Motor Start Analysis

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 19

Motor

Start

Indriatmoko
Overview

2
4
5
6
7
Video Principle Motor Induc>on

8
Dierence Motor Induksi dengan
Motor Synchron

9
OBJECTIVE
TO KNOW LOADFLOW CHARACTERISTIC
DURING MOTOR START
ENSURE MOTOR CAN BE STARTED
ISTILAH BARU
!
Sta$c Model Star$ng Device
Dynamic Model DOL
Y/D
SoXStarter
VSD
Auto Transformer
Resistance
Capaci>ve
Design Criteria
Motor can be started
Drop Voltage on motor side <20% rated motor
Drop Voltage on MCC <10%
Drop Voltage on Generator Bus <7%

12
ETAP SIMULATION
ENGINEERING KNOWLEDGE

2
INPUT DATA
3
1 ETAP STAR 4 RESULT
MODULE

13
INPUT DATA YANG DIPERLUKAN
ALAT BANTU START
DOL
Y/D
SOFTSTARTER
ADDITIONAL VENDOR DATA MOTOR
LRC
STARTING POWER FACTOR
WAKTU START TIME : NO LOAD & FULL LOAD
ANALISIS
DROP VOLTAGE
KVAR VALUE
EQUIPMENT RATING
STUDI CASE
1. Determine biggest motor for each MCC
2. Analysis all the motor using DOL start
method
STATIC STUDY
Impact to Power system
Drop Voltage
Generator capability limit evaluasi
Determine Star>ng method of the Motor

17
DYNAMIC STUDY
Determine motor can be started or not
Retrot
Determine star>ng method

18
PROBLEMSOLVING
Star>ng device
Addi>onal capacitor bank
Upgrade equipment ra>ng/reduce motor LRC
Tap Trafo & AVR
Re-Congura>on SLD