11 KV Ar
11 KV Ar
3.0 IR Value:
Tested By Witnessed/Approved By
CIVIL CONTRACTING CO (CIVILCO) .LLC RURAL AREAS ELECTRICITY CO.SAOC
Sign: Sign;
5.1 MMI:
PROTECTION (ON/OFF) ON
EARTH FAULT (ON/OFF) ON
SENSITIVE E/F (ON/OFF) ON
CURRENT UNBALCNE (ON/OFF) ON
AUTO RELOSING (ON/OFF) ON
HOT LINE (ON/OFF) OFF
ACTOVE GROUP (1/2/3/4) Active Group-1
Function Setting
OVER CURRENT
OC1- Phase Low Set time delayed
Over Current Protection Enabled.
Type of TCC IEC SI
Pick up Current(Ip), A 150 A
TMS 0.1
EARTH FAULT
Earth Fault Protection Enabled
Type of TCC IEC SI
Current Setting 15A
TMS 0.05
SENSITIVE EARTH FAULT
Sensitive Earth Fault Protection (DT) Enabled.
Current Setting 5A
Tripping Time 5 sec
CURRENT UNBALANCE
Current unbalance protection (DT) Enabled
Current Setting 0.4 A
Tripping Time 10 sec
AUTO RECLOSER
Number of Trips to lock out for IDMT OC, IDMT EF 2
Number of Trips to lock out for SEF, CU 1
Reclosing Time 180 Sec
Tested By Witnessed/Approved By
CIVIL CONTRACTING CO (CIVILCO) .LLC RURAL AREAS ELECTRICITY CO.SAOC
Sign: Sign;
CURRENT INJECTED Pick Up-A Drop out-A Tripping Time ms Tripping Time ms
@ 30 A Injection @ 75 A Injection
R-Phase 16 13 521 218
Y-Phase 16 12 519 214
B- Phase 16 12 528 217
Tested By Witnessed/Approved By
CIVIL CONTRACTING CO (CIVILCO) .LLC RURAL AREAS ELECTRICITY CO.SAOC
Sign: Sign;