfaulted cir-
cuits along the faulted R-0-W are also affected by the fault. The ground currents
and the conductor currents are calculated using symmetrical components. This
technique requires calculation or knowledge of the sequence impedances in the
system under study. It is not, obviously, within the scope of this document to
provide the basis for a computer program capable of doing this. See [71 for this
information.
5.2.13 Example 1: HV Bus Fault and LV Bus and Line Fault
5.2.13.1 System Data. The station with ZSG = 0.5 R shown in Fig 8 has
three R-0-Ws entering it:
(1) R-0-W 1 carries a single circuit 230 kV transmission line with conductor
configuration, as shown in Fig 7. The following data apply:
(a) Phase conductors: 1307.4 AS28119
R + jX = 0.0797 + j0.3720 R/mi
diameter = 1.34 in
(b) Overhead ground wires: 7 AWG No8
R + jX = 2.354 + j.644 R/mi
diameter = 0.385 in
(c) Tower footing impedance: 80 R
(d) Earth resistivity: 1000 R . m
(e) Average span: 1014 f t
(f) Line length: 7 mi
(2) R-0-W 2 data is the same as for R-0-W 1. Line length: 5 mi
(3) R-0-W 3 carries a three-phase 44 kV delta-connected circuit. In Figs 8
and 9, two fault current studies-one for the 230 kV and the other for the 44
kV bus -fault currents are shown. Both L-G and symmetrical fault currents
were calculated. The future fault condition is assumed.
40
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
Fig 7
R-0-W 1 Conductor Configuration
41
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
V
230 kV BUS
I1 "y"'
"r OfJu
-1 -
0.0078 0.0078 OPU'
-11.0382 kA -11.0382 kA 44 kV BUS 1 44 kV BUS
T
OA R-0-W 3
230 kV BUS
0.2100 0.2009
-13.8085 PU -13.7936 PU
- 44 kV BUS
-
-
t
OA
R-0-W 3
42
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
An intelligent choice of the faulted phase must be made to obtain the worst
condition.
Generally, the phase farthest from the overhead ground wire (or neutral) should
be faulted. This implies a lower mutual impedance between the phase and neu-
tral, causing lower shielding current in thp neutral forcing more current into
the ground. Since phase C is faulted, zero-sequence fault current, IC(lll,flows
in it toward this fault. Currents in the two unfaulted phases A and B are smaller
and generally flow in the direction opposite to that of the faulted phase, that
is, away from the fault, providing a shielding action and ultimately reducing
the GPR. However, in some cases the reverse may be true, thereby producing
antishielding. The induced overhead ground wire currents are calculated as Eq 18:
&~(l)~
= -224.57 + j222.288A
= -336.383 + j248.635A
Is~(2)~
Since the induced overhead ground wire current flows in the direction oppo-
site to that of the faulted phase, it provides shielding action as well. The ratio
of overhead ground wire to line current (shielding factor) is calculated as
(-0.030904 - j0.024471).
Inequality (Eq 20) shows that the line becomes electrically infinite after the
31st span. Therefore, Eq 21 can be used and will result in a overhead ground
wire-tower ladder network impedance of Z,(1) = 4.9536 + j2.0716 R.
(2) R-O-W 2. Similar to R-O-W 1 calculations:
3ZA0(1)2= 581.9 - j3116.2A
IAl(1)z = 1.774 - j15.64pu
43
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
Mutual impedances between each phase conductor and overhead ground wires
1 and 2 are the same for R-0-W 1. The same is true for the 2,(2). Phase con-
ductor currents are calculated as:
ZA(1l2= -7.919 + j404.735A
IB(1I2= -7.919 + j404.735A
= 597.737 - j3925.671A
The induced overhead ground wire currents are:
ZsK(1l2= -398.117 + j390.386A
ZSK(U2= -544.745 + j432.182A
The ratio of overhead ground wire to line current is (-0.30967 - j0.24474)
and the number of spans required for the electrically infinite overhead ground
wire-tower ladder network is 31.The residual fault current ZGpR (Eq 22) can be
shown to be ZGpR = -528.12 - j3674.21 A and GPR (Eq 24) will be 1580.88 V
where ZGpR = 0.43 + j0.03 R calculated with Zsc = 0.5 0.
5.2.13.4.2 44 kV Bus Fault. All of the 44 kV bus fault, 31AOT, is gen-
erated locally, resulting in a negligible GPR.
5.2.13.4.3 44 kV Line Fault. Because the R-0-W 3 carries a 3 wire (no
neutral) circuit, the circuit of Fig 10 can be used to calculate the 44 kV line
fault as follows:
(1) Prefault Voltage V, = 46 000 V
NOTE: The prefault voltage is higher than the operating voltage of 44 kV because the neutral
voltage undergoes a shift during the initiation of the fault.
(2) 44 kV line zero-sequence current contribution [Fig 10(a)l is 3IAO(&
= 0 A.
The low side (LS) transformer contribution is IT = 855 - j16 911 A; the total
low side fault current is 31AOT = 855 - j16 911 A; and the 230 kV zero-sequence
current contribution is IN = 0 A. The system impedance a t the faulted 44 kV
(bus) terminal is 2, = 0.11 + j1.91 0. The calculated LS line fault GPR is 5620.64
V. As a matter of interest, the fault impedance, 2, (Fig 31, of 5 R will reduce
the GPR to 1929.2 V and illustrates the need to include the appropriate value
of the fault impedance in some cases.
5.2.14 Example 2: HV Line Fault
5.2.14.1 System Data. The generating station (Fig 10) has three voltage
levels:
(1) R-0-W 1 has a tower-line carrying a single 230 kV circuit with 795.0 ACSR
26/7 conductors and two 3/8 steel overhead ground wires. The tower-footing
impedance is 79.57R and the average span is 924 ft. Earth resistivity, assumed
uniform, is 1000 R * m.
(2)R-0-W 2 has a tower-line carrying four 230 kV circuits with 795.0 ACSR
26/7 conductors and four 3/8 steel overhead ground wires. The average span
and the earth resistivity are the same as in R-0-W 1.
(3) The 44 kV bus is connected to the 230 kV bus by means of a A =
=
5
connected transformer. A 3-wire (no neutral) 44 kV circuit is on R-0-W 3.
44
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
IL = cr J
(31A0(J)r)= 3IAOT
= 356.9 - j1133.3 A
45
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
k . -j938.11
1 1 A
A
I1
4:
4&
,"
-
-
11 1L c-
230 kV
kVB
I1
BUS
US
545 - j5072 A
c-
I 10.1 - 1650 A
44 kV BUS
-YkVBU -
-
2,
26.1 - j406.7 A
=
.
base kV = 220.00
3ZAOT = 948 - j8714 A
0.002 95 + j0.025 18/0.025
I
44 kV 3-WIRE DELTA LINE
+ j 0 pu
55 pu
Fig 10
230 kV Bus Fault
46
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANST/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
230 kV BUS
-j9.2471 pu
0.0155 0.0189
-10.3933
0.544
-10.85 pu
I
(b)Three-phase Fault
47
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
Fig 11
A Sample Computer Program Output
48
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT SM 367-1987
-
+ 1 2
LEFT
STATION 1
3
4
5 1
6
7
8 2
9
10
11
12 2
13
14
15 2
16 2
17 2
18 !
19
20
t 21
23
24
e: 26
29
4 30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
RIGHT
48
STATION 49
4 50
- 2
MAX Y HAS AN ABSOLUTE VALUE OF 2216.965
EACH Y-INCREMENT HAS A VALUE OF 20.000
EACH Y-DIVISION HAS A VALUE OF 400.000
Fig 12
Left Station Potential Versus Tower Numbers
49
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
-
+ 1
LEFT 2
STATION 3
4
5
6
7
8
9
10
11
12 1
13
14
15
16
17
18 1
19 2 1
20 2 1
t 21
2 22
8 23
5 ;; 2 1
26
28 :; 29
30 2 1
31
32
33
34
35
3t
35
3t
3:
4( 2 1
41
4:
4:
4r
4f
4t
4:
41
RIGHT
STATION 4!
+-
5(
CURVES 1 AND 2 CORRESPOND TO THE FOLLOWING RGL, RGR VALUES:
RGL RGR
1 1.000 1.000
2 0.500 0.500
Fig 12 (continued)
50
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT sta 367-1987
(2) The voltage breakdown of power system insulation requires circuit break-
ers to open or fuses to melt. The fault can be cleared in one of the following
ways:
(a) Normal operation for all voltage classes when the fault clearing time
is from 0.03-3 s, or more. Telecommunication by wire-line facilities is
often used to attain a clearing time interval of 0.03-0.15 s.
(b) Abnormal operation is when fault clearing time is increased due to a
failure of some switching equipment or its control. Wire-line facilities
are often used as part of this backup tripping scheme with or without
being a part of the normal tripping. The maximum time is rarely, if
ever, over 3 s in situations having a high GPR. An uninterruptible
wire-line facility is essential in this type of operation.
(c) On distribution lines protected by single-phase reclosers, sectionaliz-
ers, or some combination thereof, following a ground fault, one or two
phases may become open while the remaining phase(s) is (are) still
operating causing a small ground current to flow. This condition is not
easy to recognize and may, consequently, take several hours to clear.
5.3.3 The calculation of the fault currents and interfering voltage should
include their changes or decay time for the duration of the fault as expected
from the normal tripping time, or abnormal tripping time if backup protection
involves wire-line telecommunications facilities. In some limited cases the tele-
communications channel can be discontinued momentarily after the tripping
signals have been r e ~ e i v e dThere
.~ are types of relay protection (for example,
phase comparison) that must have continuous telecommunications prior to, dur-
ing, and as long as the fault exists.
*See 6.2.3 in ANSI/IEEE Std 487-1980 [5] (currently under revision) for cautions concerning
personnel safety.
51
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
in the electric currents in the upper atmosphere, 50-200 mi above the earths
surface. These currents vary from 30 000-80 000 A and cause a wide variation
in the earth currents.
5.4.4 Magnetic Storms. Usually following severe sunspot activities, the
magnitude of the currents in the earths atmosphere increases. As a result, the
level of the earth currents are drastically increased; however, the overall cycle
from minimum to maximum levels takes over 20 years. Previous technical pub-
lications have shown that these solar induced (SIC) or geomagnetic currents
have seriously affected power system operations. However, little is known, or
published, regarding their effects on GPR or longitudinally induced voltages into
wire-line telecommunications facilities.
In any event, since the earths surface potential can be 6 V/km or even higher,
currents will flow in power or telecommunications systems that are grounded
at intervals that are remote from one to the other. Thus, under the most severe
conditions, both the GPR and the induced voltage can be higher than normal.
In areas where large telluric currents are known to exist or where SIC are
high (or both), one should evaluate the resultant potentials and their impact on
probability factors in determining maximum values of GPR and longitudinally
induced voltages.
NOTE: The earths surface potential gradient from this cause is primarily in the east-west direction;
therefore, only east-west power or telecommunication lines are likely to be affected.
5.4.5 There are combinations of circumstances and multiple faults that will
produce currents and voltages higher than those calculated on a single contin-
gency basis.
5.5 Example of A GPR Calculation and Volt Time Area Calculation
5.5.1 Introduction. The following is an example of a GPR calculation with
the power system having a phase-to-ground voltage of 115 kV and an arrange-
ment shown on Fig l(a) and described in 5.2.6(1). For simplicity, the contribu-
tion of fault current from the local source is neglected in the calculations, and
only that portion of the fault current that creates GPR is considered. No over-
head ground wires are assumed in this example. The remote ground source
equivalent fault impedance and the line fault impedance is given in per unit
(pu) on a 100 MVA base. The local source station ground grid impedance is given
as 1.5 0.
5.5.1.1 Impedance of Power System
Source Z1 = 0.01 + j0.05 pu on 100 MVa base
2, = 0.01 + j0.05
Zo = 0.02 + j0.08 -zero sequence impedance of the complete
fault loop, including source impedance
Line 2, = 0.03 + j0.19
2, = 0.03 + j0.19
Zo = 0.18 + j0.67
52
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
115,
base Q = -= 132.25
100
1.5
ZSG = ~ = 0.011342 pu
132.25
The value t o be inserted in the sequence network is 3.0.011342 or 0.034 pu.
Therefore,
= Z1 + 2, + Zo + 3Zsc (in pu)
ZTOTAL
= 0.314 + j1.23 pu
5.5.2 Calculations to be Performed
5.5.2.1 Calculate the peak current for phase-to-ground fault a t 115 kV in
the substation yard (see 5.5.3).
5.5.2.2 Calculate the area under the current curve as illustrated for the
interval to first zero crossing (see 5.5.4).
5.5.2.3 Calculate the GPR and voltage curve area (see 5.5.5).
5.5.2.4 Calculate the peak current for a single phase-to-ground fault fol-
lowed by a double phase-to-ground fault (see 5.5.6).
5.5.2.5 Calculate the area under the current curve to first zero crossing (see
5.5.7).
5.5.2.6 Calculate the GPR and voltage curve area (see 5.5.8).
NOTE: For the general case, only that portion of the total fault current returning through
the substation ground grid impedance with respect to reference ground should be considered.
5.5.3 Calculating Peak Current (5.5.2.1). The base current for a 100 MVA,
115 kV transformer bank is 502 A/phase. The symmetrical fault current in the
one faulted phase and ground, assuming no change in the source impedance
with time and with the substation ground grid impedance included, is three
times the base current divided by 2, + 2, + 2, + 3Zsc;.
3 (502)
zc; =
0.314 + j1.23
- 1506
-
1.269 /75.68
= 1186 A rms steady-state
5.5.3.1 The peak of the steady-state current is fi (1186) = 1677 A. This
fault current lags its corresponding phase voltage by 75.68'. When the voltage
is approaching zero and is only 14.32' away, the current will be maximum. If
a phase-to-ground fault occurs at that instant then there will be a dc offset equal
to 1677 A and of opposite polarity. The net current will be zero, assuming no
prefault current. The dc offset will decrease exponentially from this instant with
no change in polarity. When the alternating current has reversed its polarity,
and approximately one-half cycle later, the total fault current will be maximum.
-(Rt)
53
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
where
r$ = initial emf phase at the instant of fault
e = power factor angle
i = instantaneous total fault current
I = peak symmetrical current = 1677 A
t = time from start of fault or t = 0 is 90" before i is zero (at maximum current
t = 0.008 33 s)
T = time constant
A
-
-
-for
60 Hz = 0.010 39
377R
NOTE: X/R = tan 75.68"or
1.23
X/R = -= 3.9171
0.314
R = impedance of the system to the point of fault
X = reactance of the system to the point of fault
IT
Assuming 4 -8= - -, then i = i,
2
+ id, = I
id, = 1677~-0.0103g
= 752 A
'
0.008333
54
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
(-0
-
T
id, = l e
1-(
= le 0.01039
= ze-0,40103
id, = l e
- 1~-1.203
-
= I(0.300)
At t = 0.013 250 95 the ac and the dc are equal and opposite.
i, = -I cos 377t
= -I COS 4.9956
= -1(0.279 32)
(-ooo~~oz~~95)
id, = l e
= Ie-1.275356
= +I(0.279 32)
=
377
[ - cos 377t lo
0.004 167
]
55
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
-
- --1677 [(cos 900) - 111
377
= 4.448 A . s (see Fig 14)
For area No 3, the time is t = 0.013 250 95 - 0.0125.
-
1.027 /74.53" (502) /oo = 1169 ,280.270
0.4410 /154.26"
-Zo(5O2) /oo
12 =
0.4410 /154.26"
0.7857 /72.67" (502) /180"
-
-
= 894/92.42"
0.4410 /154.26"
IB =Io + 1/240"11 + 1/120"1,
56
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
Fig 13
Current Curve and Determination of Area No 1
Fig 14
Current Curve and Determination of Area No 2
Fig 15
Current Curve and Determination of Area No 3
57
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
- t_ -
0.007 128
= 0.686 and
TB 0.01039
= 0.5036
then
ZBdc = 1677 (0.5036) = 845 A
The ac component of phase B when phase C starts is - 1677 cos 153.96 = 1507 A.
Then the total phase B current = 845 + 1507 = 2352 A.
From the double phase-to-ground calculation, phase B should be lh (1882)
cos 153.96 = 2391 when phase C is maximum, but is actually 2352. Therefore,
the new phase Bdc component is -39. To obtain its decrement, evaluate the
X / R ratio for the new phase B current using the angle between EB and ZB:
tan (240' - 176.81') = tan 63.19" = 1.979
then
1.979
T B = -- - 0.005 24 88
377
The X / R ratio for phase C is determined by the angle between Ec and IC:
tan (120' - 22.85') = tan 97.15 = 7.9718
then
7.9718
Tc = ~ = 0.0211 45
377
By trial and error we find that the maximum ground current for this problem
58
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
ledc 2526
-7 E o c (FROM 19 TO GND-
SEE pg 12) 1186 rms
lh 3 1677PEAK
= I 5 0 7 AT THIS INSTANT
t 0.007128
1
t
(a)
l e o c = 2526
(e)
Fig 16
Graphical Representations of Peak Currents
59
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
appears after Is and IC have rotated 85" or at 0.003 935 6 s after their position
when IC started.
To determine the total fault current, we must evaluate the two components
of each phase current (See Fig 17).
IC,, component = 2526 sin (-90" + 85")
= -220 A
For the ICdc
component find
-
Fig. 19. r
Area No 2, under the dc offset for the second phase B current, is shown in
(-00270139)
0.20 A - s
=
Area No 3, under ac below axis for the initial phase B current, is shown in
Fig 20.
60
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 361-1981
1677
Area No 3 = -(-1) = -4.448 A . s
377
a
for of a sine wave.
Area No 4, under ac above axis for the initial phase B current, is shown in
Fig 21.
0.007 128-0.004 167
- 1677
--
-
[COS 377 (0.002 96) - COS 377 (O)]
377
= -4.448 (COS 1.1163-1)
I
0.00833-0.004 167
- 2662
--
-
[COS 337 (0.004 167) - COS 377 (0.002 96111
377
= -7.061 (COS 1.5708 - COS 1.1163)
= -7.061 (COS 90" - COS 63.96")
= -7.061 - (0.438 99)
= 3.100 A - s
tz-0.020833
Area No 6
where
= IB2
I sin 377t dt
0.033 33-0.020 833
t2 = 0.034 141 9
-2662
-
- [COS337 (0.013 308 6) - COS 377 (0.0125)l
377
= -7.0610 (COS 5.017 34 - COS 4.7125)
= -7.061 (COS 287.47" - COS 270")
= -7.061 (0.300 15 - 0 )
= 2.119 A S S
Area No 7, under the dc offset for phase C current, is shown in Fig 23.
61
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
SM 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
lG=3231
1877 1-----flcdC=2O97
T
t =O.Ol10636
Fig 18
Fig 17 DC Offset and Determination
Graphical Representation for of Area No 1 and for Initial
Arriving at Total Fault Current Phase B Current
Fig 19
DC Offset and Determination of Area No 2 and for Second Phase B
Current
Fig 20 Fig 21
Determination of Area No 3 for Determination of Area
Initial Phase B Current No 4 for Initial Phase B Current
Fig 22 Fig 23
Determination of Areas Nos 5 and Determination of Area No 7 under
6 for the Second Phase B Current the DC Offset for Phase C Current
62
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
(-0.0270139) - 13
0.02113
Area No 7 = 2526 (-0.021 13) [e
= 2526 (-0.021 13) (e-1.27846
- 1)
= 53.374 (-0.721 53)
= 38.511 A . s
Area No 8, under the ac of phase C current, is shown in Fig 24. (Note that
areas A + C equal B + D and that they therefore cancel each other.)
where
I';
Area No 8 = -Icac cos 377t dt
0.024999
tz = 0.027 013 9
- -2526
-- [sin 377 (0.027 013 9) - sin 377 (0.024 99911
377
= -6.700 [sin (10.184 24) - sin (9.4249)l
= -6.700 [sin 583.5' - sin 540"l
= -6.700 [sin 223.5' - 01
= -6.700 [-0.68851
= +4.613 A . s
63
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
Fig 24
Area No 8
Fig 25
Total Current for an Evolving Fault
rent. Then one should use only that portion of total fault current actually re-
turning via the earth path for the GPR calculation.
5.6 Summary
5.6.1 While the objective of this section is to provide examples of the calcu-
lation for worst-case or maximum GPR voltages under single-phase and double
phase-to-ground fault conditions, the likelihood of an evolving double-phase fault
occurring with the critical time intervals required to produce worst-case con-
ditions is remote. Even a single phase-to-ground fault occurring under ordinary
operating conditions and initiated at the worst possible time is remote. There-
fore, by individual judgment, reduction factors may be applied to worst-case GPR
values. as shown in Section 10.
64
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT SM 367-1987
Fig 26
Combined Relative Wave Forms
. .
G = E 2
ac
dc
A
oc
+i
dc
65
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
6. Calculation of Electromagnetic Induction Under
Power Fault Conditions
6.1 Statement of the Problem. When an electric supply line that parallels an
overhead or underground telecommunication line experiences a ground fault
during which fault current returns through ground, a longitudinal voltage is
electromagnetically induced in the telecommunication line. Almost without ex-
ception, the magnitude of this induced voltage far exceeds the electromagneti-
cally induced voltage encountered under normal operation of the supply line.
The magnitude of such induction depends chiefly on separation and length of
inductive exposure between the supply and telecommunication lines, magnitude
of fault current in the earth return path, and earth resistivity. The values of
earth resistivity to be used in the calculation and the distribution of return fault
current are the most difficult factors to ascertain with accuracy.
While there are more rigorous methods of calculation, the one presented here
will give a good approximation of induced voltages to be expected. A higher
degree of precision would demand greater accuracy in the parameters, including
the value of earth resistivity. Metallic sheathed electric supply cables (overhead
and underground) are not considered in this section of this guide.
6.2 Introduction. This part of the guide presents a simple method of calcu-
lating electromagnetic 60 Hz longitudinal induction in a telecommunication line
when exposed to an overhead electric supply line under fault conditions. Induc-
tion from lightning surges is not included. This part considers only grounded
power systems and uses values of inducing currents or L-G fault currents as
supplied by the power company concerned. While the emphasis is on transmis-
sion lines, it is applicable to all grounded power systems. However, care must
be exercised when telecommunication cable shields are bonded to power system
multigrounded neutrals associated with lower voltage supply lines because of
the additional factors introduced by the changes in return current distribution.
67
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
SM 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
6.3 General
6.3.1 Inducing Current. The value of inducing current given by the power
utility depends upon many parameters including the effeds of other supply lines,
overhead ground wires, or conductors that play a part in the fault calculations.
Where the effects of other supply lines or conductors can be neglected, the in-
ducing current can be taken either as the ground return current or the fault
current modified by return through lightning protection wires (overhead ground
wires), rails, pipes, etc.
This gives a fairly rigorous solution, and the inducing current can be either
in terms of absolute magnitude or complex values. Note that a n inducing cur-
rent is calculated for each supply source acting in the exposure.
6.3.2 Mutual Impedance. In the calculations that follow, the major empha-
sis is on the determination of the mutual impedance between the disturbing and
the disturbed circuits. If the lines involved are not reasonably parallel, the total
exposure is sectionalized and then the mutual impedance determined for each
section. The sum of these values is then taken as the total mutual impedance.
A more rigorous treatment would consider phase changes in induction as sep-
aration is changed, particularly for large changes, for example, 50-1000 ft (15-
300 m). The method used here ignores such phase changes and could therefore
produce higher values than actually present. Figs 29 through 34 presume that
one has knowledge of the average earth resistivity throughout the inductive
exposure.
The following examples consider symmetrical fault current. The mutual
impedance values using Figs 32, 33, and 34 (SI units) are based on conversion
of the separation and length in feet or kilofeet rounded off to suitable significant
figures in meters or kilometers, respectively.
The most widely used formulation for calculating the external mutual imped-
ance of parallel supply and telecommunication circuits was developed by J.R.
Carson [71.
The general configuration for mutual impedance is shown in Fig 27. The so-
lution of Carsons mutual impedance integral in meter-kilogram-second (mks)
units is:
s12
where
Z, = mutual impedance per unit length
S = horizontal separation between supply and telecommunication lines
S12= distance between conductor (1)and image of conductor (2)
s12= distance between conductors (1)and (2)
h, = height of conductor (1)
h2 = height of conductor (2)
012= angle defined in Fig 27
p = earth resistivity in meter-ohms [k]
w = 2nf = the angular frequency of the inducing current
po= the rationalized permeability of free space = 4 n .
68
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1981
AND INDUCED VOLTAGE FROM A POWER FAULT
y s - q
CON DUCTOR
CONDUCTOR (2)
I
I
\ I.I h 2
IMAGE OF
CONDUCTOR (2)
L
I
I
IMAGE OF f
CONDUCTOR (1) (->
Fig 27
General Configuration for Mutual Impedance
The corrections AR' and AX' account for the earth return effect and are
functions of O12.
Defining parameter a,
7
a =
for a
0.851 sl,
5 5
4-
i:
AR;, = 4 ~ 1 0 --~- b, a cos 01, + b2 [(ez - In alaz cos 2OI2+ O12a2sin 20121 + . . .
1
(0.6159315 - In a ) + bla cos 012 - dza2COS 2012 + . . .
where
69
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
1 1
c, = c,-, + 7 + -with starting value cz = 1.365 931 5
i i+2
Tr
d, = - b,
4
for a > 5
cos Ol2
+- fiCOS 2012 cos 3Ol2
+ 3 cosa5Sol2 45 cos 7Ol2
AR;, = (e-
a2 a3
-
a7
hl + h, S
cos 01, = ~ and sinO,, = -
Sl, SI2
References [ l l ] and [12] describe the conditions under which Carsons formula
is sufficiently accurate for determining mutual impedance. The formula is valid
for the power frequency and all its harmonics below 5 kHz. Carsons formula
can also be used for buried telecommunication lines if the log term is eliminated
and h, is replaced by a negative number with magnitude equal to the burial
depth. The only restriction on this use is that the burial depth be a small frac-
tion of the skin depth in the earth. A simpler procedure that is more valid in
most practical cases is to simply evaluate Carsons formula a t the earth surface
directly above the buried telecommunication cable, which is accurate to within
5%, as long as the burial depth in homogenous soil does not exceed 2 m and the
distance to the supply line is much greater than the burial depth.
Figs 29 through 34 are derived from Carsons formula in [7], assuming that
one has knowledge of the average earth resistivity throughout the inductive
exposure. Earth resistivity may vary widely, both geographically and season-
ally. Where a higher accuracy is required in the calculation of mutual imped-
ance, measuring the earth resistivity profile along the exposure under extreme
seasonal conditions (that is, dry soil, frozen soil, etc) is usually necessary.
A simplified approximation of Carsons formula, known as the extended com-
plex image formula (reference [131), is as follows:
where
and
70
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 361-1987
y = Vjw IJ.~U
with
po= the rationalized permeability of free space
h, = height of conductor (1)
h2 = height of conductor (2)
NOTE: Z, is a complex quantity with resistive (R,) and reactive (X,) parts. The quantities D, and
y are also complex. The value of po is 4i-r. H/m (henrys/meter), the permeability of free space.
The extended complex image formula provides results that are valid to within
5% of Carsons formula for the following values of Do:
Do < 0.51 l y l and
D2 < 51 l y l
For other values of Do,variations of up to 20% may occur. Buried telecom-
munication lines are handled with the same accuracy as in Carsons formula,
providing burial depth is less than 2 m.
Appendix 1 provides calculator program listings and user instructions for cal-
culating mutual impedance using the extended complex image formula.
6.3.3 General Formula. For an inductive exposure with uniform separation
between a supply and telecommunication line, the longitudinally induced volt-
age in an unshielded telecommunication conductor can be calculated using the
following:
v = Z,I (volts)
where
2, =product of mutual impedance z,, expressed in R + jX ohms per kilofoot
or per kilometer
L = length of exposure in kilofeet or kilometers, respectively
I = inducing current supplied by power utility, in amperes
71
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 361-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
where
S = horizontal separation between supply and telecommunication lines
1100 ft (30 m)]
D = difference in line heights 125 ft (7.5 m)]
p = earth resistivity (1000 SZ - m)
L = length of exposure [10.25 kft (3.1 km)]
Z = inducing current (absolute value) (3000 A)
z, = mutual impedance (complex), in ohms per kilofoot or per kilometer
Iz,I = mutual impedance (absolute), in ohms per kilofoot or per kilometer
2, = mutual impedance (total), in ohms
V = longitudinally induced voltage
6.4.1 Determination of Longitudinally Induced Voltage Using Complex
Values of Mutual Impedance
s = 100 ft
From Fig 29 R = 0.018 SZ/kft
From Fig 30 X = 0.103 R/kft
Fig 28
Illustration for Example 1
TRANSFORMER
UNFAULTED PHASE
UNFAULTED PHASE
TO LOAD
-
FAULTED PHASE I (FAULT1 = 3000 A
l,
- A
NOTE: In this case, the total fault current returns through the ground and, therefore, the fault
current is also the inducing current.
72
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
= 0.185 + j1.056 R
v = Z,I
= (0.185 + j1.056) 3000
S=30m
From Fig 32 R = 0.059 R/km
From Fig 33 X = 0.34 R/km
z, = 0.059 + j0.34 R/km
2, = z,L
= (0.059 + j0.34) 3.1
= 0.184 + j1.054 R
v = Z,I
= (0.184 + j1.054) 3000
IV/ = 3210 V
NOTE: In each case, V is the longitudinally induced voltage in an unshielded telecommunication
conductor.
6.4.2 Determination of Longitudinally Induced Voltage Using Absolute
Values of Mutual Impedance
s = 100 ft
From Fig 31 Iz,I = 0.104 R/kft
IzmI = I4L
= 0.104.10.25
= 1.066R
v = IZ,II
= 1.066 * 3000
= 3198 V
S=30m
From Fig 34 Iz,I = 0.34 R/km
IZmI = JzmJL
= 0.34.3.1
= 1.054R
73
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
v = lZm1I
= 1.054.3000
= 3162 V
For relatively close uniform separations, as shown previously, there is little
error in using the absolute values of mutual impedance.
Fig 29
Mutual Resistance of Ground-Return Circuits
0 05
0 04
0 03
0 02
6
e0
$ 001
u
y 0007
m
E 0005
0004
5)
y 0003
z
2
v,
0002
m
W
u
1
a 0001
3
5E 00007
0 0005
00004
0 0003
0 0002
0 0001
IO 20 30 50 70 I00 200 300 500700 1000 2000 3000 5000 7000 I 20000 30 000
IO 000
HORl ZONTA L SEPARATION- FEET
74
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
circulates a known current in the line-to-ground mode of the supply line and
measures the longitudinally induced voltage in the paralleling telecommuni-
cation line. With this method, the volts per ampere (ohms), or the absolute value
of mutual impedance modified by other return paths, can be determined. Where
the current is confined to the phase conductor-earth return path, the average
value of earth resistivity can be deduced from the absolute value of mutual
impedance obtained, and by use of Fig 31 or 34. This technique is most suitable
where uniform exposures are involved or where they can be sectionalized. Other
sampling techniques of measuring earth resistivity can also be used. These mea-
surements are fairly difficult to make and do not always give very accurate
information on the resistivity of the deep strata, which is important in the de-
termination of inductive coupling between the lines. Table l gives values of
earth resistivity to be expected based on the nature of the ground.
Fig 30
Mutual Reactance of Ground-Return Circuits
02
01
0 07
005
0 04
'0 003
B
9
- 002
Y
u
W
a 001
m
E
I 0007
0
W
' 0005
o 0004
z
3 0003
0
w
Q 0002
u
1
a
2
3
0001
00007
0 0005
0 0004
0 0003
0 0002
00001 ~
IO 2
c30 507 C y 2 0 0 3 0 0 5 0 ~ ~ 1 0 02000
0 3000 5000I 0000 20000 30000
7000
HORIZONTAL SEPARATION - FEET
75
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
Fig 31
Mutual Impedance of Ground-Return Circuits
76
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
0.5
0.1
W
c
W
E
2
IY
a
W
v)
z
I
0
0.01
0.001
Fig 32
Mutual Resistance of Ground-Return Circuits in SI Units
the fault current acts in an opposite direction and the resultant induced voltage
for such a section is subtractive. Figures 35 and 36 show special angularities of
lines. When the power and the telecommunication lines diverge as shown in Fig
37, the projection must be made as shown in this figure. The length P'Q' is not
subjected to any induction, and it is merely necessary to add the induced voltage
in PP' by ( p z ) and in Q'Q by (zq).
77
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
0.
u
W
c
W
E
s
Y
u
a
W
m
E
I
0
OC
0.oc
10 00
HORIZONTAL SEPARATION METERS
Fig 33
Mutual Reactance of Ground-Return Circuits in SI Units
78
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
Fig 34
Mutual Impedance of Ground-Return Circuits in SI Units
where
S = horizontal separation between supply and telecommunication lines (see
Fig 35)
9 = earth resistivity (1000 1R. m)
I = inducing current (absolute value) (2000 A)
D = difference in line heights [25 ft (7.5 m)l
L = length of exposure (see Fig 35)
z, = mutual impedance (complex), in ohms per kilofoot or per kilometer
JzI, = mutual impedance (absolute), in ohms per kilofoot or per kilometer
2, = mutual impedance (total), in ohms
V = longitudinally induced voltage [total (see 6.5.3)l
79
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
Table 1
Earth Resistivity
Precambrian
Cretaceous Cambrian and
Earth Resistivity Tertiary Carboniferous Ordovician Combinat.
n-cm n.m Quarternary Quarternary Triassic Devonian with Cambrian
100 1 sea water
loam
1000 10 unusually low clay
chalk
3000 30 verylow chalk
trap
10000 100 low diabase
shale shale
limestone
30000 300 medium sandstone limestone
100000 1000 high sandstone
coarse sand sandstone
300000 3000 very high and gravel dolomite quartzite
in surface slate
1 000 000 10 000 unusually high layers granite
gneisses
PART II
-
c
3wm 3Wm 3OOm 2Wm*l00~22Sm *150mi+~50 m 225m- 67s m
SUPPLY L I N E X - Y
COMMUNICATION LINE A - P
- 150011
450m
zm -
'E
L
'E -
I ?" LDU,
I
'E
49
1
+250fl;, 5OOft 250ft L
75 rn I 50 m i 7 5rnii
(b)
Fig 35
Inductive Exposure for Example 2
80
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
AND INDUCED VOLTAGE FROM A POWER FAULT ANSI/IEEE
Std 367-1987
NOTE: The section M"' is induced twice (by mz and zn).Therefore, the induced voltage in MN'
and M" is added.
Fig 36
Converging Inductive Exposure
Fig 37
Diverging Inductive Exposure
81
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
The exposure is divided into sections, Part I and Part I1 of Fig 35, showing
separations and lengths of projections. The section within 15 ft (5 m) of each
side of the crossing has been neglected. The slanting sections of Part I, shown
as DF and FH, and of Part 11, shown as LN, have been subdivided in order to
keep the ratio of maximum separation to minimum separation to 2 or below.
Table 2 shows the values of separation, the length L of each section, values
of z, (R and X per kilofoot), and corresponding values of R and X for each sec-
tion using both complex and absolute values. The induced voltage (V) per sec-
tion is shown and is computed using these values and the inducing current of
2000 A. Table 3 gives the same data in SI units.
From Table 2, the sum of the complex values of induced voltage in an un-
shielded telecommunication conductor is
V = 284 + j1387
IV1 = 1416V
Also, the sum of the absolute values of induced voltage is
[VI = 1408 V
From Table 3, the corresponding values of induced voltage using SI units are
in complex values.
V = 284 + j1368
IV1 = 1397 V
and in absolute values,
\VI = 1391 V
In most cases, where only absolute values of induction are required, the use
of absolute values of mutual impedance (from Figs 31 and 34) will give suffi-
cient accuracy.
6.9 Correction for Difference in Line Heights. Examples 1 and 2 have been
calculated using Figs 30,31,32, and 33 directly because the difference in supply
and communications line heights was taken as 25 ft (7.5 m). For horizontal sep-
arations less than 100 ft (30 m), Fig 39 gives the correction factor for other
82
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
Table 2
Example of Calculations for Part I
CornDlex Values Absolute Values
2, from Figs 29 and 30 z, = Z,L 12, I from
L (R + jX)/kft ( R+ j W L V = Z,I Fig 3l/kft ~Z,,l=lz,iL IVI=IZ,II
Section (kft) n n V n n V
83
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
Table 3
Example of Calculations for Part I1
Complex Valuer Absolute Values
(1) -
Section AB ( a b ) Parallel
SA and S, = 290 ft 0.3 0.06 + j0.17 0.018 + j0.051 36 + j102 0.180 0.054 108
(2) Section BC (bc)
S, = 290 m 0.06 + j0.17 0.18
SC = 145 m 0.3 0 06 + '0 22 0.22
av5- 0.018 + j0.059 36 + j l l 8 av 0.20 0.060 120
(3) Section CD ( c d )- Parallel
Sc and S, = 145 m 0.3 0.06 + j0.22 0.018 + j0.066 36 + j132 0.22 0.066 132
(4) Section DE ( d e )
SD = 145 m 0.06 + j0.22 0.22
SE = 70 m 0.2 0.28
0.012 + j0.050 24 + j l 0 0 av 0.25 0.050 100
(.5.) Section EF (.e..
n
SE = 70 m 0.06 + j0.28 0.280
SF = 35 m 0.1 0.06 '0.32
+ 0.330
av & 0.006 +j0.030 12 + j 6 0 av 0.031 61
(6) Section FC ( f g )
SF = 35 rn 0.06 + j0.32 0.330
So = l a m 0.225 0.06 + '0.37 0.380
av5 - 0.014 + j0.078 28 + j l 5 6 av 0.355 0.080 160
(7) Section CH ( g h )
So = 1 8 m 0.06 + j0.37 0.380
SH=9m 0.15 av =;m; 0.410
0.009 + j0.059 18 +j l l 8 av6.395 0.059 118
(8) Section H l ( h i )
S" = 9 0.41
S1=5m 0.43
0.07 5 0.005 + j0.032 1 0 + j64 av 0.42 0.032 64
(9) Section KL (kl)
Same as HI 0.075 0.06 + j0.42 0.005 + j0.032 10 + j64 0.42 0.032 64
(10) Section LM ( l m )
Same as GH 0.15 0.06 + j0.39 0.009 + j0.059 18 + j l l 8 0.395 0.059 118
(11) Section M N (rnn)
Same as FC 0.225 0.06 + j0.345 0.014 + j0.078 28 + j156 0.355 0.080 160
(12) Section NO (no)
SN = 35 m 0.06 + j0.32 0.330
So =70m 0.675 0.06 +i0.28 A&%!
av 0.06 + j0.30 0.041 + j0.203 82 + j406 av 0.305 0.206 412
(13) Section OP (op)
So = 7 0 m 0.45 0.06 + j0.28 0.28
S p = 145 m 0 06 + '0 22 0.22
I acta in opposite direc-
tion for this section
av & 0.027 + j0.113 -54 -j226 av- 0.113 -226
84
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
1.1
,1066
/-
/
/
0.9 '
/
,/
/
SECTIONS
0 I 2 3 4 5 6 7 8 9 10 I kft
0 03 06 09 12 15 I 8 21 2 4 27 30 3 km
EXPOSURE LENGTH
Fig 38
Cumulative Mutual Impedance Curves for Examples 1 and 2
differences in average line heights. (See Fig 39 and Example 3 for sample cal-
culations.) In most cases the corrections are relatively small.
6.10 Electric Supply Line with Double-End Feed. Where the supply line
has a double-end feed (from X and Y directions in Fig 401,the inducing currents
act in opposite directions. Therefore, when evaluating the resultant induced
voltage for a specific portion of the exposure, care must be taken to ensure that
opposite signs are used when adding up the contributions from each power source.
85
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
2
0
L
L
w
U
U
s
NOTES: (1) The above chart gives the correction factors to be added to the values obtained from
Figs 30, 31, 33, and 34 to allow for the difference in heights of supply and telecommunication lines.
Note that the values directly from Figs 30 and 31, and Figs 33 and 34, are based on height differ-
ences of 25 ft and 7.5 m, respectively.
(2) Example: The value from Fig 30 for a horizontal separation of 40 f t and earth resistivity p
of 31.6 R ' m , is 0.082 R/kft. This is for a height difference of 25 ft. If the height difference were
actually 60 ft, the correction factor from above would be -10 ( x ~ O - ~ or ) -0.01 R. The corrected
value would then be 0.082 - 0.01 or 0.072 R/kft.
(3) For Figs 30 and 31 separations are given in feet, whereas in Figs 33 and 34 separations are
given in meters.
Fig 39
Correction Factors for Differences in Line Heights
86
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
X t a-55
I
16.76 k m
kft i
I1
I1
6.1 k m
b4-20 k f t - c
I
I
50 t!
15mi
I 11
I1
I1
I
I
I
1; II
- 1
I
A 0 C
NOTES:
XY supply line Fault Location for Maximum Induced Voltage
AB and BC communication lines (not in- Exposure AB: Inducing current I , (value at B ' )
terconnected a t point B ) from X-end
Zl inducing current coming from Exposure BC: Inducing current Zz (value at B")
the X-end from Y-end
I2 inducing current coming from Exposure AC: Inducing current I , (value at C ' )
the Y-end from X-end
Fig 40
Double-Ended Supply System Feed and Inductive Exposure
for Example 3
6.12 Shield Factor
6.12.1 General. The electromagnetically induced voltage V, as discussed pre-
viously, is the voltage induced in an unshielded telecommunication line. A shield
factor is used to take into account the shielding action of all grounded conduc-
tors (overhead ground wires, rails, metallic pipes), including metallic sheaths of
telecommunication cables, etc, in an inductive exposure.
As on each section there can be several shielding conductors, the overall shield
factor for each section can be H , which is approximately the product of all shield
factors for that section:
= Tl1-72 ... Tln
This is true only if the individual shielding conductors act independently of
each other. Where the shielding conductors are close enough that one has an
effect on another, the resultant shield factor may be greater than the product.
87
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
The induced voltage for a section, considering the overall shield factor H for
sections, is
us = V . H
and fo; all sections combined
V=Cv
,=l
88
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
rection opposite to that of the faulted phase. In addition, the remaining circuits
on the faulted tower line and circuits on the unfaulted paralleling tower lines
on the faulted R-O-W will produce zero-sequence fault currents flowing in the
directions dictated by their terminal connections. Currents in their respective
phases will, generally, be unequal and will not necessarily flow in the same
direction. These facts must be included in the determination of the net inducing
current, taking into account the relative separations of each phase on the R-O-
W and the telecommunication line. The vector sum of currents induced in the
overhead ground wire of the faulted tower line from all of these conductors must
be deducted from the fault current entering the fault. This current does not
enter the earth but stays in the overhead ground wire and flows in the direction
opposite to the fault current. This current will induce in the telecommunication
line a voltage that counteracts the induced voltage into the same line from the
currents in the phase conductors, thereby producing shielding action.
In addition to reduction of the fault current for the purpose of determining
the net inducing current by subtracting the induced overhead ground wire
current, further reduction takes place through the effect of the current dissi-
pation into the earth conductively through the tower or pole footing ground
impedances. Near the fault, overhead ground wire may carry up to 80% of the
fault current, which is then gradually dissipated into the earth at each succes-
sive tower or pole. For long lines, the ratio of ground wire current to ground
current becomes relatively constant between the supply source and the faulted
tower or pole. In order to properly determine the amount of current conducted
into the earth one needs to model the impedance of the overhead ground wire-
tower ladder networks. Techniques employing both distributed and lumped pa-
rameter methods are now available. Their extension also allows for including
the inductive shielding effects of counterpoises and other buried ground con-
ductors.
If the previously mentioned reductions are not included in the information
provided by the power utility, additional shield factors must be considered to
take care of these conditions.
The shield factor range may be estimated according to Table 4 where the in-
ductive exposure is relatively remote from the source and from the fault loca-
tion.
For inductive exposure locations close to the supply source, or to the fault
location, the value of fault-current split should be computed.
6.12.4 Shield Factor for Continuously Grounded Telecommunication
Cables with Metallic Shields. Shield factors for telecommunication cables de-
pend upon many factors, such as
(1)Location of the shield-most effective if located in near proximity to either
the disturbed or disturbing conductor.
(2) Earth resistiuity-the ratio of mutual and self-impedances determine the
shielding current in the shield conductor. Both the numerator and the denom-
inator of the ratio are influenced by the earth resistivity in the same direction;
hence, variation in earth resistivity causes relatively small changes in the
shielding factor.
Typical 60 Hz shield factors for aluminum-shielded cables is given in Table
89
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
SM 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
Table 4
Shield Factors for Supply Line with
Overhead Ground Wires
60 Hz Shield Factor
Overhead Ground
Wire Type* Single Wire Double Wire
90
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
Table 5
Shield Factors for Alpeth Communication Cable
(Alpeth cable with 0.008 in (0.02 cm) aluminum shield)
11 pair 26 gauge
300 pair 19 gauge
1.34
0.28
4.40
0.92
1 0.99
0.97
0.98
0.90
0.97
0.80
Table 6
Shield Factors for
Stalpeth Communication Cable
(Stalpeth cable, 1.94 in (4.93 cm)
core diameter, with 0.008 in (0.02 cm)
aluminum shield and 0.006 in (0.015 cm)
steel shield. DC shield resistance =
0.37 S2/kft (1.21 Q/km).)
Primary Field
V/kft
22.9
V/km
75
I 6 0 Hz Shield Factor for Given R T / L
1.0
3.28
0.95
0.3
0.98
0.81
0
0
0.53
n /kft
/km
Table 7
Shield Factors for
Tape Armored Communication Cable
(Tape armored cable, 20G pair, with 0.008 in
(0.02 cm) aluminum shield and two 0.041 in
(0.104 cm) steel tapes. DC resistance (shield
and tapes) = 0.14 Q/kft (0.46Q/km).)
91
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
6.13 Typical Supply Line Fault Current Distribution. Figure 42 shows typ-
ical fault current distributions for faults occurring at different locations. As with
the shielding effects of overhead ground wires, the location of the fault, its po-
sition relative to the inductive exposure, and the length of the exposure will
determine whether averaging values of inducing currents are satisfactory in the
induction calculations. For example, a short exposure near an assumed tower
fault location could involve great differences in inducing currents at each end
of the exposure, that is, large overhead ground wire component a t one end only.
In some cases, the worst case could be a fault somewhat remote from the end
of the exposure where the earth return component has reached a more constant
value throughout the exposure.
100
0 90
0 80
070 LT
060 v
U
e
LL
050 n
J
W
040
v)
0 30
0 20
0 IO
12 15 2 3 4 5 6 7 8 9 1 0 15 20 30 40 50 607080kf+
06 09 12 I 5 18 27 30 6 I2 I8 24 km
EXPOSURELENGTH
Fig 41
Illustration of 60 Hz Shield Factors for Buried Telecommunication
Cable with Continuous Leakage
92
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
F - FAULT LOCATION
su P P L Y
SOURCE N
SUPPLY
SOURCE - c SU E STATION
FAULT
SUPPLY SUPPLY
SOURCE SOURCE
Fig 42
Examples of Fault Current Distribution for Line-to-Ground Faults
93
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
Where there are several supply lines between the same terminal points, the
circuits and the overhead ground wires provide paths toward and away from a
L-G fault on one circuit. Determination of the inducing current is much more
complicated than in the single circuit case of the single supply line.
6.14 Example 3. This example shows the calculations for a double-ended sup-
ply feed, and a telecommunication line that consists of both shielded cable and
open wire. Tine use of Fig 39, which gives mre&nn factors for biference:s iii
line heights, is also shown.
Given a uniform inductive exposure between a supply and telecommunication
line, as shown in Fig 40, which shows exposure AB and BC taken separately.
S = horizontal separation between supply and communication lines 50 ft
(15 m)
p = earth resistivity (316 R .m)
, I = inducing current (see Fig 40)
D = difference in line heights
exposure AB - 50 f t (15 m)
exposure BC = 15 f t (4.5 m)
L = length of exposure
exposure AB = 55 kft (16.76 km)
exposure BC = 20 kft (6.1 km)
q = shield factor (communication lines)
exposure AB - shielded underground cable = 0.5
exposure BC - open wire = 1.0
z, = mutual impedance (complex), in ohms per kilofoot or per kilometer
Iz,/ = mutual impedance (absolute), in ohms per kilofoot or per kilometer
2, = mutual impedance (total), in ohms
v = longitudinal induced voltage with shielding volts
94
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
?,AB) = 0.5
VSAB) = (0.990 + $5.335) 500.0.5
= 248 + j1334 V
JVSAB)J= 1357 V
Exposure BC:
Zm(BC) = 0.360 + j2.080 R
I , (at C') = 500 A
q(BC)= 1
VsBc) = (0.360 + j2.080) 500.1
= 180 + j1040 V
JV&c)J = 1055 V
95
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
X = 0.340 R/km from Fig 33. From Fig 39, the correction factor for X
whenD = 15 m and horizontal separation = 15 m is -0.018 R/km.
X (corrected) = 0.322 R/km.
z, = (0.06 + j0.322) R/km
L = 16.76 km
Zrn(mj= ZrnL
= (0.06 + j0.322) 16.76
= 1.006 + j5.397 R
I , (at B') = 600 A
AB) = 0.5
VSAB) = zrnllq
= (1.006 + j5.397) 600 * 0.5
= 302 + j1619 V
IvsABjI = 1647 v
Exposure BC:
Zm(BC) = 0.366 + j2.098 R
I , (at C') = 500 A
q(BC) = 1
VS,,, = (0.366 + j2.098). 500.1
96
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
= 183 + j1049 V
IVfBcll = 1065 V
Exposure AB plus BC:
VSAc) = VSAB,+ V&c)
= (252 + j1349) + (183 + j1049)
= 435 + j2398
IVsAc)l = 2437 V
97
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
7. The Vectorial Summation of a Ground Potential
Rise (GPR) with a Longitudinally Induced Voltage
7.2 General. This section presents a method of calculating the resultant volt-
age between the electric power station ground grid and a conductor that is
grounded at a remote location such as a telephone central office. The combi-
nation of electromagnetic induction and power station GPR (before the appli-
cation of protective devices) for both symmetrical and asymmetrical fault cur-
rent waveforms is considered.
7.2.1 The following examples illustrate the proper combination of voltages
that exist on a telecommunication wire line that is terminated at an electric
power station. Figure 43(a) shows a telecommunication wire line serving a power
station that is not the source of fault current. Figure 43(b) shows a telecom-
munication wire line serving a power station that is the source of fault current.
99
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
F A U L T CURRENT
SOURCE
-- I ( F A U L T )
FAULT
- ,flGROULD RETEN! - - - -- _ _
-E- - - - -&
A
( IN D U C E D VOLTAGE
Fig 43
Illustrations for Examples 1 and 2
100
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
7.2.2 For simplicity, assume that the inducing current is also that which cre-
ates the station GPR while flowing through the power station ground grid
impedance.
Other symbols:
E = longitudinally induced voltage = 12,
101
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
=
(
2516 sin 377t --
3 + 2516 e- w0.01039
The GPR is the sum of a sine wave voltage and a positive exponentially de-
caying dc voltage. Since the sine wave and the dc term are of opposite polarity
at t = 0, the maximum instantaneous value of the GPR voltage occurs at the
approximate time when the sine wave reaches its first positive crest value. Thus
the maximum voltage occurs when
T r T r
3772 - - zz -
2 2
or
t = 0.00833 s
Accordingly, the maximum value of V, is
102
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1988
max IV,l =
(
2516 sin 377.0.00833 - -
2 "1 + 2516 e- (""1
0.01039
= 2516 + 1128
= 3644 V
7.4.2 The 60 Hz longitudinally induced voltage V, is
Vg = - E = -12m
From 7.4.1, it can be seen that the inducing symmetrical fault current in polar
form is:
I = ll86/00
V, = -E = -IZ m
V, = -(1186)(0.185 + j1.056)
Vg = -(219 + j1252)
V, = 1272 1-99.92" = 1271 /-1.74 radians V
V, = 1272 sin(377t - 1.74) V
7.4.3 The combination of induced voltage V, and ground potential rise V, as
a function of time is
v, = v, - v,
=
(
2516 sin 377t --
3 + 2516 e- w
0.01039
v, = 3774 /-93.33"
V, = 3774 /-1.51 rads
103
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
and the maximum value of V, is
104
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
8. Power System Fault Current Probability
8.1 General. During the operation of a high-voltage power system, the loca-
tion, duration, magnitude, and asymmetry of fault currents will all vary in ac-
cordance with the laws of random events. As well, the layout of most large power
system networks is constantly changing.
The random character or nature of a fault, and the extremely low probability
of a fault having maximum possible worst-case characteristics, make it econom-
ically and technically possible to abandon such ultimate or worst-case fault cur-
rent calculations and conditions in favour of a more realistic approach when
determining the magnitude of interference into wire-line telecommunications
facilities.
105
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
(3) Knowing the distribution laws of random variables, an interdependence
between the possible values of interfering voltages and their respective proba-
bilities can be established.
(4)The relationship deduced from incorporating power fault field data anal-
ysis allows a determination of the probability of an interfering voltage exceed-
ing a predetermined permissible value under actual operating conditions. Less
than worst-case values can then be assigned for economical protective equip-
ment design.
(5) The power utility should determine the appropriate magnitude, wave-
form, and duration of fault currents that introduce interfering voltages into wire-
line telecommunication facilities by using probability studies for fault-current
characteristics.
106
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
9. Zone of Influence of
Ground Potential Rise (GPR)
9.2 Equipotential Lines. As a result of current flowing from the ground elec-
trode(s) to earth and through the earth path, equipotential surfaces plotted at
right angles to these current lines will assume a shape controlled by the path
of the current. The density of the equipotential (potential gradients) surfaceb),
Fig 45, having equal voltage differences between them, across a path in a given
direction, determines the interfering voltage that may be encountered. This re-
sulting potential gradient will be higher near the grounding electrode, as shown
in Fig 44(b). Figure 44(c) shows examples of fall-of-potential for different sizes
of grid areas with respect to distance to remote earth.
107
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
"
-
-
LINE-TO-GROUND
FAULT ON
POWER LINE
REMOTE
GROUND
TRANSFORMERS GROUNDED
THROLGHOUT ThE SYSTEM
t
STATION
DISTANCE FROM GROUND GRID-
GROUND
Fig 44
Zone of Influence of GPR and its Distribution
108
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
NOTES: (1) A small grid area-approximate grid area 1600 ft2 (150 m2).
(2) A medium small grid area-approximate grid area 35 000 ft2 (3350 m2).
(3) A medium large grid area-approximate grid area 290 000 ft2 (27 000 m2)
(4) A large grid area-approximate grid area 935 000 ft2 (87 000 m2).
(5) See reference 161.
109
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
I 0
NOTES:
A-Power station ground grid
B-Points of equal value of ground resistance from station grounding grid where the GPR is reduced
to an acceptable limit, for example, 300 V.
C-Area of the zone of influence of the GPR.
Fig 45
Boundary of the GPR Zone of Influence
110
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
111
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
around the power station. Potential gradients in and around a large substation
should be determined for two or more fault conditions.
Underground metallic structures, metallic structures on the surface of the earth,
metallic fences, and overhead ground wires in the vicinity of a substation, whether
connected to the ground grid or not, will usually have a significant effect upon
potential gradients and should be considered when making potential gradient
measurements. These structures include neutral conductors, metallic cable
sheaths, metallic water and gas lines, and railroad rails.
When a potential gradient study cannot be justified economically, potential
gradients may be calculated from ground resistance and soil resistivity mea-
surements. The accuracy of such calculations will be dependent upon the ac-
curacy of the measurements and the unknown abnormalities of the earth around
and below the ground grid. (See ANSI/IEEE Std 81-1983 [4].)The adequacy of
such calculations may then be verified with relatively few potential gradient
measurements.
When a ground electrode ground grid, or a buried cable of a telecommuni-
cation system is located in the vicinity of a high-voltage ground grid, part of
the potential arising in the latter during a ground fault can transfer to the for-
mer through resistive and inductive coupling. A high-voltage metal tower or
conductor that has fallen to the ground can also be regarded as a ground elec-
trode in the same sense. The potential may enter the telecommunication circuit
from the telecommunications grounding electrodes or cable sheath through the
overvoltage protectors or due to a dielectric failure of the cable jacket or con-
ductors.
112
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
9.5 The Effects of GPR Within the Zone of Influence. Depending upon the
magnitude of a GPR, the following effects may arise outside a power station or
adjacent to a power line grounding electrode or transmission line tower (within
the zone of influence of the GPR):
(1) The potential may be transferred through a metal part, bonded with, or
coupled resistively to the plant grounding electrodeb), to remote locations.
(2) The touch voltage between a part grounded to the plant grounding elec-
trode and a local ground (for example, a high-voltage interface ground) may be
excessive.
(3) Reversed touch voltage (or voltage stress) between the local ground and
a part having a lower or even zero potential may become excessive, for example,
a telephone cable protection interface.
9.6 The Transfer of a GPR. The station ground potential can, for example,
appear outside the zone of influence through a conductor of a telecommunica-
tion line; a system grounded neutral conductor of a lower voltage distribution
system; a metallic sheath of a telecommunication or power cable; railway rails;
and metallic pipes, such as water pipes, entering the station. The magnitude of
this transferred GPR is somewhat lower than the station ground potential be-
cause of the longitudinal impedance of these cable sheaths, water pipes, rails,
etc.
where
L span length
=
Z, impedance of overhead ground wires per unit length
=
2, = tower-footing impedance (assumed to be constant)
113
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
9.8 The Case of a Short, Noninsulated Conductor Within the Zone of In-
fluence and Subject to a GPR Interference. Assume that, apart from the
power-system ground grid under consideration, there are no other metallic con-
ductors in the soil, which is assumed to have a homogeneous resistivity. At a
distance, d, which is more than three times the radius of the ground grid, the
potential of the earth surface is in effect raised to the level
d e
(Pe = -
2nd
where
p = soil resistivity
Also assume that a relatively short noninsulated conductor, for example, a
section of the lead sheath of a telecommunication cable, is embedded in the soil
near the current-discharging ground grid.
In the past, the conductive interference into such conductors was often mea-
sured in an electrolytic tank. Figure 46 shows typical potential curves thus de-
termined for the earth surface in the vicinity of an overhead line tower ground.
In the past, a tower ground electrode was assumed to take the form of a con-
ductive hemisphere, of the same impedance to remote earth, which was buried
in the soil. This hemispherical electrode, indicated at the bottom left in Fig 47,
and the conductor subject to interference were simulated in a n electrolytic tank.
For example, a noninsulated conductor of 600 m length, whose center part was
immediately opposite the tower at a distance of 25 m, assumed a potential of
between 3 and 5% of the earth electrode voltage (curve b in Fig 46).
Normal practice is to use computer programs to determine the conductive in-
terference of conductors within the ground grid area of grounding systems.
The potential appearing on the cable shield, expressed as a percentage of the
tower footing voltage, is shown in Fig 48 for various lengths and positions of
the shield subject to interference. Some of the curves shown on the left-hand
side of Fig 48 were determined using an electrolytic tank, and others by using
a computer program. The curves on the right-hand side were determined using
a computer program.
The program was used to calculate the discharged and absorbed currents per
length of the electrode sections, as shown in Fig 48. This method was also used
to calculate the currents in the corner footings of the tower and in the influ-
enced conductor.
114
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 361-1981
25 50 75 100
d = (METERS)
NOTES: (See also Fig 49). Earth surface potential cp. referred to the ground grid voltage U, as a
function of distance d from the tower center. Distance of the conductor from the tower center is
25 m. (Source: CIGRE-Study Committee 36)
Fig 46
Conductive Interference in a Bare Metallic Conductor Embedded in
the Soil Caused by a Tower Ground Grid
115
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
M i M5
40 Ue
\\ 0
\.
\ \
250 400 m2
30
EARTHING SYSTEM \ \
10 iCrivE HEMISPHERE \ O F F I G 4 8 W'ITHOUT
~~ ~
\
\
8 rH
BURIED CABLE \
7 Mi
\
6
I
1
Mo
DISTANCE d FROM THE CENTER OF THE EARTHING SYSTEM (METERS)
I , 1 I 1 I f 1 1 1 I l l # I I I I 1
for Ma Mi M2 M3 M4 M5
Fig 47
Relative Potential of the Surface of the Earth in the Vicinity of Earth
Grids and in the Vicinity of a Tower Footing with Ring Electrode
116
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
-
-WITHOUT BURIED CABLE
18 -- WITH CABLE ACTING AS EARTH ELECTRODE
16 -
40 -
14 -
lo -
Pe a = 20m
40 m LEFT HAND DRAWING
10 - u, 100 rn I=40m
600 m 2-
0 1000 m
1 1 1 1 1 1 1 1 1 1 I I I I
2 4 6 8 10 12 14 16 18 20 10 20 30 40
x (METERS) x (METERS)
Fig 48
Conductive Interference Between the Earthing System of a Power Line
Tower and the Metallic Sheath of a Telecommunication Cable as
Influenced Conductor
117
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
(a) 1 = 40 m
(b) 1 = 100 m
Fig 49
Approximate Value A of the Current Absorbed and Discharged Per
Length by the Conductor Metallic Sheath of Cables Subject to
Interference
9.9 The Case of a Long, Noninsulated Conductor Within the Zone of In-
fluence and Subject to Interference. The potential a t the various points of
a long conductor subject to interference shows substantial differences, because
the currents flowing between the absorption range and the discharge range cause
considerable voltage drops. This problem is considered in other literature (see
bibliography, Section 13).
For instance, consider a telecommunication cable that, in the area where it
crosses under a power line, is embedded in the soil and has a noninsulated me-
tallic sheath. Outside the crossing area, the cable is suspended in air and has
a metallic shield. An equivalent diagram (Fig 50) takes into account the imped-
ance per length of the metallic sheath and shield.
The variable E in Fig 50 represents the earth potential of the nearest point
of the metallic cable sheath subject to interference (point 1 of the equivalent
circuit) under the condition of no current absorption in the metallic sheath. When
the metallic sheath of the crossing sheath is connected to the metallic shield of
the cable suspended in air on either side of the crossing, a current enters the
metallic sheath via the impedance Rel.
118
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
- Zb
CONDUCTOR SUBJECT TO
CONDUCTIVE INTERFERENCE
REMOTE EARTH
NOTE: Various publications (see bibliography, Section 13) show equivalent diagrams covering the
conductive interference on long conductor sections passing current-discharging power system earth
electrodes.
Fig 50
Circuits for Calculating Potential Transferred to Another Earth
Electrode
119
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT SM 367-1987
140
110
60
-4 -
-6
1 I 1 I I i
50 100 150 200 250 300 50 100 159 200 250 300
X (METERS) X (METERS)
P
CURVE R/km O.m
a IZI -+
OPTIONAL FINITE VALUE
b 6 + 16.7 or
100
C 1.32 + j1.23 I
or
100
d 0 OPTIONAL
Fig 51
Potential of a 600 m Long Influenced Conductor (According to Fig 48)
at 11w)o V Interfering Earth Electrode Voltage
121
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
Apart from the power station ground grid under consideration, assume there
are no other metallic conductors in the soil. At a distance x, which is more than
three times the radius of the station ground grid (modeled as a hemispherical
electrode), the potential of the earth surface is in effect raised with respect to
remote earth to the level
122
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
where
V(x)= earth potential with respect to a remote location, in V,
p = resistivity for uniform soil, in ohm-meters
x = distance from center of ground grid, in meters
(x 2 3r, r = station ground grid radius)
1, = rms station ground current, in amperes
For distances closer than three times the radius of the station ground grid, the
spherical electrode of Eq 25 can be modified for a disk-like electrode in uniform
soil, as illustrated in Eq 26.
pr, sin-'
V(x)= -
2nr
(f) (radians) (Eq 26)
where
r = radius of a circle equal in area to the grid, in meters
At a distance of three times the radius of the station ground grid, Eq 25 has
an inaccuracy of approximately 2% when compared to Eq 26. The closer one
approaches the station, the less accurate Eq 25 becomes, compared to Eq 26. At
a distance greater than three times the radius of the station ground grid, both
Eqs 25 and 26 will provide identical results.
Thus, to avoid confusion as to which equation to use depending on the distance
from the station, it is strongly recommended that Eq 26 be used at all times.
Eq 26 could be used directly if I, is known, but V(x)has often been related
to the station GPR.Derived from Laurent and Niemann formula (ANSI/IEEE
Std 80-1986 [31),
pr, + -
GPR = - d, (Eq 27)
4r L
where
r = radius of a circle equal in area to the grid, in meters
L = total length of buried conductor, in meters
Note that other expressions for GPR in terms of I, may be available.
In Eq 27, the first term accounts for the GPR of a solid circular plate electrode
of radius r. The second term provides a correction for the open mesh nature of
the grid with the relative correction approaching zero for very dense- grids
(L >> r). Combining Eqs 26 and 27 gives
V(x) -
--
GPR
0.64
(1 + 4 r / L )
sin-' (5) (radians) (Eq 28)
123
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
Fig 52
Determination of Zone of Influence Boundary for Power Stations
From ANSI/IEEE Std 80-1986 [31, the tolerable touch voltage is defined as
= (1000 + 1.5C(h,, K ) p,) 0.116/
Vtouchso fifor 50 kg body weight
= (1000 + 1.5C(hS,K ) p,) 0.157/ fifor 70 kg body weight
VtoUChgO
where
C = a reduction factor for derating the nominal value of surface layer resis-
tivity and is a function of h,, thickness of the crushed rock in meters, and
K, a reflection factor
p, = the resistivity of the surface material, in fl . m
t, = duration of shock current, in seconds
Assuming t, = t = power fault duration, in seconds, refer to Section 11:
C = 1 for crushed stone resistivity equal to soil resistivity
p, = soil resistivity beneath a workers feet, in
fl m
124
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 361-1981
10.0
5.0
4.0
I
v) 3.0
5
>
0
9
- 2.0
Y
I
Y
v,
Fig 52 (continued)
116 + 0.17 ps
Vt0UCh50 = (Eq 29)
v?
For different power fault durations, Eq 29 serves as a limit to define V ( x )in
Eq 28, that is,
= vt0UCh50
125
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
10.0
5.0
4.0
- 3.0
v)
2
5 2.0
-
-
Y
Y
v,
2 1.0
z
r
2
n
z
3
B
(3
Fig 52 (continued)
--
243.51
GPR V?
- 0.58 sin-' ($) (Eq 30)
r
therefore, x = (meters)
sin ( 243.5
0.58 q t GPR
)
(Caution: Eauation is in radians, not degrees.)
Note that & is defined as the distance from the center of the ground grid. The
zone of influence boundary from the edge of the grid is
126
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
10.0
5.0
4.0
Gi 3.0
3
0
5- 2.0
Y
Fig 52 (continued)
Distance from v
127
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
10. Summary of Mitigating and Reduction Factors
Applicable to GPR or Induced Voltages,
or Both
10.1 Introduction
10.1.1 The design and cost of special protection arrangements that must usu-
ally be applied to wire-line telecommunication facilities serving electric power
stations to ensure reliable and safe operation, are sensitive to the level of the
expected electrical environment. To provide the design engineer with informa-
tion that should be considered in the determination of practical values of GPR
or induced voltage, or both, certain modifying factors are discussed in this sec-
tion. The effects of longitudinal induction (see Sections 6 and 7) must also be
considered in the overall design.
129
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
10.2.4 High-voltage power systems usually have the capability for producing
the greatest ground fault current and usually have a higher X / R ratio, which
tends to produce a longer duration of dc offset. The higher X / R ratios, applicable
to the high-voltage transmission lines, can be considerably reduced by the in-
clusion of the terminal apparatus in the calculations for purposes of this guide.
The terminal apparatus may mean the transmission or distribution line ground-
ing networks (for both), fault current limiting devices, etc. High voltage sys-
tems, however, have the best system protection in terms of fault detection and
fast interruption time. The ground impedance will tend to be low because of the
large grid area of these power stations. In distribution systems some distance
from the inductive source, the X / R ratio is much lower than in high-voltage
systems and, consequently, a shorter transient duration is expected; but the fault
clearing time may be higher.
The X / R ratio to be used for dc offset calculations should be that as seen from
the fault location looking back into the power system, far enough to include the
reduction of the X / R ratio due to the reducing effects of the terminal apparatus.
10.2.5 The fault currents and the station ground grid impedance must be de-
termined accurately so that a true value of GPR can be calculated. Where fault
currents are higher (for example, 100 kA) and the station ground impedance is
low, inaccuracies even in the order of 10%in measuring or calculating station
ground impedance will result in critical errors in GPR calculations.
130
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
131
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
11. Communication Channel Time Requirements
11.1 Introduction. To give both reliability and economy of service to the cus-
tomer, electric power systems have evolved to a point in which large load centers
are served by multiple transmission lines, generators, and transformers. These
complex systems have special operating problems that require high-speed clear-
ing of short circuits and other abnormalities. This is accomplished by protective
relaying systems that must distinguish between normal load currents and fault
currents and then isolate the faulty section before equipment is damaged or the
entire system is disrupted.
133
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
11.2.3 Fault interruption for power fuses varies widely, from 0.1 s to several
minutes, since clearing time is almost solely dependent on the ampere rating
of the fuse and on the fault current magnitudes.
11.2.4 Air-break switches are not normally designed to interrupt faults. They
have opening times of 0.5-1.5 s.
134
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
Z3D 17 R
I
Z2D 12.5 fl
I
Z1D 8.5 R
ZONE 1C 8.5 fl ]
ZONE 2C 12.5 R 1
ZONE 3C 22 n I
IMPEDANCE RELAYS
ARE DIRECTIONAL
ZONE 1 HIGH SPEED (40 ms)
ZONE 2 WITH 20 CYCLE DELAY (333 ms)
ZONE 3 WITH 75 CYCLE DELAY (1250 ms)
NOTE: Fault clearing time equals relay operating time plus circuit breaker opening time (16-100 ms).
Fig 53
Typical Three-Zone Impedance Relay Reach
clearing in the last 10-15% of the protected line will be delayed by this amount.
Note that impedance relays are used for both phase and ground fault protection.
135
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
I
f
-
z
U CNrnULD
136
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
trip frequency and the fault will be cleared with high speed, the only additional
delay being that of the communication channel and the audio tone equipment,
generally about 4-16 ms. If the fault is external to the protected line (Fault 31,
even though the near-end relay may detect the fault and key its transmitter,
the far end relay at Breaker C, being directional, will not detect the fault, will
not trip Breaker C, and will continue to transmit a guard signal to block trip-
ping of Breaker D.
11.4.2 A phase comparison relaying system analyzes the location of a fault
by comparing the phase relationship of fault currents a t each end of a protected
line. Power line carrier or audio tone equipment is commonly used as a com-
munication channel. If the fault currents are in phase, the fault is considered
to be external to the protected line and a tripping will be blocked. If the fault
currents are out of phase, the fault is internal and tripping normally will take
place. In general, the fault is sensed and tripping is initiated in 8-20 ms. A
channel failure, reduced signal level, or noise a t the time of fault may cause
improper operation, either disallowing a necessary trip or causing an incorrect
operation, depending on the fault location.
11.4.3 Pilot wire relaying is a differential protection scheme designed to pro-
tect transmission lines by comparing the polarity of circulating current in a
metallic communication circuit to determine if the fault is internal or external
t o the protected line. An open or short circuit in the communication pair can
prevent a correct operation. However, independent monitoring systems are
available that can signal the system operator upon the occurrence of a com-
munications cable fault.
11.4.4 A transferred-tripping scheme is designed to transfer a trip signal from
a local protective relaying terminal to a remote terminal for the purpose of trip-
ping the remote breaker. Almost any type of conventional communication chan-
nel may be employed. Transferred tripping is used to protect lines and trans-
formers and for breaker failure protection. Direction, unsupervised tripping, upon
receipt of the trip signal by the receiver, places severe security requirements
on the communication channel and related equipment. For security, usually two
signals are sent in parallel and received in series. Transmitter-receiver time is
4-12 ms and channel time is 1-10 ms, with total tripping initiation times of
generally less than 16 ms. (See Fig 55.)
11.4.5 Backup systems must be provided to protect the power system from
the failure of a relay to detect a fault or a breaker to open.
11.4.5.1 Remote backup can be accomplished by using a Zone 3 imped-
ance relay set to protect its own line and all of the next line. (See Fig 53.) Proper
coordination with the adjacent line is obtained by using a time delay to give the
adjacent line breakers a chance to clear before the backup relay operates. With
this system, all faults not cleared in proper time will then be cleared in 1.5-3 s
by the backup relay. This has the disadvantage of being slow, and at times it
may be difficult for the Zone 3 impedance relay to distinguish between load and
far-end faults on the adjacent line.
11.4.5.2 Local backup for line faults is accomplished by using redundant
front-line relaying systems plus a breaker failure scheme. The OR logic of all
line relays is ANDed with an overcurrent fault detector for each circuit breaker
137
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
POWER
TRANSFORMER
I,
rz89 I+DC
<
>
BKRA
>:\;
< BKRC
TRANS I
.
- 1+ - - - - --+
TRANS2 -
POWER LINE CARRIER
TRIP
COIL
BKR B
-DC
Fig 55
Simplified Transfer Trip System
and connected to a timer to provide coordination. This scheme will detect the
failure of a circuit breaker to trip within a preset time-usually 5-8 cycles-
and open all other sources of fault current to the faulted element. Certain bus
arrangements, such as a ring bus, require a transfer trip system to open a re-
mote breaker, if high-speed fault clearing is required. This is particularly true
on EHV systems.
11.4.6 Automatic reclosing after a fault is used in most systems and must be
considered. Table 8 can be used as a guide. Generally, the higher the system
voltage, the faster the fault is cleared and the faster the breakers reclose, al-
though they may reclose fewer times.
11.4.7 Some EHV systems utilize single-phase tripping and reclosing. This
means the remaining phases remain energized and continue to carry load during
the normal reclose dead time. The imbalanced current that flows for this brief
interval (about 0.3-0.4 s) will generally not cause problems for communications
circuits.
11.4.8 Secure and reliable communications are necessary on permissive over-
reach, phase comparison, and transfer tripping. A channel failure, increase or
decrease in level, test tone, or noise a t the time of fault may cause improper
operation, either by causing the communication receiver to squelch and thereby
disallowing a necessary trip (for upwards of 2 s on some systems), or causing
an unwanted trip, depending on the data transmission logic. Since no fault de-
tector is used with a transfer trip system, an unwanted trip could occur any
time any of the above channel conditions exist, particularly on a single-channel
system.
138
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
Table 8
Typical Trip and Reclose Sequence
Clearing Dead Clearing Dead Clearing Dead Clearing Dead
kV Time Time Time Time Time Time Time Time
500
345 2-5~ 2 0 ~ 2-5~ stop
230
115 3-8~ 25 c 3-8~ 15 s 3-8c stop
69 4-40 c 0.5 s 4-40 c 15 s 4-40 c stop
34 4-60 c 0.5 s 4-60 c 15 s 4-60 c 45 s 4-60 c Stop
4/12/25 5-120~ 3s 5-120 c 15 s 5-120~ 45 s 5-120~ Stop
1 c (cycle) = 16.67 ms
NOTES:
(1) Tripping by Zone 2 relay can add 300-400 ms to the 115-500 kV times.
(2) Tripping by time-overcurrent ground relay could extend times to 1.5 s on voltages below
230 kV.
(3) Dead time is followed by closing of the breaker.
139
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
12. Administrative Guidelines
12.2 The most accurate data can be obtained by directing the proper questions
to the correct engineer. The following are notes and questions that the telephone
protection or telecommunications protection engineer should ask the power util-
ity engineer in order to obtain a realistic value of the GPR:
(1) The telecommunications protection engineer should make certain that the
appropriate engineer in the power utility has been contacted. Such a person will
typically be called a Stations or Systems Planning Engineer with respon-
sibilities of determining fault current levels, or the amount of current injected
into various parts of the system when faults to ground occur. For ground grid
impedance values, this engineer might either be a Planning, a Substations,
or a Transmission Line engineer. There may, however, be personnel in the
power utility-for example, a Power Systems Communication Department-who
are also responsible for inductive coordination studies, and who are familiar
with all aspects of these studies. One should not contact design engineers who
will usually give worst-case projected values. Determine if the person contacted
has the responsibility for station specifications of the power station in question.
If not, seek out the individual having such responsibility.
(2) Next, obtain the station ground impedance value to remote earth, the
maximum fault current, and hence the GPR. If the GPR given is the product of
the first two numbers, it is probably too high, as not all the fault current returns
through the ground grid. One should ask what part of the total fault current
actually flows from ground through the grid. This is usually a complicated ques-
tion involving the use of the computer.
(3) Next, inquire if the total ground grid impedance ZsCT was calculated or
measured, and if the overhead ground wires and distribution neutrals were con-
141
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
SM 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
nected when the impedance was determined. A calculated value may be based
upon a worst-case design estimate and may be inaccurate. Unfortunately, a de-
sign engineer may be depending on inaccurate soil resistivity figures. One should
particularly be insistent on an estimate with the distribution neutral and over-
head ground wires connected, as this can reduce ground grid impedance ZsCT
by as much as an order of magnitude.
There is no substitute of course for a real measurement, so if one can obtain
measured values of the real impedance one should do so. However, beware of
stated or calculated values below 1 R. For example, most small test sets should
not be trusted below 1R. ANSI/IEEE Std 81-1983 [4]illustrates accurate meth-
ods of testing the station ground. Questions concerning what methods, test pro-
cedures, and equipment were used to measure the ground grid impedance should
be asked to establish credibility in the data.
(4)Next, the validity of fault current levels should be established. Fault cur-
rent estimates should be based on a L-G fault. If the estimate is for a L-G de-
veloping into a 2L-G phase fault, a worst case, which rarely occurs, is assumed
and should be discarded in favour of the L-G fault. The L-G figure may include
a large dc offset value. If so, a reduction in the dc offset value may be appro-
priate, as statistical evidence shows that dc offsets are usually not very severe.
The value of the GPR should be given in the rms symmetrical value. Peak or
dc offset factors can be applied later to the GPR calculation by agreement. Next,
one should ask the engineer for what fault location the GPR was calculated. In
most cases a worst GPR is produced by a fault that occurs a few spans outside
the station fence.
12.3 Planning studies are usually for periods of five to twenty or more years
ahead. The fault studies are based on ultimate figures, but the station may
never reach this capacity, or may reach this ultimate value many years hence.
Decide for what length of time (say fifteen years) the protection design will be
valid and obtain a fault current prediction for this period.
12.4 The telecommunications protection engineer should now be able to ask for,
and receive, a realistic GPR. Such request for information and answer should
be put in writing.
12.5 The electric power utility creates the GPR and induction environment and
is therefore responsible for defining it. The telecommunication utility protection
engineer must complete the protection designb) based on reliable data supplied
by the power utility. The motivation for an accurate and reasonable assessment
of the GPR or induced voltage or both, is (1)economic, (2) increased reliability
of telecommunications services and (3) increased personnel and plant safety. In
order to arrive at a realistic assessment of the assumed magnitude of interfering
voltages, a very high degree of mutual understanding and cooperation is nec-
essary.
12.6 Large power utilities have the engineering capability to provide either by
calculation or measurement, or both, accurate values for the inducing current
142
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
and the net earth return portion of the fault current. Also, most large utilities
can provide accurate values for ground grid impedance and hence the GPR. The
degree of accuracy required and the economics related to determining the ap-
propriate value of GPR particularly for very large stations are, of course, sub-
jects for negotiation. Many small power utilities, private designers, or contrac-
tors do not have this level of expertise and may elect to use outside specialized
consultants.
143
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
13. Bibliography
145
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
146
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
147
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
148
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
149
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
[B741 THAPAR, B. and MADAN, S. K. Current for Design of Grounding Sys-
tems. IEEE/PES 1984 Winter Meeting.
[B751 TIBENSKY, M. S. and PERFECKY, L. J. Methods for R M S Symmetrical
Station Ground Potential Rise Calculations for Protection of Telecommunications
Circuits Entering Power Stations. IEEE Paper 81 SM 392-0, IEEE Transactions
on PES, Dec 1981.
[B761 Transmission Line Reference Book, 345 kV and Above. Electric Power Re-
search Institute, 1975.
[B771 VALJUS, J. and SARMANTO, R. Practical Earthing Measurements of Large
Rural and Urban Substations. CIGRE 1984-36-04.
[B781 VELAZQUEZ, R., REYNOLDS, P. H., and MUKHEDKAR, D. Earth-Re-
turn Mutual Coupling Effects in Ground Resistance Measurements of Extended
Grids. IEEE/PES 1982 Summer Meeting.
[B791 WAGNER, C. F. Decrement of Short-circuit Currents. Electric Journal,
March, 1933.
[B801 WAIT, J . R. Electromagnetic Waves in Stratified Media. New York:
MacMillan Company, 1962. (An in-depth theoretical treatment of the basic cou-
pling mechanism and electromagnetic propagation that may be applied to 60 Hz
type problems.)
[B811 WEEDY, B. M. Electric Power Systems. New York: John Wiley & Sons,
2nd edition, 1967.
[B821 WILLHELM, R. and WATERS, M. Neutral Ground in High Voltage
Transmission. New York: Elsevier Publishing Company, 1956.
[B831 YU, L. Y. M. Determination of Induced Currents and Voltages in Earth
Wires During Faults. Proceedings of the IEEE, vol 120, no 6, June 1973.
150
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Appendix
Mutual Impedance Calculations
(This Appendix is not a part of ANSI/IEEE Std 367-1987, IEEE Recommended Practice for De-
termining Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault.)
Al. General
A l . l This Appendix provides the program listing and user instructions for
calculating mutual impedance using the extended complex image formula on a
small programmable calculator.
A1.2 The calculator programs in this Appendix have been developed for use
with the Hewlett-Packard model 67 or 97 calculator (HP-67/97).
A2.2 The program provides the user with engineering estimates of external
mutual impedance between conductors (1)and (2).
The program outputs are lZ121, L Z12,R l z , and X,,. R l z and X12are the re-
sistive and reactive components of external mutual impedance. If the Xlz and
h inputs are in meters, the output impedances 1Z121,IR12(,and (Xl,I are ex-
pressed in ohms per kilometer. If the inputs are in feet, the output impedances
are in ohms per kilofoot.
151
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
CONDUCTOR (1)
CONDUCTOR (1)
PI CONDUCTOR (2)
4
1
4i P
Fig A1
Configuration for Mutual
P
Fig A2
91
CONDUCTOR (2)
hi
Fig A3
Configuration for Mutual
Impedance-Examples 2(b), 2(c)
Since the program is designed to be used with either metric or English data,
the units option must be set in Step 1before any data is entered in Step 2. When
using meters, press to begin; when using feet, press m,a.
The mutual imped-
ance outputs then have units of either ohms/kilometer or ohms/kilofoot in ac-
cordance with the input data and the option chosen. Note that Steps 4 through
7 may be performed in any order, omitting those results not desired.
A numeric prompt is provided for each input parameter. In addition to re-
152
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT SM 367-1987
minding the user which data is required, the prompt specifies the appropriate
register for input data. This feature allows individual input parameters to be
changed without re-entering any previous unaltered data.
The program variables are stored in the following registers:
Register Input Parameter
1 hl-vertical conductor height (meters or feet)
2 h2-vertical conductor height (meters or feet)
3 xlz-horizontal separation (meters or feet)
4 p-earth resistivity (meter-ohms)
5 f-frequency (hertz)
To change input data, simply store the new number($ in appropriate regis-
ter(s) and go on to Steps 4, 5, 6, or 7 depending on the output desired. When
making changes in input data, the dimensional units (m or ft) must be consis-
tent with the previously chosen option. If an execution error should occur (due
to faulty data such as p = 0, f = 0, or hl = 0 and x12= 0) one must return to
Step 2 and re-enter all data.
A3.2 Examples of Mutual Impedance Calculations. The following ex-
amples are provided for tutorial and verification purposes. Figure A1 shows the
configuration for Examples l(a) and (b), Fig A2 shows the configuration for Ex-
ample 2(a), and Fig A3 for Examples 2(b) and (c).
Example 1. Aerial Power and Telephone Cable (English Units Option)
Parameter UC) Ub)
hi (ft) 50 50
h2 (ft) 25 25
x12 (ft) 100 500
p (m . ohms) 500 500
f (Hz) 60 60
l(a) Enter location data:
Input Key(s) Display
(English) mm 1.
hl 50, IR/sl 2.
hZ 257 (R/SI 3.
x12 100, IR/sl 4.
P 500, IR/sl 5.
f 60, IR/sl lZl21 = 0.096 R/kft
a LZ,, = 79.3"
Dl R12 = 0.018 fl/kft
IEi XI2 = 0.094 R/kft
153
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
Example 2. Aerial Power and Buried Telephone Cable (Metric Units Option)
Parameter 2(a) 2(b) 2(c)
hl (m) 10 10 10
h2(m) -1 10 10
x12(m) 0 15 15
P(m. R) 500 500 100
f (Hz) 60 60 60
154
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
155
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
Data:
EXTERNAL MUTUAL IMPEDANCE PROGRAM
INPUT OUTPUT
INSTRUCTIONS DATNUNITS DATNUNITS
I n s e r t c a r d (programmed p e r T a b l e 1A)
1.
2.
3.
4.
5.
Z,,lO/kft
Z !,,lO/km kft
E v a l u a t i o n of 12
I
E v a l u a t i o n of '12 I
E v a l u a t i o n of K12
I
E v a l u a t i o n of '12 O/km kft
NOTES :
S t e p s 4 throu_eh 7 may he Izerfarmed in any n r d e r ,
hnw resiilts a-
I
Fig A4
User Instructions
156
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
Table A1
External Mutual Impedance Program-HP-67/97
LOC ENTRY KEY CODE COMMENT LOC ENTRY KEY CODE COMMENT
157
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Table A1 (continued)
LOC ENTRY KEY CODE COMMENT LOC ENTRY KEY CODE COMMENT
- 24
125 2 02 173 LN 32
726 X - 35 774 + - 55
127 XSY -41 175 RCLG 36 06
128 +R 44 176 X - 35
129 P&5 16-51 177 STOE 35 15
130 RCLS 36 09 178 RCLD 36 14
131 X 53 179 e S 76-51
132 + - 55 780 FO? 16 23 00
133 +P 34 787 GT06 22 06
134 FttS 16-51 782 RCLO 36 00
135 XeY -41 183 X - 35
136 STO9 35 09 184 STOD 35 14
137 XF?Y -41 185 RJ -31
138 ST08 35 08 186 RCLO 36 00
139 RCL7 36 07 187 X - 35
140 X2 53 188 STOE 35 15
141 X - 35 189 RCLD 36 14
142 l/X 52 190 *LBL6 27 06
143 X2 53 797 +P 34
144 8 08 192 STOB 35 72
145 X - 35 193 RJ -31
746 3 03 194 STOC 35 13
747 - - 24 195 RTN 24
148 RCLS 36 09 196 R/S 51
158
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
Index
159
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
160
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSIIIEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
H
G Height, line, 71-72, 75-76, 78-79, 82,
Gas lines, 17, 112 85-86, 94
Generating stations, 107 Hewlett-Packard 67/97 calculator, 151
Generators, 27-28, 30, 130, 134 High-voltage, direct-current (HVDC),
Geomagnetically induced currents 22
(GIC), 24, 52 High-voltage (HV) bus fault GPR, 32-
Ground conductors 38, 40-44
buried, 16, 89, 129 High-voltage (HV) line fault GPR, 39-
overhead, 16, 18-19, 27-28, 30, 32- 40
33,36-37,39-41,43-44,68,87- Horizontal separation, 68, 72, 74-79,
88, 90, 109, 111-112, 114, 131, 86, 94, 151
141- 142 HV (high-voltage) bus fault GPR, 32-
Ground faults. See Faults 38, 40-44
GPR. See Ground potential rise HV (high-voltage) line fault GPR, 39-
Ground grid, 109-110, 114-116, 122- 40
127, 130 HVDC (high-voltage, direct-current),
Ground grid impedance, 16-19,27-28, 22
65, 99-100, 129
calculating, 16-18
information about, 19, 141-143
measuring, 16-18 I
reducing with chemicals, 131 Impedance, footing, 16, 18, 32, 37, 39-
Ground potential rise (GPR), 15-16, 19, 40, 44, 113, 129
27-65 Impedance, ground grid. See Ground
administrative guidelines, 141- 143 grid impedance
161
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
162
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
P
Parallel (uniform) exposure, 71-74, 76- R
77 Radial feeders, 134
Personnel safety, 13, 22, 107, 113, 124- Railroad rails, 16, 18, 27, 39, 68, 87,
125, 127, 142 109, 112-113, 129
Per unit system (PU), 23-24 Reactance, 24, 28, 31, 41, 65, 71, 74-
Phase angles, 133 76, 78, 90, 130
Phase-comparison relays, 137-138 Reclosers, 51
Phase faults. See Faults Reduction and mitigating factors, 22,
Phase-to-phase faults, 15. See also 64, 129-131
Faults References, 25-26
Pilot wire relays, 137-138 Relays, 15, 20-22, 45, 51, 133
Pipes, 16-18, 27, 39, 68, 87, 108-109, automatic reclosing, 138-139
112-113, 122, 129, 131. See also backup, 137-138
Buried ground conductors differential, 134, 138
Poles, 16, 18, 88. See also Towers fault pressure, 134, 138
Polyethylene-jacketed telecommunica- frequency, 134
tion cables, 90 impedance, 134-136
Positive-sequence fault currents, 31-33, independent timing, 134
35-36, 39-41, 88 instantaneous-overcurrent, 134
Potential contour survey, 111-112 lockout, 138
Power faults. See Faults phase-comparison, 137- 138
Power fuses, 51, 133-134 pilot wire, 137
Power line shielding, 34 thermal, 133-134
Power stations, 13, 15, 20. See also time-overcurrent, 134, 138-139 . E
163
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
Std 367-1987 ELECTRIC POWER STATION GROUND POTENTIAL RISE
164
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.
ANSI/IEEE
AND INDUCED VOLTAGE FROM A POWER FAULT Std 367-1987
165
Authorized licensed use limited to: ABB Inc. Downloaded on October 23,2012 at 20:13:23 UTC from IEEE Xplore. Restrictions apply.